Specifications

30259-0-0212 Page 17
COLINEAR TRANSITION VENT KIT
TheColinearTransitionKit(PartnumberPVCT)isavailableand
can be used to secure the ue and inlet pipes from the Mantis.
Whenventingvertically, theexhaust pipe termination must bea
minimumof3inchesabovetheairinlet.
TheuecanbeterminatedwithaPTraportwo90°elbows.The
VerticalTerminationCap(PartnumberPVVTC)canalsobeused
toterminatetheuepipewhenusingtheColinearTransitionKit.
AIR INTAKE
PTRAP OR290° ELBOWS
SUPPLIED BY INSTALLER
TRANSITION PLATE
PVC CEMENT
PVC CEMENT
OUTDOOR SEALER REQUIRED
OPTIONAL
TERMINATION CAP
3” MIN.
REQUIRED HEIGHT IS 12” MINIMUM.
IT IS RECOMMENDED TO BE 12” ABOVE
THE MAXIMUM EXPECTED SNOW
LEVEL.
AIR INTAKE
PTRAP OR290° ELBOWS
SUPPLIED BY INSTALLER
TRANSITION PLATE
PVC CEMENT
PVC CEMENT
OUTDOOR SEALER REQUIRED
3” MIN.
EXHAUST
PTRAP OR 2 90° ELBOWS
SUPPLIED BY INSTALLER
REQUIRED HEIGHT IS 12” MINIMUM.
IT IS RECOMMENDED TO BE 12” ABOVE
THE MAXIMUM EXPECTED SNOW LEVEL.
Installation of the Colinear Transition Plate
1. Attachthe plate to chimney chase, atroof,oroutside wall
withfour(4)screws.Useoutdoorsealanttosealthetransition
platetothesurface.
2. Cut inlet air pipe and ue exhaust pipe to correct lengths.
Forverticalterminationsthroughtherooforchimney,theair
intake and exhaust pipe termination must be a minimumof
12 inches above the roof line. It is recommended that the
airintakeand exhaustpipeterminationbe12 inchesabove
themaximumexpectedsnowlevel.SeeFigures13and14.
Whenventingvertically,theexhaustpipeterminationmustbe
aminimumof3inchesabovetheairintake.Alsorefertolocal
codes.Forhorizontalterminationthroughoutsidewalls,the
minimumpipelengthis9inchesforexhaustpipetermination
and6inchesfortheairintake.
3. Attachtheueandinletairpipestothetransitionplate.Use
theappropriateprimerandcementtopermanentlybondthe
jointsandthepipestothetransitionplate.
Figure 13
Figure 14
Available from Empire Comfort Systems, Inc.
Colinear Transition Plate
Note:Mustmaintainaminimum3”be-
tweenexhaustoutletandairintake.