VENT EXAMPLES FOR SINGLE FLUE
Max Vent Run - 40 ft. Equivalent With Three (3) 90° Elbows
Special Note: The vent terminal 90° elbow and rst 90° el-
bowoffbackoftheheater,whenwithin6”(15.2cm),donot
contribute to the overall vent length measurement. For each
45° elbow installed in the horizontal run, the length of the
horizontal run MUST be reduced by 1.5 feet (45 cm). This
does not apply if the 45° elbows are installed on the vertical
partoftheventsystem.Reducethelengthofthehorizontal
run 3 feet (91.4 cm) for every 90° elbow.
Note: On horizontal runs, a P.V.C. support clamp needs to be in-
stalled every 3 feet. No “sags” in horizontal vent runs; water will
settle in the pipe.
When installing a single ue horizontal, the minimum vent length
protruding from the outside wall is 6” (15.2 cm). See Figure 23.
Minimum vent from the rear of the unit is 12”.
Note: Horizontal discharge 90° elbow must be pointed down-
ward. See Figure 23. All horizontal runs require either a 1/4” per
foot rise to run condensation back to the heater, or a 1/4” per foot
downward slope to run condensation away from the heater.
Note: All PVC vent run piping can be purchased at a local hard-
ware store. Schedule 40 PVC pipe should be used and cemented.
Flex Kit and Horizontal Vent Adaptor Kit are available from Em-
pire Comfort Systems, Inc.
Figure 23
Single Flue - Straight Out Back
Min6”OutsideWall
Min 2” From Unit to Wall for Intake Air
Min vent length 12”
EXTERIOR GRADE
12” MIN.
6” MIN.
MIN. 2”
12” MIN.
SINGLE FLUE ADAPTOR
Figure 24
SingleFlue-VentingwithShroudKitInstalled