Installation manual
LOCATION 
Corners 
shoutd 
be 
considered where 
space 
is 
limited 
or 
at 
a 
premium. 
A 
corner-installed fireplace can 
make 
use 
of 
space 
that 
may 
not normally 
be 
used 
(see 
Figure 
1). 
PROJECTION 
FIGURE 
1 
LOCATlON 
AND  INSTALLATION 
. 
A 
fireplace 
may 
be installed flush with 
the 
linished wall 
or 
projecting any  distance  into the  room.  Flush 
installation is  recommended for 
srnoolh 
or 
thin  wall- 
facing materials.  By installing 
the 
fireplace to project 
into 
the room, 
a 
shallower cavity is required 
fo 
contain 
the 
fireplace; thicker natural materials, such  as  field 
stone, 
can then be used for 
face 
material. 
A location that  requires cutting the  least number 
of 
joists,  roof  rafters,  and floor  joists  will reduce costs 
and 
make installation easier.  This 
may 
mean moving 
only one 
or 
two 
inches 
from the  selected ideal 
loca- 
tion. 
Any 
location 
selected must allow adequate room 
to  accommodate the  fireplace  and  framing 
dirnen- 
sions 
shown 
in Figures 
4, 
5 
& 
6. 
SEE 
FIGURE 
1 
FOR 
LOCATION 
EXAMPLES. 
WHAT- 
EVER 
LOCATION 
IS 
CHOSEN, 
ACCESSIBILITY  TO 
OUTSIDE  COMBUSTION  AIR 
SHOULD 
BE 
CONSID- 
ERED. 
(SEE 
PAGE 
5). 
Do 
not 
place 
the 
fireplace on 
soft-surfaced 
floor 
cov- 
ering 
such 
as 
carpeting. 
The 
mounting 
surface 
must 
be 
flat 
and 
hard 
(such 
as 
plywood, 
wood 
flooring, 
particle 
board 
or 
any 
other  hard-surfaced material), 
and 
evenly 
support 
the 
total 
base 
of 
the 
fireplace. 
A 
raised platform 
may 
be 
used 
to 
support 
the 
fireplaces. 
When 
a 
fireplace 
is 
installed on 
a 
combustible floor,  a 
non-combustible  hearth extension 
must 
be 
provided 
to 
protect the floor in front 
of 
the opening.  (Refer to 
Hearth 
Extension, 
Pages 
15 
& 
16). 
CLEARANCES 
A 
fireplace must not  be installed closer than 
20 
inches 
to 
any 
unprotected 
combustible 
wall perpendicular 
to 
the door  opening (Figure 
3). 
. 
When 
a 
24" 
W 
x 
36" 
H 
wall shield made from 
a 
non- 
combustible 
inorganic  materia! 
with 
thermal 
conduc- 
tivity 
K 
of 
.54 
or  less  is used, 
clearance 
may 
be 
reduced to 
14 
inches. 
See table (Figure 
36 
Page 
15) 
for 
common  materials  which 
can 
be 
used  as 
wall 
shield. 
. 
When 
installed 
in 
accordance 
with 
the  instructions 
given 
in 
this 
manual, 
the 
fireplace system  may  touch 
combustible materials at 
the 
bottom. 
2" 
clearance is 
required 
on 
sides 
arid 
back 
of 
fireplace, 
except 
at 
the 
nailing flange, 
where 
clearance 
is 
0". 
The 
chimney 
system 
requires 
2" 
minimum air  space. 
. 
Combustible  materials should 
not 
be 
in contact with 
mounting flange 
of 
upper frame. 
WARNING: 
DO 
NOT 
PACK 
REQUIRED 
AIR 
SPACES 
WITH 
INSULATION 
OR 
OTHER 
MATERIALS. 
1 
2" 
MIN. 
NAlLlNG 
RANGE 
FIGURE 
2 










