Specifications

Installation Instructions Section 2
2-4
Part No. 80-1175-3, 6/03
Location of Ice Machine
The location selected for the ice machine must meet the
following criteria. If any of these criteria are not met,
select another location.
The location must be free of airborne and other
contaminants.
The air temperature must be at least 35°F (1.6°C),
but must not exceed 110°F (43.4°C).
The location must not be near heat-generating
equipment or in direct sunlight.
The location must not obstruct airflow through or
around the ice machine. See below for clearance
requirements.
Ice Machine Head Section Clearance
Requirements
Top/Sides 5” (127 mm) is recommended for efficient
operation and servicing. There is no minimum clearance
required.
Back 1” (25.4 mm) required when routing electrical inlet,
water inlet and refrigeration tubing out of the top of the
unit.
5” (127 mm) required when routing all connections out
the back.
Stacking Two Ice Machines on a Single
Storage Bin
A stacking kit is required for stacking two ice machines.
Installation instructions are supplied with the stacking kit.
Location of CVD Condensing Unit
The location selected for the CVD Condensing Unit must
meet the following criteria. If any of these criteria are not
met, select another location.
The air temperature must be at least -20°F (-28.9°C)
but must not exceed 130°F (54.4°C).
The location must not allow exhaust fan heat and/or
grease to enter the condenser.
The location must not obstruct airflow through or
around the condensing unit. See below for clearance
requirements.
Condensing Unit Clearance Requirements
Top/Sides
There is no minimum clearance required, although 6”
(152 mm) is recommended for efficient operation and
servicing only.,
Front/Back
48” (122 cm)
Condensing Unit Heat of Rejection
Ice machines, like other refrigeration equipment, reject
heat through the condenser. It is helpful to know the
amount of heat rejected by the ice machine when sizing
air conditioning equipment where self-contained air-
cooled ice machines are installed.
This information is also necessary when evaluating the
benefits of using water-cooled or CVD® Condensing
Units to reduce air conditioning loads. The amount of
heat added to an air-conditioned environment by a
QuietQube® ice machine head section is negligible.
!
Caution
The ice machine head section must be protected if it
will be subjected to temperatures below 32°F (0°C).
Failure caused by exposure to freezing
temperatures is not covered by the warranty. See
“Removal from Service/Winterization”.
Series
Condensing Unit
Heat of Rejection*
*B.T.U./Hour
Air Conditioning**
**Because the heat of rejection varies during the ice making cycle,
the figure shown is an average.
Peak
CVD675 9,000 13,900
CVD875 12,400 19,500
CVD1075 16,000 24,700