LOW PRESSURE CUTOUT (LPCO) CONTROL
(ST3000/S3300 Only)
FUNCTION
Signals the control board to energize and de-energize
the ice machine when suction pressure rises above or
falls below setpoint.
The LPCO control is closed at pressures above
setpoint and opens at pressures below setpoint.
Two controls have been used and either will function
correctly.
CHECK PROCEDURE
1. Connect manifold gauge set at suction and
discharge access valves and verify refrigerant
pressure exceeds LPCO cut-in.
2. Isolate LPCO electrical leads, connect a
multimeter and read resistance.
Open = Replace Switch
Closed = Switch OK
NOTE: When the LPCO opens the compressor
contactor opens and the control board light will flash
When the control closes the compressor contactor
closes and the control board light stops flashing.
Specifications
Cut-Out Cut-In
12 psig ±3 35 psig ±3
7 psig ±3 22 psig ±3