Specifications
30259-0-0212Page 18
DIRECT VENT COLINEAR VENT EXAMPLES
Note:Exhaustmustbea
minimumof3inchesabove
airintakeinlet.
Max Vent Run - 40 ft. Equivalent With Three (3) 90° Elbows
Special Note: The vent terminal 90° elbow and rst 90° elbow
off back of the fireplace, when within 6” (15.2 cm), do not con-
tribute to the overall vent length measurement. For each 45°
elbow installed in the horizontal run, the length of the hori-
zontal run MUST be reduced by 1.5 feet (45 cm). This does not
apply if the 45° elbows are installed on the vertical part of the
vent system. Reduce the length of the horizontal run 3 feet
(91.4 cm) for every 90° elbow.
6’
5’
10’
10’
SINGLE FLUE ADAPTER
MODEL PVVK-FC
CO-LINEAR DIRECT VENT ADAPTER
MODEL PVCA
FIRST 90
DOES NOT GET COUNTED
WHEN WITHIN 6” (15.2cm)
OFF BACK OF HEATER
° ELBOW
90° ELBOW
3 FEET
90° ELBOW
3 FEET
CO-LINEAR TRANSITION
MODEL PVCT
OPTIONAL
VERTICAL TERMINA
TION CAP
MODEL PVVTC
PTRAP
H = 5’ + 6’ = 11’
V = 10’+ 10’= 20’
(3) 90° = 9’
TOTAL= 40’
SIDE VIEW
3” MIN.
12” MIN.
FLAT ROOF
3” MIN.
12” MIN.
EXHAUST
AIR INTAKE
EXHAUST
AIR INTAKE
SLOPE
SLOPE
Figure 15
Calculation example of vent run maximum 40 feet
Figure15 displays atwo-pipeinstallation. Because thedistance
from the replace to the rst elbow is more than 6 inches, the
equivalentlengthallowancefortherst90°elbowmustbeadded
tothetotalventlength.Theequivalentlengthofthesecond90°
elbow also needs to be added to the total length. The third el-
bowalsoneedstobeincluded.TheequivalentlengthofthePTrap
doesnotneedto be added since it is the termination.The total
horizontalventlengthoftheuesystemis11feet,andthetotal
verticallengthis20feet.Thethree90°elbowsareequivalentto9
feet,bringingthetotalto40feet.
Note:Theexhaustmustbeaminimumof3inchesabovetheinlet
airpipe.Theuemustbeatleast12inchesfromtheroofline,and
itisrecommendedtobeatleast12inchesabovethemaximum
expectedsnowlevelasindicatedinFigures7,9,13,14,16and
20.
Note: Onhorizontalruns,aP.V.C.supportclampneedstobein-
stalledevery 3feet.Do notallow “sags”inhorizontal ventruns;
waterwillsettleinthepipe.
When installing a colinear horizontal, the minimum vent length
protrudingfromtheoutsidewallis6”(15.2cm)forairintakeand9”
for exhaust. See Figure 16.
Note:Horizontaldischarge90°elbowmustbepointeddownward.
SeeFigure16.Allhorizontalrunsrequireeithera1/4”perfootrise
toruncondensationbacktothefireplace,ora1/4”perfootdown-
wardslopetoruncondensationawayfromthefireplace.
Note:AllPVCventrunpipingcanbepurchasedatalocalhard-
warestore.Schedule40PVCpipeshouldbeusedandcemented.
PVCAHorizontalColinearDirectVentAdaptor,PVVTCCap,PV-
VK-CFA Flex Kit and PVVK-SH Horizontal VentAdaptor Kit are
availablefromEmpireComfortSystems,Inc.
In both vertical and horizontal colinear direct vent applications,
acolineartransitionplatemodelPVCTcanbeusedtominimize
clearancesbetweenintakeandexhaustpipes.
Forhorizontalcolineardirectventing,exhaustandintakeair,cap
pipeswith90ºelbows,pointeddownward.
Note:Iftransitionplate(modelPVCT)isused,themeasurement
forcentertocenterofthepipeswillbe2.5”.Ifthetransitionplate
(modelPVCT)isnotused,themeasurementforcentertocenter
ofthepipescanbe3”to24”maximum.
9”
MIN.
MIN. 2”
6” MIN.
3” MIN.
12" MIN TO GRADE
(RECOMMENDED 12"MIN.
TO MAX EXPECT SNOW LEVEL)
Figure 16