Service Manual
Section 7 Refrigeration System
Part No. 80-1100-3 7-31
LOW ON CHARGE VERIFICATION
The remote ice machine requires more refrigerant 
charge at lower ambient temperatures than at higher 
temperatures. A low on charge ice machine may 
function properly during the day, and then malfunction at 
night. Check this possibility.
If you cannot verify that the ice machine is low on 
charge:
1. Add refrigerant in 2 lb. increments, but do not 
exceed 6 lbs.
2. If the ice machine was low on charge, the 
headmaster function and discharge pressure will 
return to normal after the charge is added. Do not let 
the ice machine continue to run. To assure operation 
in all ambient conditions, the refrigerant leak must 
be found and repaired, the liquid line drier must be 
changed, and the ice machine must be evacuated 
and properly recharged.
3. If the ice machine does not start to operate properly 
after adding charge, replace the headmaster.
FAN CYCLE CONTROL VS. HEADMASTER
A fan cycle control cannot be used in place of a 
headmaster. The fan cycle control is not capable of 
bypassing the condenser coil and keeping the liquid line 
temperature and pressure up.
This is very apparent when it rains or the outside 
temperature drops. When it rains or the outside 
temperature drops, the fan begins to cycle on and off. At 
first, everything appears normal. But, as it continues 
raining or getting colder, the fan cycle control can only 
turn the fan off. All the refrigerant must continue to flow 
through the condenser coil, being cooled by the rain or 
low outside temperature.
This causes excessive sub-cooling of the refrigerant. As 
a result, the liquid line temperature and pressure are not 
maintained for proper operation.










