Owner`s manual
25700-1-0809Page 8
Model F(F,I,W)28BM(N,P)
Input BTU/HR (KW/H) 15,000 Rear - 13,000 Front
Height 24 3/4”
Width 28 3/16”
Depth 17 5/8”
Gas Inlet (Pipe) 3/8” Flair
Electrical - Unit has a 5’ (1.5 m) 3 pronged cordset for con-
nection to an approved 115 VAC 60 Hz maximum
AMPs - 5A wall receptacle.
Accessories
Part Number Description
TRW Wall Thermostat - Wireless Remote
FRBTC Battery Operated Remote with Thermostat
FRBTP Battery Operated Remote with Programmable
Thermostat
TDV1 24 Digital Wall Thermostat
T24V 24 Volt Thermostat
TMV2 Two-Stage Thermostats
PVVK24H Direct Vent 24” Vent Kit
PVVK48H Direct Vent 48” Vent Kit
PVVK-SH Single Flue Horizontal Vent Kit
PVVK-SV Single Flue Vertical Vent Kit
PVVK-CFA Flex Vent Kit
PVCT Colinear Transition
PVVTC Vertical Termination Cap - 1.5”
PVCA Colinear Adapter
SPECIFICATIONS
INSTALLATION INSTRUCTIONS - GENERAL SAFETY INFORMATION
1. This installation must conform with local codes or, in the
absence of local codes with NFPA54.
2. Provide adequate clearances around the product for
servicing and ensure there are no obstructions to the
combustion air intake situated at the back of the heater. Refer
to Page 14, Figures 6 through 10.
3. The appliance must be installed on a at, solid continuous
surface (i.e. wood, metal, concrete). Please Note: Rough
or uneven surfaces can cause vibration or humming in the
heater.
4. The Mantis Power-Vent High-Effeciency Fireplace can be
installed in a wide variety of ways and will t nearly any
room layout. It may be installed in a recessed position, framed
out into the room, or across a corner. For installation options
refer to page 14.
5. This appliance needs to be installed in such a way that the
heater can be removed at all times to service the heater ex-
changer and ue fan located in the rear section of the heater.
Note: Under no circumstances should the appliance be
installed under conditions which would not allow for
easy removal of the appliance to carry out routine
inspection and service to the appliance, to do so will
void the warranty.
Note: On Single Wall ue pipe installations (imitation
zero clearance replace) a minimum of 2” (50.8 cm)
clearance must be provided at the rear of the heater to
enable the heater to get sufcient combustion air to the
air inlet located at the rear of heater. Refer to installation
instructions on page 14, Figures 6 through 10.
Note: Where a mantel surround is being used on insert
installations and zero clearance replace installations,
the combustion air intake slot located in the top mantel
surround must have no obstructions to allow combustion
air to enter through the slot to the combustion air inlet
located at the back of the heater.