Service manual

Section 7 Refrigeration System
7-15
Safety Limit #2
Harvest time exceeds 3.5 minutes for 3 consecutive harvest cycles.
Possible Cause Check/Correct
Improper installation See “Installation/Visual Inspection Checklist” on page 7-10
Water system Water area (evaporator) dirty
Dirty/defective water dump valve
Vent tube not installed on water outlet drain
Water freezing behind evaporator
Plastic extrusions and gaskets not securely mounted to the evaporator
Low water pressure (20 psi min.)
Loss of water from sump area
Clogged water distribution tube
Dirty/defective float valve
Defective water pump
Electrical system Ice thickness probe out of adjustment
Ice thickness probe dirty
Bin switch defective
Premature harvest
Refrigeration system Non-Manitowoc components
Water regulating valve dirty/defective
Improper refrigerant charge
Defective head pressure control valve (remotes)
Defective harvest pressure control (HPR) valve (remotes)
Defective hot gas valve
TXV flooding (check bulb mounting)
Defective fan cycling control
NOTE: Because there are many possible external
problems, do not limit your diagnosis to only the
items listed in this chart.
NOTE: This chart reflects the removal of safety limits
#3 and #4 from new style control boards.