Freeze Cycle Suction Pressure High Checklist
Possible Cause Check/Correct
Improper installation See “Installation/Visual Inspection Checklist” on page 7-10
Discharge pressure Discharge pressure is too high, and is affecting low side (See “Freeze Cycle
Discharge Pressure High Checklist” on page 7-19)
Improper refrigerant charge Overcharged
Wrong type of refrigerant
Other Non-Manitowoc components in system
H.P.R. solenoid leaking
Hot gas valve stuck open
TXV flooding (check bulb mounting)
Defective compressor
Freeze Cycle Suction Pressure Low Checklist
Possible Cause Check/Correct
Improper installation See “Installation/Visual Inspection Checklist” on page 7-10
Discharge pressure Discharge pressure is too low, and is affecting low side (See “Freeze Cycle
Discharge Pressure Low Checklist” on page 7-19)
Improper refrigerant charge Undercharged
Wrong type of refrigerant
Other Non-Manitowoc components in system
Improper water supply over evaporator (See “Water System Checklist” on
page 7-10)
Loss of heat transfer from tubing on back side of evaporator
Restricted/plugged liquid line drier
Restricted/plugged tubing in suction side of refrigeration system
TXV starving (check bulb mounting)
NOTE: Do not limit your diagnosis to only the items listed in the checklists.