Service Manual
Table Of Contents
- Safety Notices- Definitions
- General Information
- Installation
- Maintenance
- Operation
- Troubleshooting- Troubleshooting
- Troubleshooting By Symptom- Reset To Factory Defaults
- Symptom #1 - Ice Machine Will Not Run
- #2 - Low Production, Long Freeze Cycle
- Symptom #2 - Freeze Cycle Refrigeration System Operational Analysis Tables
- Symptom #3 & #4 - Harvest Problems Self‑contained Air, Water & Remote Condenser Models
- Symptom #3 - Self-Contained Air or Water-cooled
- Symptom #3 - Remote Condenser
- Symptom #4 - Self-Contained Air, Water-Cooled or Remote
 
 
- Component Check Procedures- Electrical Components- Control Board, Display And Touchscreen
- Control Board Relay Test
- Programming A Replacement Control Board
- USB Flash Drive Specifications and Formatting
- Exporting Data to a Flash Drive
- Upgrading Firmware with a Flash Drive
- Main Fuse
- Bin Switch
- Water Level Control Circuitry
- Ice Thickness Probe (Initiates Harvest)
- Bin Level Probe
- Thermistors
- High Pressure Cutout (HPCO) Control
- Fan Cycle Control
- Harvest Assist Air Pump
- Compressor Electrical Diagnostics
- Diagnosing Start Components
 
- Refrigeration Components
- Refrigerant Recovery/Evacuation
- System Contamination Clean-Up
- Liquid Line Filter-Driers
- Replacing Pressure Controls Without Removing Refrigerant Charge
- Total System Refrigerant Charge
 
- Electrical Components
- Charts
- Diagrams- Wiring Diagrams- Wiring Diagram Legend
- IF0300/IT0420/IT0450/IT0500/IT0620/IT0750 1ph Air/Water
- IT0500/IT1200 - 1ph Remote Air-Cooled
- IF0600/IF0900/IT0900/IT1200 - 1ph Air/Water
- IF0600/IF0900/IT0900/IT1200 - 3ph Air/Water
- IT1500/IT1900 - 1ph Air/Water
- IT1500/IT1900 - 3 ph Air/Water
- IF0500/IF0600/IF0900/IT1200/IF1500 - 1ph Remote
- IF0500/IF0600/IF0900/IT1200/IF1500 - 3ph Remote Condenser
 
- Electronic Control Board
- Refrigeration Tubing Schematics
 
- Wiring Diagrams
 
174  Part Number: 000015430 Rev 02 5/20
Harvest Cycle
REMOTE CONDENSER
The head pressure control cycles into full bypass due to the 
pressure drop when the harvest valve opens. Refrigerant 
flows from the compressor to the evaporator through the 
harvest valve and the head pressure valve is out of the 
circuit.
Undercharge Symptoms
•  Long Freeze or Long Harvest in control board memory 
and an alert indicating Long Freeze or Long Harvest.
•  Harvest cycle suction pressure is low.
•  Harvest cycle discharge pressure is low.
•  Liquid line entering receiver feels warm to hot in the 
freeze cycle.
Overcharge Symptoms
•  Long Harvest in control board memory and an alert 
indicating Long Harvest is displayed.
•  Harvest cycle discharge pressure is normal.
•  Freeze cycle time, suction and discharge pressure are 
normal and the ice machine will not harvest. The sheet 
of ice cubes show little or no sign of melting when 
removed from the evaporator after the harvest cycle 
has been completed. (If the cubes are melted you have 
a release problem, clean the ice machine.)