Part Number 000015433_03 5/20 31
Step 5 Refer to chart and premix cleaner/descaler
with lukewarm water in a non-metallic container.
Model Water
Reservoir
Capacity
Mix Cleaner/Descaler and
Water
Use Ice machine cleaner/
descaler, part number
000000084 only
Cleaner Water
UNF0200
UFF0200
UFF0350
UNF0300
14 oz (400 ml) 9 oz (266 ml) 5 oz (148 ml)
RNF0320
RFF0320
RNF0620
RFF0620
17 oz (500 ml) 11 oz (325 ml) 6 oz (177 ml)
RNF1020C
RNF1100
RFF1220C
RFF1300
34 oz (1 L) 23 oz (680 ml) 11 oz (325 ml)
RNF2000C
RFF2200C
RFF2500
68 oz (2 L) 46 oz (1.3 L) 22 oz (650 ml)
Step 6 Remove all water from the evaporator and
water reservoir. Add the entire descaler/water solution
and re-install the reservoir cover.
Leave the descaler/water solution in the evaporator for a
minimum of 4 hours.
Step 7 Remove all descaler/water solution from the
evaporator and water reservoir.
Step 8 Perform the detailed descaling and sanitizing
procedure.