Installation Instructions
//Data2/MarineSync-Sales Marketing/Approved Technical Docs/RUM
11
Reconnect conductors to the buss bar and secure.
Connect the brown/blue leads from the Current Transformer to the RUM Transponder – Terminal 13 &
14. This connection is not polarity specific.
Ground Fault CT
Connecting Ground Fault Indicator Light (LED) – Optional
Only use MarineSync supplied LED Indicator Light.
Panel mount the LED in a visible location on the exterior of the pedestal.
Connect the positive lead of the LED to the “PWR” terminal of the RUM Transponder – Terminal 5
Connect the negative lead of the LED to the “LED” terminal of the RUM Transponder – Terminal 16
Light will only illuminate when RUM transponder senses High ground fault current. Contact MarineSync
for help configuring Ground Fault levels.
Panel Mount LED