Specifications
30259-0-0212Page 14
VENT EXAMPLES FOR SINGLE FLUE
Figure8displaysasingleue(one-pipe)installation.Becausethe
distancefromthereplacetotherstelbowismorethan6inches,
therst90°elbowmustbeconsideredintothetotalventlength.
Theequivalentlengthofthesecond90°elbowalsoneedstobe
addedtothetotallength,butthethirdelbowdoesnotsinceitisthe
ueterminal.Thetotalhorizontalventlengthoftheuesystemis
7feet,andthetotalverticallengthis27feet.Thetwo90°elbows
areequivalentto6feet,bringingthetotalto40feet.
Figure9isanexampleofhowthereplacecanbeventedifthe
ueoutletisbelowtheleveloftheoor.
90
ELBOW°
2’
(61.0cm)
27’
(8.2m)
5’
(1.5m)
VENT TERMINAL
90° ELBOW
(NOT COUNTED)
3 FEET
FIRST 90
DOES NOT GET COUNTED
WHEN WITHIN 6” (15.2cm)
OFF BACK OF HEATER
° ELBOW
SLOPE
Figure 8
Single Flue - Horizontal Tall Vent Run
Example Calculation Max Vent Run 40 feet
H= 5’+2’=7’
V= 27’
(2)-90°= 6’
Total= 40’
90° ELBOW
FLUE CENTER
6”
(15.2cm)
MIN.
1/4” DOWNWARD SLOPE
PER FOOT TO OUTSIDE
12” MIN. TO GRADE
(RECOMMENDED 12” MIN.
TO EXPECTED SNOW LEVEL)
Figure 9
Minimum Exterior Grade Dimension - Single Flue, Horizontal
Venting Below Floor
Figure 7
Single Flue - Straight Out Back
Min 6” Outside Wall
Min 2” From Fireplace to Wall for Intake Air
Min vent length 12”
12” MIN. TO GRADE
(RECOMMENDED 12” MIN.
TO EXPECTED SNOW LEVEL)
6” MIN.
MIN. 2”
12” MIN.
90 ELBOW°
36’
(11m)
1’
(30.5cm)
SINGLE FLUE ADAPTOR
MODEL #PVVK-FC
SLOPE
Figure 10
Single Flue - Vertical Vent Run
H= 1’
V= 36’
(1)-90°= 3’
Total= 40’