Maintenance
Coil Eliminator Removal
The coil eliminators are comprised of a series of PVC pack assemblies, oriented
to strip water from the air prior to leaving the fluid cooler. They are packed
tightly to ensure no water escapes.
Eliminatorsheetscanbeverysharpandcouldcutskinifproper
protection is not used. Always wear gloves and sleeves when han-
dlingeliminatorpacks.
To remove the eliminators, place both hands on the eliminator face and push
up, this will indicate where one assembly stops and another starts. Push a
single section up until it hits the top of the metal retaining channel
(1). Push
the bottom side of the pack
down inside the fluid cooler
(2). Turn the pack sideways
and remove the eliminator
(3). Repeat this procedure
for other packs to gain
necessary access.
Proper eliminator pack replacement is essential to operation. Incorrect instal-
lation may result in excessive drift rates and fan inefficiency! To ensure packs
are reinstalled in the correct orientation, it is recommended that one pack is left
in its original location inside the fluid cooler as a reminder of pack orientation.
Place packs in the tower in the order they were removed. Packs should nest
tightly with each other, leaving a level surface with no gaps.
Caution