Part Number 000014141 Rev 07 2/20  27
Section 2  Installation
4.  Add together the calculated rise, 
calculated drop, and horizontal 
distance to get the total calculated 
distance. If this total exceeds 150 feet 
(45 meters), move the condenser/
condensing unit to a new location and 
perform the calculations again.
Maximum Line Set Distance Formula
Step 1. 
Measured Rise (R) 35 feet (10.7 meters) 
Maximum   _____ x 1.7  = 
_____ Calculated Rise
Step 2. 
Measured Drop (D) 15 feet (4.5 meters) 
Maximum _____ x 6.6  = 
_____ Calculated Drop
Step 3. 
Measured Horizontal Distance (H) 100 feet 
(30 meters) Maximum 
  _____ Horizontal Distance
Step 4. 
Total Calculated Distance 150 feet (45 
meters) Maximum 
  _____ Total Calculated 
Distance
Notice
The refrigeration system warranty will 
not apply if the Manitowoc Ice Machine 
and Manitowoc CVD Condensing Unit are 
not installed according to specifications. 
This warranty also will not apply if the 
refrigeration system is modified with a 
condenser, heat reclaim device, or other 
parts or assemblies not approved by 
Manitowoc.
REMOTE CONDENSER MODELS
Step 1  Secure the Condenser.
Through-holes are provided to secure 
the condenser to a curb, rack or wooden 
timber.
n
Warning
The ice machine head section contains 
refrigerant charge. The ice machine head 
section contains refrigeration valves 
that must remain closed until proper 
installation of the line sets is completed.
n
Warning
Electrical power to the ice machine head 
section, condensing unit or condenser 
must be disconnected before proceeding.
Step 2  Route the Refrigeration Tubing.
Route the refrigeration tubing between 
the ice machine head section and the 
condenser.
•  Maximum line set exposed on rooftop is 
25% of total line set length.
•  A qualified person must perform all roof 
penetrations.
•  Interconnecting wire must be routed 
between the ice machine and condenser.
Step 3  Connect the Line Set.
In most cases, by routing the line set 
properly, shortening will not be necessary. 
When shortening or lengthening is 
required, do so before connecting the 
line set to the ice machine or the remote 
condenser. This prevents the loss of 
refrigerant in the ice machine or condenser.
The quick connect fittings on the line sets 
are equipped with access valves. Use these 
valves to recover any vapor charge from the 
line set. 