Part Number 8014793 6/18 175
Specifications
MAIN FUSE
The main fuse is 250 Volt, 7 amp.
FAN CYCLE CONTROL
(Self-Contained Air-Cooled Models Only)
HIGH PRESSURE CUTOUT (HPCO) CONTROL
Model Cut-In (Close) Cut-Out (Open)
S300 / S320
S420 / S450
S500 / S600
S850
250 ±5
(1723 kPa ±.34)
(17.23 bar ±.34)
200 ±5
(1517 kPa ±.34)
(15.17 bar ±.34)
S1000 / S1200
S1400 / S1600
S1800
275 psig ±5
(1896 kPa ±34)
(18.96 bar±.34)
225 psig ±5
(1551 kPa ±34)
(15.51 bar ±.34)
Specifications
Cut-Out Cut-In
450 psig ±10
(3103 kPa ±69 31 bar
±.69)
Automatic Reset
(Must be below 300 psig (2068 kPa 20.68 bar) to reset.)
ST3000 R410A Refrigerant Only
600 psig ±10
(3147 kPa ±69)
450 psig ±10
(3103 kPa ±69)