Specifications

Part Number STH12 9/10 91
NO
YES
YES
NO
YES
NO
PRESSURE
VERIFIED
TEMPERATURE
VERIFIED
VERIFY TEMPERATURE
WITH SECOND
THERMOMETER
TROUBLE SHOOT WATER
SUPPLY SYSTEM TO FIX.
HIGH WATER PRESS,
REGULATOR BAD, NEEDED
FIRST CHECK FOR
CONDENSER FAILURE OR HOT
GAS BYPASS
TEMPERATURE
VERIFIED
GO TO COMPRESSOR /
REFRIGERATION SYSTEM
TROUBLESHOOTING
REPLACE WATER
PRESSURE TRANSDUCER
020001992
GO TO COMPRESSOR
TROUBLESHOOTING TO FIX
REFRIGERATION SYSTEM
REPLACE DISCHARGE/LIQUID
LINE TEMPERATURE
THERMISTOR 020001991
VERIFY TEMP WITH SECOND
THERMOMETERIF STILL <200°F
REPLACE ERC CONTROL
BOARD 020001985
VERIFY PRESS WITH
SECOND GAUGE, IF
CORRECTREPLACE ERC
BOARD 020001985
REPLACE WATER BATH
THERMISTOR
020002142