Service Manual
Table Of Contents
- Safety Notices- Definitions
- General Information
- Installation
- Maintenance
- Operation
- Troubleshooting- Troubleshooting
- Troubleshooting By Symptom- Reset To Factory Defaults
- Symptom #1 - Ice Machine Will Not Run
- #2 - Low Production, Long Freeze Cycle
- Symptom #2 - Freeze Cycle Refrigeration System Operational Analysis Tables
- Symptom #3 & #4 - Harvest Problems Self‑contained Air, Water & Remote Condenser Models
- Symptom #3 - Self-Contained Air or Water-cooled
- Symptom #3 - Remote Condenser
- Symptom #4 - Self-Contained Air, Water-Cooled or Remote
 
 
- Component Check Procedures- Electrical Components- Control Board, Display And Touchscreen
- Control Board Relay Test
- Programming A Replacement Control Board
- USB Flash Drive Specifications and Formatting
- Exporting Data to a Flash Drive
- Upgrading Firmware with a Flash Drive
- Main Fuse
- Bin Switch
- Water Level Control Circuitry
- Ice Thickness Probe (Initiates Harvest)
- Bin Level Probe
- Thermistors
- High Pressure Cutout (HPCO) Control
- Fan Cycle Control
- Harvest Assist Air Pump
- Compressor Electrical Diagnostics
- Diagnosing Start Components
 
- Refrigeration Components
- Refrigerant Recovery/Evacuation
- System Contamination Clean-Up
- Liquid Line Filter-Driers
- Replacing Pressure Controls Without Removing Refrigerant Charge
- Total System Refrigerant Charge
 
- Electrical Components
- Charts
- Diagrams- Wiring Diagrams- Wiring Diagram Legend
- IF0300/IT0420/IT0450/IT0500/IT0620/IT0750 1ph Air/Water
- IT0500/IT1200 - 1ph Remote Air-Cooled
- IF0600/IF0900/IT0900/IT1200 - 1ph Air/Water
- IF0600/IF0900/IT0900/IT1200 - 3ph Air/Water
- IT1500/IT1900 - 1ph Air/Water
- IT1500/IT1900 - 3 ph Air/Water
- IF0500/IF0600/IF0900/IT1200/IF1500 - 1ph Remote
- IF0500/IF0600/IF0900/IT1200/IF1500 - 3ph Remote Condenser
 
- Electronic Control Board
- Refrigeration Tubing Schematics
 
- Wiring Diagrams
 
172  Part Number: 000015430 Rev 02 5/20
Freeze Cycle Operation All Remote Condenser Models
The headmaster is non adjustable.
At ambient temperatures of approximately 70°F (21°C) 
or above, refrigerant flows through the valve from the 
condenser to the receiver inlet. At temperatures below 
this (or at higher temperatures if it is raining), the head 
pressure control dome’s nitrogen charge closes the 
condenser port and opens the bypass port from the 
compressor discharge line.
In this modulating mode, the valve maintains minimum 
head pressure by building up liquid in the condenser and 
bypassing discharge gas directly to the receiver.
Harvest Cycle Operation 
Remote Condenser Models
Refrigerant flows from the compressor to the evaporator 
through the harvest valve and the head pressure valve is 
out of the circuit.
Diagnostics
1.  Determine if the coil is clean. 
2.  Determine the air temperature entering the 
condenser.
3.  Determine if the head pressure is high or low in 
relationship to the outside temperature. (Refer to 
the proper “Cycle Times/24-Hour Ice Production/
Refrigerant Pressure Charts” ). 
4.  Determine the temperature of the liquid line entering 
the receiver by feeling it. This line is normally warm; 
“body temperature.”
5.  Using the information gathered, refer to the chart.