Specifications

Part Number STH12 9/10 27
3. The easiest method to create a trap is to bend the
tubing (smoothly, no kinks) into the trap form.
4. The trap(s) must be of minimum height of 3"
(7.6 cm) and a width of 6" (15.2 cm) to minimize oil
accumulation. The traps can also be bent out of the
refrigeration tubing. Carefully bend the tubing down
12", and then sweep the tubing back up.
5. It is critical that the remote condensing line size
specifications for the specific model be
maintained. The specifications are 1/2" discharge
and 3/8" liquid lines.
To the
Condenser
Discharge Line Trap Every
25 Vertical ft. (7.62 m)
3 ft (.9 m) (minimum) of Discharge
Line Trap at the Compressor
Compressor
3" (7.6 cm) x 6" (15.2 cm)
Maximum Trap Area
Discharge Line
Condenser Trap