Use and Care
Installation Instructions Section 2
10
 Part Number 040002909 5/13
Water Service/Drains
WATER SUPPLY
Local water conditions may require treatment of the 
water to inhibit scale formation, filter sediment, remove 
chlorine, and improve taste and clarity.
WATER INLET LINES
Follow these guidelines to install water inlet lines:
• Do not connect the ice machine to a hot water 
supply. Be sure all hot water restrictors installed for 
other equipment are working. (Check valves on sink 
faucets, dishwashers, etc.)
• If water pressure exceeds the maximum 
(80 psig-551.5 kPA) recommended pressure, obtain 
a water pressure regulator from your Manitowoc 
distributor.
• Install a water shut-off valve and union for both the 
ice making and condenser water lines.
• Insulate water inlet lines to prevent condensation.
DRAIN CONNECTIONS
Follow these guidelines when installing drain lines to 
prevent drain water from flowing back into the ice 
machine and storage bin:
• Drain lines must have a 1.5 inch drop per 5 feet of 
run (2.5 cm per meter), and must not create traps.
• The floor drain must be large enough to 
accommodate drainage from all drains.
• Run separate bin and water-cooled condenser drain 
lines. Insulate them to prevent condensation.
• Vent the ice machine drain. Do not vent the 
condenser drain on water-cooled models.
COOLING TOWER APPLICATIONS
(Water-Cooled Models)
A water cooling tower installation does not require 
modification of the ice machine. The water regulator 
valve for the condenser continues to control the 
refrigeration discharge pressure.
It is necessary to know the amount of heat rejection and 
the pressure drop through the condenser and water 
valves (inlet and outlet) when using a cooling tower on 
an ice machine.
• Water entering the condenser must not exceed 90F 
(32C).
• Water flow through the condenser must not exceed 5 
gallons (19 liters) per minute.
• Allow for a pressure drop of 7 psi (48 kPA) between 
the condenser water inlet and the outlet of the ice 
machine.
• Water exiting the condenser must not exceed 110F 
(43C).
!
Caution
Plumbing must conform to state and local codes.
Important
If you are installing a Manitowoc water filter 
system, refer to the Installation Instructions 
supplied with the filter system for ice making water 
inlet connections.
!
Warning
For ice making, connect to a potable water supply 
only.
Important
The Commonwealth of Massachusetts requires 
that all water-cooled models must be connected 
only to a closed loop, cooling tower system.