Service Manual
Table Of Contents
- Safety Notices
- Definitions
- General Information
- Installation
- Maintenance
- Operation
- Troubleshooting
- Troubleshooting
- Troubleshooting By Symptom
- Reset To Factory Defaults
- Symptom #1 - Ice Machine Will Not Run
- #2 - Low Production, Long Freeze Cycle
- Symptom #2 - Freeze Cycle Refrigeration System Operational Analysis Tables
- Symptom #3 & #4 - Harvest Problems Self‑contained Air, Water & Remote Condenser Models
- Symptom #3 - Self-Contained Air or Water-cooled
- Symptom #3 - Remote Condenser
- Symptom #4 - Self-Contained Air, Water-Cooled or Remote
- Component Check Procedures
- Electrical Components
- Control Board, Display And Touchscreen
- Control Board Relay Test
- Programming A Replacement Control Board
- USB Flash Drive Specifications and Formatting
- Exporting Data to a Flash Drive
- Upgrading Firmware with a Flash Drive
- Main Fuse
- Bin Switch
- Water Level Control Circuitry
- Ice Thickness Probe (Initiates Harvest)
- Bin Level Probe
- Thermistors
- High Pressure Cutout (HPCO) Control
- Fan Cycle Control
- Harvest Assist Air Pump
- Compressor Electrical Diagnostics
- Diagnosing Start Components
- Refrigeration Components
- Refrigerant Recovery/Evacuation
- System Contamination Clean-Up
- Liquid Line Filter-Driers
- Replacing Pressure Controls Without Removing Refrigerant Charge
- Total System Refrigerant Charge
- Electrical Components
- Charts
- Diagrams
- Wiring Diagrams
- Wiring Diagram Legend
- IF0300/IT0420/IT0450/IT0500/IT0620/IT0750 1ph Air/Water
- IT0500/IT1200 - 1ph Remote Air-Cooled
- IF0600/IF0900/IT0900/IT1200 - 1ph Air/Water
- IF0600/IF0900/IT0900/IT1200 - 3ph Air/Water
- IT1500/IT1900 - 1ph Air/Water
- IT1500/IT1900 - 3 ph Air/Water
- IF0500/IF0600/IF0900/IT1200/IF1500 - 1ph Remote
- IF0500/IF0600/IF0900/IT1200/IF1500 - 3ph Remote Condenser
- Electronic Control Board
- Refrigeration Tubing Schematics
- Wiring Diagrams
210 Part Number: 000015430 Rev 02 5/20
IT0500 SERIES
IT0500A Self-Contained Air-Cooled Model
Characteristics vary depending on operating conditions.
CYCLE TIMES
Freeze Time + Harvest Time = Total Cycle Time
Air Temp.
Entering
Condenser °F/°C
Freeze Time
Harvest
Time ¹
Water Temperature °F/°C
50/10 70/21 90/32
70/21 11.2-12.9 13.1-15.0 14.5-16.5
1-2.5
80/27 12.3-14.1 14.5-16.5 14.9-17.0
90/32 13.2-15.1 15.1-17.2 16.9-19.3
100/38 14.7-16.8 16.9-19.3 18.6-21.2
110/43 15.5-17.7 18.0-20.5 20.2-23.1
1 Times in minutes
24 HOUR ICE PRODUCTION
Air Temp. Entering
Condenser °F/°C
Water Temperature °F/°C ¹
50/10 70/21 90/32
70/21 520 455 415
80/27 480 415 405
90/32 450 400 360
100/38 410 360 330
110/43 390 340 305
1 Based on average ice slab weight of 4.60 - 5.20 lb.
2 230/50/1 is approximately 12% lower than 230/60/1
OPERATING PRESSURES
Air Temp
Entering
Condenser
°F/°C
Freeze Cycle Harvest Cycle
Discharge
Pressure
PSIG
Suction
Pressure
PSIG ¹
Discharge
Pressure
PSIG
Suction
Pressure
PSIG
50/10 260-340 70-38 130-150 110-120
70/21 265-350 75-38 140-165 110-135
80/27 310-375 80-39 160-190 120-155
90/32 345-400 85-40 175-200 140-165
100/38 410-500 90-48 240-260 150-195
110/43 455-510 95-48 245-260 170-200
1 Suction pressure drops gradually throughout the freeze cycle