User manual

16
Fan cycling limits:
Considering the normal fan and motor sizes utilized on MH Fluid
Coolers, anticipate that approximately4 to 5 starts perhour are
allowable.
If your fluid cooler is equipped with a two-speed motor(s), you will enjoy
greater opportunity for process temperature control. When the process
fluid temperature becomes too cold, switching the fan to half-speed will
cause the cold process fluid temperature to rise—stabilizing at a tempera-
ture a few degrees higher than before. With a further reduction in fluid
temperature, the fan may be cycled alternately from half-speed to off.
Donotstartthemotormorethanfourtovetimesperhour(each
lowspeedstartandeachhighspeedstartcountasonestart).
For greater insight on process fluid temperature control, please read
“Cooling Tower Energy and its Management”, Technical Report
#H-001-A, available at spxcooling.com.
Pump cycling limits: Marley does not recommend the recirculation
water pump(s) be cycled to control process fluid temperature. It is recom-
mended that while process fluid is being circulated through the coil the
fluid cooler recirculation water system always be in operation. Cycling
the recirculation water pump(s) may lead to premature scaling of the coil
surface.
Dampers: If equipped, the positive closure damper system is designed
to help prevent heat loss from the coil due to air movement caused by
convection or wind conditions when both the fan and pump are off.
Upon start-up of the fluid cooler fans, the damper actuator is energized
and rotates the damper assembly blades open. The actuator should be
wired into the control circuitry of the fan motor. Upon system shutdown
the damper actuator is de-energized and the spring return actuator returns
the damper blades to the closed position.
Ifthedampersareequippedwithanautomaticelectricactuator,
the actuator electric motor controller will include a 115-volt AC
space heater in accordance with the SPX Cooling specification.
The space heater is to be energized at all times whether actuator
Operation
Note
Note
Note