Service Manual
Refrigeration System Section 7
7-24 Part No. 80-1100-3
HOW TO USE THE REFRIGERATION SYSTEM
OPERATIONAL ANALYSIS TABLES
General
These tables must be used with charts, checklists and 
other references to eliminate refrigeration components 
not listed on the tables and external items and problems 
which can cause good refrigeration components to 
appear defective.
The tables list five different defects that may affect the 
ice machine’s operation.
NOTE: A low-on-charge ice machine and a starving 
expansion valve have very similar characteristics and 
are listed under the same column.
NOTE: Before starting, see “Before Beginning Service” 
on Page 7-9 for a few questions to ask when talking to 
the ice machine owner.
Procedure
Step 1 Complete the “Operation Analysis” column.
Read down the left “Operational Analysis” column. 
Perform all procedures and check all information listed. 
Each item in this column has supporting reference 
material to help analyze each step.
While analyzing each item separately, you may find an 
“external problem” causing a good refrigerant 
component to appear bad. Correct problems as they are 
found. If the operational problem is found, it is not 
necessary to complete the remaining procedures.
Step 2 Enter check marks (
√) in the small boxes.
Each time the actual findings of an item in the 
“Operational Analysis” column matches the published 
findings on the table, enter a check mark.
Example: Freeze cycle suction pressure is determined 
to be low. Enter a check mark in the “low” box.
Step 3 Add the check marks listed under each of the 
four columns. Note the column number with the highest 
total and proceed to “Final Analysis.”
NOTE: If two columns have matching high numbers, a 
procedure was not performed properly and/or supporting 
material was not analyzed correctly.
Final Analysis
The column with the highest number of check marks 
identifies the refrigeration problem.
COLUMN 1 - HARVEST VALVE LEAKING
A leaking harvest valve must be replaced.
COLUMN 2 - LOW CHARGE/TXV STARVING
Normally, a starving expansion valve only affects the 
freeze cycle pressures, not the harvest cycle pressures. 
A low refrigerant charge normally affects both pressures. 
Verify the ice machine is not low on charge before 
replacing an expansion valve.
1. Add refrigerant charge in 2 to 4 oz. increments as a 
diagnostic procedure to verify a low charge. If the 
problem is corrected, the ice machine is low on 
charge. Find the refrigerant leak.
The ice machine must operate with the nameplate 
charge. If the leak cannot be found, proper 
refrigerant procedures must still be followed Change 
the liquid line drier. Then, evacuate and weigh in the 
proper charge.
2. If the problem is not corrected by adding charge, the 
expansion valve is faulty.
On dual expansion valve ice machines, change only 
the TXV that is starving. If both TXV’s are starving, 
they are probably good, and are being affected by 
some other malfunction, such as low charge.
COLUMN 3 - TXV FLOODING
A loose or improperly mounted expansion valve bulb 
causes the expansion valve to flood. Check bulb 
mounting, insulation, etc., before changing the valve. On 
dual expansion valve machines, the service technician 
should be able to tell which TXV is flooding by analyzing 
ice formation patterns. Change only the flooding 
expansion valve.
COLUMN 4 - COMPRESSOR
Replace the compressor and start components. To 
receive warranty credit, the compressor ports must be 
properly sealed by crimping and soldering them closed. 
Old start components must be returned with the faulty 
compressor.










