Specifications
Part Number STH044 10/13 103
Component Specifications
MAIN FUSE
The main fuse is 250 Volt, 10 amp.
ICE/OFF/CLEAN TOGGLE SWITCH
Single-pole, double-throw switch. The switch is
connected into a varying low D.C. voltage circuit.
HIGH PRESSURE CUTOUT (HPCO) CONTROL
FILTER-DRIERS
Driers are covered as a warranty part. The drier must
be replaced any time the system is opened for repairs.
The size of the filter-drier is important. The refrigerant
charge is critical. Using an improperly sized filter-drier
will cause the ice machine to be improperly charged
with refrigerant. Listed below is the recommended
OEM field replacement drier:
Cut-Out Cut-In
450 psig ±10
(3103 kPa ±69)
31 bar ±.69
Automatic Reset
(Must be below 300 psig
(2068 kPa 20.68 bar) to reset.)
Model
Drier
Size
End
Connection
Size
RNS012 RNS020 DML-032S 1/4"