Service manual
22
Installation and Service Manual
REMOTE CONDENSER INSTALLATION GUIDELINES
REMOTE CONDENSERS MAXIMUM LOCATION DISTANCE
(REFRENCES DRAWING C)
Remote condenser installations consist of vertical
and horizontal distances to the condenser that, when
combined, must fit within approved guidelines.
TOTAL MAXIMUM LINE LENGTH:
This should never exceed 50 feet (15.24 meters)
total. The pressure drop, due to the refrigerant flowing
through the lines and condenser, will exceed the design
limits of the head pressure control.
CONDENSER MAXIMUM HEIGHT:
This should never exceed 35 feet (10.66 meters).
CONDENSER MAXIMUM DROP:
The condenser should never be positioned more than
15 feet (4.57 meters) below the ice machine. the liquid
refrigerant pushed from the condenser up to the ice
machine will contribute to an overall pressure drop.