REFRIGERATION LINE SET INSTALLATION
The following requirements assure proper oil return.
The refrigeration line set installer must be certified/
licensed in refrigerant handling and servicing.
Step 1 Lineset Requirements
Maximum lineset length is 100' (30 m).
Maximum rise is 35' (10 m).
Maximum drop is 15' (4.5 m).
A suction line oil trap is required when rise is more
than 20' (6 m).
Maximum lineset exposed on rooftop is 25% of total
line set length.
Only one trap is allowed in the lineset.
Shorten the lineset as required, do not coil lineset.
A qualified person must perform all roof penetrations
.
Manitowoc S-Trap Kit
Step 2 Secure Condenser
Through holes are provided to secure the condenser to
a curb, rack, or wooden timber.
Step 3 Route Refrigeration Tubing
Properly route refrigeration tubing between the ice
machine head section and the CVD® condensing unit.
The line set can be routed for entry through the top or
rear of the ice machine head section.
Top routing requires the cover to be trimmed.
Rear routing may require the use of 90° elbows.
!
Warning
The ice machine head section contains refrigerant
charge. The ice machine head section contains
refrigeration valves that must remain closed until
proper installation of the line sets is completed.
!
Warning
Electrical power to the ice machine head section
and CVD® condensing unit must be disconnected
before proceeding.
35' (10 M)
MAX.
DISTANCE
100' (30 M)
MAX LINESET
LENGTH
Model
S-Trap Kit
Number
Tubing Size
S0600C IB600C
S0800C IB800C
S1000C
K00172
5/8 inch
(15.9 mm)
IB1000C S1200C
S1470C S1870C
S2170C
S3000C*
SF3000C*
K00166
3/4 inch
(19.1 mm)
*S3000C/SF3000C - requires two S-Trap kits, one for each
suction line.
15' (4.5 M)
MAX.
DISTANCE
MORE THAN 20' (6 M) RISE
S-TRAP KIT REQUIRED