User manual
14
    Some trial  and  error  adjustment of  the  float  valve  may  be required  to 
balance the makeup water with tower operation. Ideally, the float valve 
setting will be such that no water is wasted through the overflow at pump 
shutdown. However, the water level after pump start-up must be deep 
enough to assure positive pump suction.
5.   Open the valve on the tower bleed line and adjust bleed to the recom-
mended rate. See Water Treatment section on page 20.
6.   Continue pump operation for about 15 minutes, after which it is recom-
mended that the water system be drained, flushed and refilled.
7.  While operating the recirculating water pump(s) and prior to operating 
the fluid cooler fan, execute one of the two alternative biocidal treatment 
programs described in the following:
•  Resume treatment with the biocide which had been used prior to shut-
down. Utilize the services of the water treatment supplier. Maintain the 
maximum recommended biocide residual (for the specific biocide) for 
a sufficient period of time (residual and time will vary with the biocide) 
to bring the system under good biological control or
•  Treat the system with sodium hypochlorite to a level of 4 to 5 mg/L 
(ppm) free chlorine residual at a pH of 7.0 to 7.6. The chlorine residual 
must be  held at  4 to  5 mg/L  (ppm) for  six hours,  measurable with 
standard commercial water test kits.
    If the fluid cooler has been in operation and then shut down for a dura-
tion of time and not drained, perform one of the two previous biocidal 
treatment programs directly to the fluid cooler storage vessel (collection 
basin, drain down tank, etc.) without circulating stagnant water over the 
cooling tower fill or operating the cooling tower fan.
    After  biocidal  pretreatment  has  been  successfully  completed,  cooling 
water may be circulated over the tower fill with the fan off.
    When biocidal treatment has been maintained at a satisfactory level for 
at least six hours, the fan may be turned on and the system returned to 
service. Resume the standard water treatment program, including biocidal 
treatment. 
Operation