VENTING REQUIREMENTS
WARNING
This replace must not be vented with any other appliances,
even if that appliance is of the condensing type. Common
venting can result in severe corrosion of other appliances
or their venting and can allow combustion gases to escape
through such appliances or vents. Do not vent the replace
into a replace chimney or building chase.
WARNING
Upon completion of the installation, carefully inspect the en-
tire ue system to assure it is properly sealed. DO NOT use
any vent material other than what is specied in this manual.
Leaks in the ue system can result in serious personal injury
or death due to exposure of ue products, including carbon
monoxide.
TheMantis is classied asa“Category IV” appliance,whichre-
quires special venting materials and installation procedures. In-
stallationscanbeConventional(1-pipe)andDirectVent(2-pipe).
Ventingmustbecompletedwith1-1/2inchdiameterpipe.Inse-
lecting a location for installation,it isnecessary to provide ade-
quateclearancesforservicingandproperinstallation.
Allventandcombustion airpipesandttings mustbeSchedule
40PVCandmeettheANSI/ASTMStandardD1785.Cementmust
conformtoASTMStandardD2564.
Maximum Vent Length is 40 feet with (3) 90° elbows. The
minimum vent length is 12 inches.Each90°elbowusedin
theventsystemwillbetheequivalentto3feet,andeach45°
elbowisequivalentto1.5 feet,which shouldbe addedtothe
overall vent length. See Table 1.
It is recommended that the Mantis Power-Vent High-Efciency
Fireplacebelocatedonanexteriorwallforeaseofventing.The
ueexhaustpipeandinletairpipeshouldbelocatedbetweenwall
studs.Therequiredopeningforventingis1-7/8inchindiameter
for1-1/2inchPVCpipe.
Theminimumdistancefromthecenteroftheventcaptothenear-
estoutsidecornerorobstructionis12inches.Theueoutletmust
beatleast12inchesfromanyopeningwhichuegasescoulden-
terthebuilding.SeeFigure1.Theueoutletmustbeaminimum
distanceof6feetfromanypressureregulator.
Thebottomoftheexhaustventterminal andthe airintake shall
be located at least12 inches above gradeand must be vented
outside.Itisrecommendedtheexhaustandintakebelocated12
inches from the maximum snow level.
Theuepipemustbesupportedonhorizontalventruns.Theue
pipeneedstobesupportedevery3feet.Allhorizontalrunsofthe
uemustbepitched¼inchperfooteithertowardsthereplaceor
awayfromthereplace.
Note: Iftheventrundipsorsags,condensationmaybecome
trappedandcausetheunittonotoperateproperly.
The minimum vent length protruding from outside the wall is 6
inches.Fortwo-pipeinstallation,aminimumdistanceof3inches
andmaximumdistanceof24inchesmustbemaintainedbetween
thepipes.SeeFigures2and3.
Single ue (one-pipe) installations must have a minimum clear-
anceof2inchesonthebackofthereplaceforcombustionair.
Note: If vent length requirements are not followed, the unit
will not operate properly.
Figure 3 - Colinear Direct Vent
Table 1 - Equivalent Vent Length Example
EVL=EquivalentVentLength
EVLmustbegreaterthanorequalto1’andlessthanorequalto40’
EVL = 90ºelbow + 4’straightpipe + 45ºelbow + 2’straightpipe + 45ºelbow + 3’straightpipe = 15’
EVL = 3’
(90ºelbow)
+ 4’
(straightpipe)
+ 1.5’
(45ºelbow)
+ 2’
(straightpipe)
+ 1.5’
(45ºelbow)
+ 3’
(straightpipe)
= 15’
12” MIN TO GRADE.
(RECOMMENDED 12” MIN
TO MAX EXPECTED SNOW LEVEL)
6” Min
12” MIN TO GRADE.
(RECOMMENDED 12” MIN
TO MAX EXPECTED SNOW LEVEL)
TYPICAL BOTH PIPES
9” Min
3” Min
24” Max
EXHAUST
INLET
6” Min
Figure 2 - Single Flue