Specifications

112 Part Number 80-01111-9 7/10
Safety Limit Checklist
The following checklists are designed to assist the
service technician in analysis. However, because
there are many possible external problems, do not
limit your diagnosis to only the items listed.
Safety Limit #1
Freeze time exceeds 60 minutes for 6 consecutive
freeze cycles.
Possible Cause Checklist
Improper installation
Refer to “Installation and Visual Inspection
Checklist” on page 104
Water System
Water Level set too high (water escaping through
over flow tube)
Low water pressure (20 psig min.)
High water pressure (80 psig max.)
High water temperature (90°F/32.2°C max.)
Clogged water distribution tube
Dirty/defective float valve
Defective water pump
Electrical System
Ice thickness probe out of adjustment
Harvest cycle not initiated electrically
Contactor not energizing
Compressor electrically non-operational
Restricted condenser air flow
High inlet air temperature (110°F/43.3°C max.)
Condenser discharge air re-circulation
Dirty condenser fins
Defective fan cycling control
Defective fan motor
Low water pressure (20 psig min.)
High water temperature (90°F/32.2°C max.)
Dirty condenser