Service Manual
Table Of Contents
- Safety Notices- Definitions
- General Information
- Installation
- Maintenance
- Operation
- Troubleshooting- Troubleshooting
- Troubleshooting By Symptom- Reset To Factory Defaults
- Symptom #1 - Ice Machine Will Not Run
- #2 - Low Production, Long Freeze Cycle
- Symptom #2 - Freeze Cycle Refrigeration System Operational Analysis Tables
- Symptom #3 & #4 - Harvest Problems Self‑contained Air, Water & Remote Condenser Models
- Symptom #3 - Self-Contained Air or Water-cooled
- Symptom #3 - Remote Condenser
- Symptom #4 - Self-Contained Air, Water-Cooled or Remote
 
 
- Component Check Procedures- Electrical Components- Control Board, Display And Touchscreen
- Control Board Relay Test
- Programming A Replacement Control Board
- USB Flash Drive Specifications and Formatting
- Exporting Data to a Flash Drive
- Upgrading Firmware with a Flash Drive
- Main Fuse
- Bin Switch
- Water Level Control Circuitry
- Ice Thickness Probe (Initiates Harvest)
- Bin Level Probe
- Thermistors
- High Pressure Cutout (HPCO) Control
- Fan Cycle Control
- Harvest Assist Air Pump
- Compressor Electrical Diagnostics
- Diagnosing Start Components
 
- Refrigeration Components
- Refrigerant Recovery/Evacuation
- System Contamination Clean-Up
- Liquid Line Filter-Driers
- Replacing Pressure Controls Without Removing Refrigerant Charge
- Total System Refrigerant Charge
 
- Electrical Components
- Charts
- Diagrams- Wiring Diagrams- Wiring Diagram Legend
- IF0300/IT0420/IT0450/IT0500/IT0620/IT0750 1ph Air/Water
- IT0500/IT1200 - 1ph Remote Air-Cooled
- IF0600/IF0900/IT0900/IT1200 - 1ph Air/Water
- IF0600/IF0900/IT0900/IT1200 - 3ph Air/Water
- IT1500/IT1900 - 1ph Air/Water
- IT1500/IT1900 - 3 ph Air/Water
- IF0500/IF0600/IF0900/IT1200/IF1500 - 1ph Remote
- IF0500/IF0600/IF0900/IT1200/IF1500 - 3ph Remote Condenser
 
- Electronic Control Board
- Refrigeration Tubing Schematics
 
- Wiring Diagrams
 
160  Part Number: 000015430 Rev 02 5/20
SYMPTOM
Alert icon on the display and the alert indicates a T1, T2, 
T3, or T4 Fault.
CHECK PROCEDURE
Navigate to Menu/Service/Data/Real Time data/Time & 
Temperature
NOTE: An open thermistor will display less than -10°F 
(-23°C) and a shorted thermistor will display higher than 
400°F (204°C).
Thermistor Test
1.  Disconnect thermistor from control board and 
measure resistance. 
2.  Measure temperature at the thermistor.
3.  Compare measured resistance/temperature readings 
to resistance/temperature relationship chart.
A.  Within 10% of the published resistance value - 
Thermistor is good.
B.  Not within 10% of the published resistance 
Control Board Test
1.  Disconnect thermistor from control board - The 
display temperature reading, dropping below -10°F 
(-23°C) indicates the control board is good.
2.  Short thermistor pins - The display temperature 
reading, higher than 400°F (204°C) indicates the 
control board is good.