Service Manual
Table Of Contents
- Safety Notices- Definitions
- General Information
- Installation
- Maintenance
- Operation
- Troubleshooting- Troubleshooting
- Troubleshooting By Symptom- Reset To Factory Defaults
- Symptom #1 - Ice Machine Will Not Run
- #2 - Low Production, Long Freeze Cycle
- Symptom #2 - Freeze Cycle Refrigeration System Operational Analysis Tables
- Symptom #3 & #4 - Harvest Problems Self‑contained Air, Water & Remote Condenser Models
- Symptom #3 - Self-Contained Air or Water-cooled
- Symptom #3 - Remote Condenser
- Symptom #4 - Self-Contained Air, Water-Cooled or Remote
 
 
- Component Check Procedures- Electrical Components- Control Board, Display And Touchscreen
- Control Board Relay Test
- Programming A Replacement Control Board
- USB Flash Drive Specifications and Formatting
- Exporting Data to a Flash Drive
- Upgrading Firmware with a Flash Drive
- Main Fuse
- Bin Switch
- Water Level Control Circuitry
- Ice Thickness Probe (Initiates Harvest)
- Bin Level Probe
- Thermistors
- High Pressure Cutout (HPCO) Control
- Fan Cycle Control
- Harvest Assist Air Pump
- Compressor Electrical Diagnostics
- Diagnosing Start Components
 
- Refrigeration Components
- Refrigerant Recovery/Evacuation
- System Contamination Clean-Up
- Liquid Line Filter-Driers
- Replacing Pressure Controls Without Removing Refrigerant Charge
- Total System Refrigerant Charge
 
- Electrical Components
- Charts
- Diagrams- Wiring Diagrams- Wiring Diagram Legend
- IF0300/IT0420/IT0450/IT0500/IT0620/IT0750 1ph Air/Water
- IT0500/IT1200 - 1ph Remote Air-Cooled
- IF0600/IF0900/IT0900/IT1200 - 1ph Air/Water
- IF0600/IF0900/IT0900/IT1200 - 3ph Air/Water
- IT1500/IT1900 - 1ph Air/Water
- IT1500/IT1900 - 3 ph Air/Water
- IF0500/IF0600/IF0900/IT1200/IF1500 - 1ph Remote
- IF0500/IF0600/IF0900/IT1200/IF1500 - 3ph Remote Condenser
 
- Electronic Control Board
- Refrigeration Tubing Schematics
 
- Wiring Diagrams
 
Part Number: 000015430 Rev 02 5/20 177
5.  Discharge line temperature is greater than 150°F 
(66°C) [22" Models Only - 140°F (60°C)] at the end of 
the freeze cycle? 
See “Discharge Line Temperature Analysis” on 
.
6.  Connect refrigeration manifold gauge set to the 
access valves on the front of the ice machine. 
Establish baseline by recording suction and discharge 
pressure and freeze & harvest cycle times. (Refer to 
“Cycle Times/24-Hour Ice Production/Refrigerant 
Pressure Charts” on page 201 for data collection 
detail.)
7.  Freeze cycle Head Pressure is in the range indicated in 
the cycle time/24 hour ice production and operational 
pressure chart? 
If the head pressure is low refer to “Freeze Cycle 
.
8.  Freeze cycle Suction Pressure normal? 
Refer to  if 
suction pressure is high or low.
9.  Harvest cycle suction and discharge pressures are 
lower than indicated in the cycle times/refrigerant 
pressures/24 hour ice production chart? 
Replace Harvest Pressure Regulating solenoid.