Refrigeration System Section 7
7-28 Part No. 80-1100-3
FREEZE CYCLE
The H.P.R. system is not used during the freeze cycle. 
The H.P.R. solenoid is closed (de-energized), preventing 
refrigerant flow into the H.P.R. valve.
HARVEST CYCLE
During the harvest cycle, the check valve in the 
discharge line prevents refrigerant in the remote 
condenser and receiver from backfeeding into the 
evaporator and condensing to liquid.
The H.P.R. solenoid is opened (energized) during the 
harvest cycle, allowing refrigerant gas from the top of the 
receiver to flow into the H.P.R. valve. The H.P.R. valve 
modulates open and closed, raising the suction pressure 
high enough to sustain heat for the harvest cycle, 
without allowing refrigerant to condense to liquid in the 
evaporator.
In general, harvest cycle suction pressure rises, then 
stabilizes in the range of 75-100 psig (517-758 kPA).
Exact pressures vary from model to model. These can 
be found in the “Operational Refrigerant Pressures” 
charts, beginning on Page 7-32.