Service Manual
Table Of Contents
- Safety Notices- Definitions
- General Information
- Installation
- Maintenance
- Operation
- Troubleshooting- Troubleshooting
- Troubleshooting By Symptom- Reset To Factory Defaults
- Symptom #1 - Ice Machine Will Not Run
- #2 - Low Production, Long Freeze Cycle
- Symptom #2 - Freeze Cycle Refrigeration System Operational Analysis Tables
- Symptom #3 & #4 - Harvest Problems Self‑contained Air, Water & Remote Condenser Models
- Symptom #3 - Self-Contained Air or Water-cooled
- Symptom #3 - Remote Condenser
- Symptom #4 - Self-Contained Air, Water-Cooled or Remote
 
 
- Component Check Procedures- Electrical Components- Control Board, Display And Touchscreen
- Control Board Relay Test
- Programming A Replacement Control Board
- USB Flash Drive Specifications and Formatting
- Exporting Data to a Flash Drive
- Upgrading Firmware with a Flash Drive
- Main Fuse
- Bin Switch
- Water Level Control Circuitry
- Ice Thickness Probe (Initiates Harvest)
- Bin Level Probe
- Thermistors
- High Pressure Cutout (HPCO) Control
- Fan Cycle Control
- Harvest Assist Air Pump
- Compressor Electrical Diagnostics
- Diagnosing Start Components
 
- Refrigeration Components
- Refrigerant Recovery/Evacuation
- System Contamination Clean-Up
- Liquid Line Filter-Driers
- Replacing Pressure Controls Without Removing Refrigerant Charge
- Total System Refrigerant Charge
 
- Electrical Components
- Charts
- Diagrams- Wiring Diagrams- Wiring Diagram Legend
- IF0300/IT0420/IT0450/IT0500/IT0620/IT0750 1ph Air/Water
- IT0500/IT1200 - 1ph Remote Air-Cooled
- IF0600/IF0900/IT0900/IT1200 - 1ph Air/Water
- IF0600/IF0900/IT0900/IT1200 - 3ph Air/Water
- IT1500/IT1900 - 1ph Air/Water
- IT1500/IT1900 - 3 ph Air/Water
- IF0500/IF0600/IF0900/IT1200/IF1500 - 1ph Remote
- IF0500/IF0600/IF0900/IT1200/IF1500 - 3ph Remote Condenser
 
- Electronic Control Board
- Refrigeration Tubing Schematics
 
- Wiring Diagrams
 
Part Number: 000015430 Rev 02 5/20 35
Design & Burst Pressure
Design Pressure 600 psig - 4137 kPa
Burst Pressure 2500 psig - 17237 kPa
Head Pressure Control Valve
Do not use a fan cycling control to try to maintain 
discharge pressure. Compressor failure will result. Any 
remote condenser connected to a Manitowoc Ice Machine 
must have the OEM head pressure control valve installed. 
Manitowoc will not accept substitute “off the shelf” head 
pressure control valves. 
Kits are available for head pressure control installation:
•  R404A Refrigerant - K00479
•  R410A Refrigerant - K00221
Fan Motor
The condenser fan must be on during the complete ice 
machine freeze cycle (do not cycle on fan cycle control). 
The ice maker has a condenser fan motor circuit for use 
with a Manitowoc condenser. It is recommended that 
this circuit be used to control the condenser fan(s) on the 
multi-circuit condenser to assure it is on at the proper 
time. Do not exceed the rated amps for the fan motor 
circuit listed on the ice machine’s serial tag.
Internal Condenser Volume
The multi-circuit condenser internal volume must not 
be less than or exceed that used by Manitowoc. Do 
not exceed internal volume and try to add charge to 
compensate, as compressor failure will result.
Model
Minimum 
ft³ (cm3)
Maximum 
ft3 (cm³)
IF0500N IT0500N 0.020 (566) 0.030 (850)
IF0600/IF0900N 
IT0900N/IT1200N
0.045 (1274) 0.060 (1699)
IT1500N/IT1900N/IF0900 0.085 (2407) 0.105 (2973)