Service Manual
Table Of Contents
- Safety Notices
- Definitions
- General Information
- Installation
- Maintenance
- Operation
- Troubleshooting
- Troubleshooting
- Troubleshooting By Symptom
- Reset To Factory Defaults
- Symptom #1 - Ice Machine Will Not Run
- #2 - Low Production, Long Freeze Cycle
- Symptom #2 - Freeze Cycle Refrigeration System Operational Analysis Tables
- Symptom #3 & #4 - Harvest Problems Self‑contained Air, Water & Remote Condenser Models
- Symptom #3 - Self-Contained Air or Water-cooled
- Symptom #3 - Remote Condenser
- Symptom #4 - Self-Contained Air, Water-Cooled or Remote
- Component Check Procedures
- Electrical Components
- Control Board, Display And Touchscreen
- Control Board Relay Test
- Programming A Replacement Control Board
- USB Flash Drive Specifications and Formatting
- Exporting Data to a Flash Drive
- Upgrading Firmware with a Flash Drive
- Main Fuse
- Bin Switch
- Water Level Control Circuitry
- Ice Thickness Probe (Initiates Harvest)
- Bin Level Probe
- Thermistors
- High Pressure Cutout (HPCO) Control
- Fan Cycle Control
- Harvest Assist Air Pump
- Compressor Electrical Diagnostics
- Diagnosing Start Components
- Refrigeration Components
- Refrigerant Recovery/Evacuation
- System Contamination Clean-Up
- Liquid Line Filter-Driers
- Replacing Pressure Controls Without Removing Refrigerant Charge
- Total System Refrigerant Charge
- Electrical Components
- Charts
- Diagrams
- Wiring Diagrams
- Wiring Diagram Legend
- IF0300/IT0420/IT0450/IT0500/IT0620/IT0750 1ph Air/Water
- IT0500/IT1200 - 1ph Remote Air-Cooled
- IF0600/IF0900/IT0900/IT1200 - 1ph Air/Water
- IF0600/IF0900/IT0900/IT1200 - 3ph Air/Water
- IT1500/IT1900 - 1ph Air/Water
- IT1500/IT1900 - 3 ph Air/Water
- IF0500/IF0600/IF0900/IT1200/IF1500 - 1ph Remote
- IF0500/IF0600/IF0900/IT1200/IF1500 - 3ph Remote Condenser
- Electronic Control Board
- Refrigeration Tubing Schematics
- Wiring Diagrams
234 Part Number: 000015430 Rev 02 5/20
IT1900N
Remote Air-Cooled Condenser Model
Characteristics vary depending on operating conditions.
CYCLE TIMES
Freeze Time + Harvest Time = Total Cycle Time
Air Temp.
Entering
Condenser °F/°C
Freeze Time
Harvest
Time ¹
Water Temperature °F/°C
50/10 70/21 90/32
70/21 8.9-10.1 9.4-10.7 11.0-12.5
1-2.5
80/27 9.4-10.7 10.0-11.4 11.8-13.4
90/32 10.2-11.6 10.8-12.3 12.9-14.6
100/38 11.7-13.4 12.6-14.3 14.0-15.8
110/43 13.7-15.5 14.0-15.8 14.3-16.2
1 Times in minutes
24 HOUR ICE PRODUCTION
Air Temp. Entering
Condenser °F/°C
Water Temperature °F/°C ¹
50/10 70/21 90/32
70/21 1830 1740 1520
80/27 1740 1650 1430
90/32 1625 1540 1320
100/38 1435 1350 1230
110/43 1250 1230 1205
1 Based on average ice slab weight of 13.2- 14.8 lb.
OPERATING PRESSURES
Air Temp
Entering
Condenser
°F/°C
Freeze Cycle Harvest Cycle
Discharge
Pressure
PSIG
Suction
Pressure
PSIG ¹
Discharge
Pressure
PSIG
Suction
Pressure
PSIG
-20/-29 260-290 65-38 170-180 110-130
50/10 270-330 70-38 170-180 115-130
70/21 280-340 75-38 170-180 120-130
80/27 320-400 75-39 170-190 130-150
90/32 345-420 75-40 170-195 140-155
100/38 395-480 85-46 180-210 140-155
110/43 405-485 85-47 180-215 140-155
1 Suction pressure drops gradually throughout the freeze cycle