Electrical Requirements
FUSE/CIRCUIT BREAKER
A dedicated circuit and a separate fuse/circuit breaker
are required for each ice machine.
GROUND FAULT INTERRUPTER CIRCUIT (GFIC)
We do not recommend the use of a GFCI/GFI circuit
protection with our equipment. If a GFCI/GFI is required
by code, use a GFCI/GFI breaker rather than outlet
which is more prone to intermittent nuisance trips than
panel circuit breakers.
Ice Machine
Voltage/
Phase/
Cycle
Air-Cooled Water-Cooled
Maximum
Fuse/Circuit
Breaker
Minimum
Circuit
Amps
Total
Circuit
Amps
Maximum
Fuse/Circuit
Breaker
Minimum
Circuit
Amps
Total
Circuit
Amps
RF-0244
115/1/60 15 Amp N/A 7.5 N/A N/A N/A
230/1/50 10 Amp N/A .87 N/A N/A N/A
RF-0266
115/1/60 15 Amp N/A 7.5 N/A N/A N/A
230/1/50 10 Amp N/A .87 N/A N/A N/A
RF-0388
115/1/60 15 Amp N/A 10.0 N/A N/A N/A
230/1/50 10 Amp N/A 2.9 N/A N/A N/A
RF-0399
115/1/60 15 Amp N/A 10.0 N/A N/A N/A
230/1/50 10 Amp N/A 2.9 N/A N/A N/A
RF-0300
115/1/60 15 Amp 10.0 N/A N/A N/A N/A
230/1/50 10 Amp 2.9 N/A N/A N/A N/A
RF-0650
208-230/1/60 15 Amp 7.3 N/A N/A N/A N/A
230/1/50 16 Amp 4.6 N/A N/A N/A N/A
RF-1200
208-230/1/60 15 Amp 15.0 N/A 15 Amp 15.0 N/A
230/1/50 16 Amp 7.3 N/A 16 Amp 7.3 N/A
RF-2300
208-230/3/60 20 Amp 15.0 N/A 20 Amp 15.0 N/A
400-415/3/50 16 Amp 13.9 N/A 16 Amp 13.9 N/A
Maximum allowable voltage variation at compressor start-up is ±10% of voltage listed above and on the model/serial plate.
!
Warning
The ice machine must be grounded in accordance
with national and local electrical codes.
For United Kingdom Only
As the colours of the wires in the mains lead of the appliance may not correspond with the coloured markings identifying the terminals in your
plug, proceed as follows:
• The wire which is coloured green and yellow must be connected to the terminal in the plug which is marked with the letter E or by the
earth ground symbol or coloured green or green and yellow.
• The wire coloured blue
must be connected to the terminal which is marked with the letter N or coloured black.
• The wire coloured brown
must be connected to the terminal which is marked with the letter L or coloured red.