Specifications
00218012 Revision B (KAK) 7 August, 2000
24
Multiplex Company, Inc.
Fountain Troubleshooting Guide
Troubleshooting Guide
WARNING: Inspection, testing, and repair of elec-
trical equipment should be performed only by
qualified service personnel. The unit should be
unplugged when servicing, except when electri-
cal tests are required.
DANGER: Use extreme care during electrical cir-
cuit tests. Live circuits may be exposed.
Section 6: Electrical System
Qualifier Probable Cause Corrective Action
Fuse/Circuit Breaker is
open.
Short Circuit or overload
within unit.
Push Toggle Switches labeled carbonator and
circulator to the off position. Push the Toggle
Switches for Booster Pump, Air Compressor, Agi-
tator and Refrigeration to the off position.
Replace fuse(s) and reset circuit breaker. Push
the Toggle Switches on in the following se-
quence as labeled below, to locate short or
overload within unit, waiting momentarily be-
tween steps. *Agitator *Refrigeration *Carbon-
ator A and/or B *Circulator A and/or B (after
carbonator Motor Cycles off) *Booster Pump
*Air Compressor.
Push the Agitator Toggle Switch in the on
position. If the fuse/circuit breaker opens, the
trouble is in the Agitator Motor Circuit. This
Circuit must be checked for shorts and/or over-
load. If the fuse/circuit breaker does not open
after running about 1 minute, the problem is
not in the Agitator Motor Circuit.
Push the Refrigeration Toggle Switch in the
on position. If the fuses/circuit breaker
opens, the trouble is in the Refrigeration Cir-
cuit. Refer to wiring diagram for possible faulty
components. Push the carbonator Toggle Switch
A to the on position. Draw Carbonated Wa-
ter from the Dispensing valve until Pump cycles.
If the fuse/circuit breaker opens, the trouble
is in the carbonator Circuit. Refer to wiring dia-
gram for possible faulty components.
Push the carbonator Toggle Switch B to the on
position. Follow procedure above for carbon-
ator A. Push the Circulator Toggle Switch A to
the on position. If fuse/circuit breaker
opens, the trouble is in the Circulator Circuit.
Refer to wiring diagram for possible faulty com-
ponents. Push the Circulator Toggle Switch B
to the on position. Follow procedure above
for Circulator A.
Push the Booster Pump Toggle Switch to the
on position (allow unit to cycle). If fuse/cir-
cuit breaker opens, the trouble is in the Booster
Pump Circuit. Refer to wiring diagram for pos-
sible faulty components.
Push the Air Compressor Toggle Switch to the
on position. (Allow unit to cycle). If fuse/
circuit breaker opens, the trouble is in the Air
Compressor Circuit. Refer to wiring diagram for
possible faulty components.
Important Note: Worn out Circuit Breakers or
low voltage are frequently responsible for
shorts and overloads. Contact service agent to
examine possible defective Circuit Breakers or
low voltage.