Specifications
Installation Instructions Section 2
2-12
Part Number 000000345
MAXIMUM BREAKER SIZE & MINIMUM CIRCUIT AMPERAGE CHART
(* indicates preliminary data)
MINIMUM POWER CORD SPECIFICATIONS
If a power cord is used the wire size to the receptacle is dependant upon location, materials used, length of run, etc.,
so it must be determined by a qualified electrician. Local, state or national requirements will supersede our minimum
requirements.
Ice Machine
Voltage
Phase
Cycle
Air-Cooled Water Cooled Remote
Maximum
Fuse/Circuit
Breaker
Minimum
Circuit Amps
Maximum
Fuse/Circuit
Breaker
Minimum
Circuit Amps
Maximum
Fuse/Circuit
Breaker
Minimum
Circuit Amps
S300
115/1/60 20 12.9 20 12.1 N/A N/A
230/1/50 15 6.4 15 5.9 N/A N/A
S320
115/1/60 15 11.3 15 10.5 N/A N/A
208-230/1/60 15 6.0 15 5.6 N/A N/A
230/1/50 15 6.0 15 5.6 N/A N/A
S420/S450
115/1/60 20 16.3 20 15.6 N/A N/A
208-230/1/60 15 8.2 15 8.2 N/A N/A
230/1/50 15 6.7 15 6.4 N/A N/A
S500
115/1/60 20 13.0 20 12.3 20 14.1
208-230/1/60 15 7.3 15 6.9 N/A N/A
230/1/50 15 6.5 15 5.9 N/A N/A
S600
208-230/1/60 15 8.3 15 7.9 15 8.9
230/1/50 15 6.7 15 6.1 15 7.1
S850
208-230/1/60 20 11.3 20 10.3 20 10.6
208-230/3/60 15 7.8 15 6.8 15 7.8
230/1/50 20 10.5 20 9.1 20 9.7
S1000
208-230/1/60 20 13.6 20 12.6 20 12.8
208-230/3/60
15 9.9 15 8.9 15 9.9
230/1/50
20 12.6 20 11.2 20 12.0
S1200
208-230/1/60 30 17.1 30 16.1 N/A N/A
208-230/3/60
20 11.4 20 10.4 N/A N/A
230/1/50
30 13.7 30 12.3 N/A N/A
S1400
208-230/1/60 30 17.5 30 16.1 30 17.1
208-230/3/60 20 13.2 20 11.8 20 12.8
230/1/50 30 15.1 30 13.7 30 14.7
S1600
208-230/1/60 30 19.8 30 18.4 30 19.4
208-230/3/60 20 13.5 20 12.1 20 13.1
230/1/50 30 16.7 30 15.3 30 13.1
S1800
208-230/1/60
40 23.5 40 22.1 40 23.1
208-230/3/60
20 13.4 20 12.0 20 13.0
230/1/50
40 21.9 40 20.5 40 21.5
Maximum Breaker Size Minimum Wire Size Maximum Length of Power Cord
15 amp 14 gauge 6 feet (1.83 m)
20 amp 12 gauge 6 feet (1.83 m)
30 amp 10 gauge 6 feet (1.83 m)
40 amp 8 gauge 6 feet 1(.83 m)