Service Manual
Table Of Contents
- Safety Notices- Definitions
- General Information
- Installation
- Maintenance
- Operation
- Troubleshooting- Troubleshooting
- Troubleshooting By Symptom- Reset To Factory Defaults
- Symptom #1 - Ice Machine Will Not Run
- #2 - Low Production, Long Freeze Cycle
- Symptom #2 - Freeze Cycle Refrigeration System Operational Analysis Tables
- Symptom #3 & #4 - Harvest Problems Self‑contained Air, Water & Remote Condenser Models
- Symptom #3 - Self-Contained Air or Water-cooled
- Symptom #3 - Remote Condenser
- Symptom #4 - Self-Contained Air, Water-Cooled or Remote
 
 
- Component Check Procedures- Electrical Components- Control Board, Display And Touchscreen
- Control Board Relay Test
- Programming A Replacement Control Board
- USB Flash Drive Specifications and Formatting
- Exporting Data to a Flash Drive
- Upgrading Firmware with a Flash Drive
- Main Fuse
- Bin Switch
- Water Level Control Circuitry
- Ice Thickness Probe (Initiates Harvest)
- Bin Level Probe
- Thermistors
- High Pressure Cutout (HPCO) Control
- Fan Cycle Control
- Harvest Assist Air Pump
- Compressor Electrical Diagnostics
- Diagnosing Start Components
 
- Refrigeration Components
- Refrigerant Recovery/Evacuation
- System Contamination Clean-Up
- Liquid Line Filter-Driers
- Replacing Pressure Controls Without Removing Refrigerant Charge
- Total System Refrigerant Charge
 
- Electrical Components
- Charts
- Diagrams- Wiring Diagrams- Wiring Diagram Legend
- IF0300/IT0420/IT0450/IT0500/IT0620/IT0750 1ph Air/Water
- IT0500/IT1200 - 1ph Remote Air-Cooled
- IF0600/IF0900/IT0900/IT1200 - 1ph Air/Water
- IF0600/IF0900/IT0900/IT1200 - 3ph Air/Water
- IT1500/IT1900 - 1ph Air/Water
- IT1500/IT1900 - 3 ph Air/Water
- IF0500/IF0600/IF0900/IT1200/IF1500 - 1ph Remote
- IF0500/IF0600/IF0900/IT1200/IF1500 - 3ph Remote Condenser
 
- Electronic Control Board
- Refrigeration Tubing Schematics
 
- Wiring Diagrams
 
88  Part Number: 000015430 Rev 02 5/20
E01 LONG FREEZE CYCLE
If the freeze time reaches 35 minutes, the control board 
automatically initiates a harvest cycle. If 3 consecutive 
35-minute freeze cycles occur, the ice machine stops.
E02 LONG HARVEST CYCLE
If the harvest time reaches 7 minutes, the control board 
will start a Thaw Cycle and automatically return the ice 
machine to the freeze cycle. After 3 consecutive long 
harvest cycles the ice machine stops.
STOPPED THE ICE MACHINE
Service Faults are designed to stop the ice machine prior 
to major component failures, most often a minor problem 
or something external to the ice machine. This may be 
difficult to diagnose, as many external problems occur 
intermittently.
Example: An ice machine stops intermittently on Service 
Fault (long freeze times). The problem could be a low 
ambient temperature at night, a water pressure drop, the 
water is turned off one night a week, etc.
Refrigeration and electrical component failures will cause 
a Service Fault trip. Eliminate all electrical components 
and external causes first. If it appears that the refrigeration 
system is causing the problem, use Manitowoc’s Freeze 
Cycle Refrigeration System Operational Analysis Table, 
along with detailed charts, checklists, and other references 
to determine the cause.
The following checklists are designed to assist the service 
technician in analysis. However, because there are many 
possible external problems, do not limit your diagnosis to 
only the items listed.