Specifications
30259-0-0212 Page 17
COLINEAR TRANSITION VENT KIT
TheColinearTransitionKit(PartnumberPVCT)isavailableand
can be used to secure the ue and inlet pipes from the Mantis.
Whenventingvertically, theexhaust pipe termination must bea
minimumof3inchesabovetheairinlet.
TheuecanbeterminatedwithaPTraportwo90°elbows.The
VerticalTerminationCap(PartnumberPVVTC)canalsobeused
toterminatetheuepipewhenusingtheColinearTransitionKit.
AIR INTAKE
PTRAP OR290° ELBOWS
SUPPLIED BY INSTALLER
TRANSITION PLATE
PVC CEMENT
PVC CEMENT
OUTDOOR SEALER REQUIRED
OPTIONAL
TERMINATION CAP
3” MIN.
REQUIRED HEIGHT IS 12” MINIMUM.
IT IS RECOMMENDED TO BE 12” ABOVE
THE MAXIMUM EXPECTED SNOW
LEVEL.
AIR INTAKE
PTRAP OR290° ELBOWS
SUPPLIED BY INSTALLER
TRANSITION PLATE
PVC CEMENT
PVC CEMENT
OUTDOOR SEALER REQUIRED
3” MIN.
EXHAUST
PTRAP OR 2 90° ELBOWS
SUPPLIED BY INSTALLER
REQUIRED HEIGHT IS 12” MINIMUM.
IT IS RECOMMENDED TO BE 12” ABOVE
THE MAXIMUM EXPECTED SNOW LEVEL.
Installation of the Colinear Transition Plate
1. Attachthe plate to chimney chase, atroof,oroutside wall
withfour(4)screws.Useoutdoorsealanttosealthetransition
platetothesurface.
2. Cut inlet air pipe and ue exhaust pipe to correct lengths.
Forverticalterminationsthroughtherooforchimney,theair
intake and exhaust pipe termination must be a minimumof
12 inches above the roof line. It is recommended that the
airintakeand exhaustpipeterminationbe12 inchesabove
themaximumexpectedsnowlevel.SeeFigures13and14.
Whenventingvertically,theexhaustpipeterminationmustbe
aminimumof3inchesabovetheairintake.Alsorefertolocal
codes.Forhorizontalterminationthroughoutsidewalls,the
minimumpipelengthis9inchesforexhaustpipetermination
and6inchesfortheairintake.
3. Attachtheueandinletairpipestothetransitionplate.Use
theappropriateprimerandcementtopermanentlybondthe
jointsandthepipestothetransitionplate.
Figure 13
Figure 14
Available from Empire Comfort Systems, Inc.
Colinear Transition Plate
Note:Mustmaintainaminimum3”be-
tweenexhaustoutletandairintake.