Owner's Manual
Part Number: 04002909 Rev02 4/16  11
Section 2  Installation
Water Service/Drains
WATER SUPPLY
Local water conditions may require treatment of the water 
to inhibit scale formation, filter sediment, remove chlorine, 
and improve taste and clarity.
WATER INLET LINES
Follow these guidelines to install water inlet lines:
•  Do not connect the ice machine to a hot water supply. 
Be sure all hot water restrictors installed for other 
equipment are working. (Check valves on sink faucets, 
dishwashers, etc.)
•  If water pressure exceeds the maximum (80 psig-
551.5kPa) recommended pressure, obtain a water 
pressure regulator from your Manitowoc distributor.
•  Install a water shut-off valve and union for both the 
ice-making and condenser water lines.
•  Insulate water inlet lines to prevent condensation.
DRAIN CONNECTIONS
Follow these guidelines when installing drain lines to 
prevent drain water from flowing back into the ice machine 
and storage bin:
•  Drain lines must have a 1.5 inch drop per 5 feet of run 
(2.5 cm per meter) and must not create traps.
•  The floor drain must be large enough to accommodate 
drainage from all drains.
•  Run separate bin and water-cooled condenser drain 
lines. Insulate them to prevent condensation.
•  Vent the ice machine drain. Do not vent the condenser 
drain on water-cooled models.
COOLING TOWER APPLICATIONS
(Water-Cooled Models)
A water cooling tower installation does not require 
modification of the ice machine. The water regulator valve 
for the condenser continues to control the refrigeration 
discharge pressure.
It is necessary to know the amount of heat rejection and 
the pressure drop through the condenser and water valves 
(inlet and outlet) when using a cooling tower on an ice 
machine.
•  Water entering the condenser must not exceed 90°F 
(32°C).
•  Water flow through the condenser must not exceed 5 
gallons (19 liters) per minute.
•  Allow for a pressure drop of 7 psi (48 kPa) between the 
condenser water inlet and the outlet of the ice machine.
•  Water exiting the condenser must not exceed 110°F 
(43°C).
WATER SUPPLY & DRAIN LINE SIZING CONNECTIONS
Location Water Temperature Water Pressure Ice Machine Fitting
Tubing Size Up To The Ice Machine 
Fitting
Ice Making Water 
Inlet
40°F (4°C) Min.
90°F (32°C) Max. 
20 psi (137.9 kPa) Min.
80 psi (551.5 kPa) Max.
3/8 Female Pipe Thread
3/8 (9.5 mm) 
minimum inside diameter
Condenser Water 
Inlet
40°F (4°C) Min.
90°F (32°C) Max.
20 psi (137.9 kPa) Min.
150 psi (1034.2 kPa) Max
3/8 Female Pipe Thread
U310 Only
1/2 Female Pipe Thread
3/8 (9.5 mm) 
minimum inside diameter
U310 Only
1/2 (12.7 mm) 
minimum inside diameter
Condenser Water 
Drain
--- --- 1/2 Female Pipe Thread
1/2 (12.7 mm) 
minimum inside diameter
Bin Drain --- --- 1/2 Female Pipe Thread
1/2 (12.7 mm) 
minimum inside diameter