Service Manual
Table Of Contents
- Safety Notices
- Definitions
- General Information
- Installation
- Maintenance
- Operation
- Troubleshooting
- Troubleshooting
- Troubleshooting By Symptom
- Reset To Factory Defaults
- Symptom #1 - Ice Machine Will Not Run
- #2 - Low Production, Long Freeze Cycle
- Symptom #2 - Freeze Cycle Refrigeration System Operational Analysis Tables
- Symptom #3 & #4 - Harvest Problems Self‑contained Air, Water & Remote Condenser Models
- Symptom #3 - Self-Contained Air or Water-cooled
- Symptom #3 - Remote Condenser
- Symptom #4 - Self-Contained Air, Water-Cooled or Remote
- Component Check Procedures
- Electrical Components
- Control Board, Display And Touchscreen
- Control Board Relay Test
- Programming A Replacement Control Board
- USB Flash Drive Specifications and Formatting
- Exporting Data to a Flash Drive
- Upgrading Firmware with a Flash Drive
- Main Fuse
- Bin Switch
- Water Level Control Circuitry
- Ice Thickness Probe (Initiates Harvest)
- Bin Level Probe
- Thermistors
- High Pressure Cutout (HPCO) Control
- Fan Cycle Control
- Harvest Assist Air Pump
- Compressor Electrical Diagnostics
- Diagnosing Start Components
- Refrigeration Components
- Refrigerant Recovery/Evacuation
- System Contamination Clean-Up
- Liquid Line Filter-Driers
- Replacing Pressure Controls Without Removing Refrigerant Charge
- Total System Refrigerant Charge
- Electrical Components
- Charts
- Diagrams
- Wiring Diagrams
- Wiring Diagram Legend
- IF0300/IT0420/IT0450/IT0500/IT0620/IT0750 1ph Air/Water
- IT0500/IT1200 - 1ph Remote Air-Cooled
- IF0600/IF0900/IT0900/IT1200 - 1ph Air/Water
- IF0600/IF0900/IT0900/IT1200 - 3ph Air/Water
- IT1500/IT1900 - 1ph Air/Water
- IT1500/IT1900 - 3 ph Air/Water
- IF0500/IF0600/IF0900/IT1200/IF1500 - 1ph Remote
- IF0500/IF0600/IF0900/IT1200/IF1500 - 3ph Remote Condenser
- Electronic Control Board
- Refrigeration Tubing Schematics
- Wiring Diagrams
Part Number: 000015430 Rev 02 5/20 217
IT0620 SERIES
IT0620A
Self-Contained Air-Cooled Model
Characteristics vary depending on operating conditions.
CYCLE TIMES
Freeze Time + Harvest Time = Total Cycle Time
Air Temp.
Entering
Condenser °F/°C
Freeze Time
Harvest
Time ¹
Water Temperature °F/°C
50/10 70/21 90/32
70/21 7.2-8.5 7.9-9.3 8.2-9.6
1-2.5
80/27 7.9-9.3 8.7-10.2 9.0-10.6
90/32 8.5-10.0 9.4-11.0 9.8-11.4
100/38 9.4-11.0 10.4-12.2 10.9-12.7
110/43 9.9-11.6 11.1-12.9 11.6-13.5
1 Times in minutes
24 HOUR ICE PRODUCTION
Air Temp. Entering
Condenser °F/°C
Water Temperature °F/°C ¹
50/10 70/21 90/32
70/21 560 520 505
80/27 520 480 465
90/32 490 450 435
100/38 450 410 395
110/43 430 390 375
1 Based on average ice slab weight of 3.4 - 3.9 lb.
OPERATING PRESSURES
Air Temp
Entering
Condenser
°F/°C
Freeze Cycle Harvest Cycle
Discharge
Pressure
PSIG
Suction
Pressure
PSIG ¹
Discharge
Pressure
PSIG
Suction
Pressure
PSIG
50/10 255-335 60-30 155-170 105-130
70/21 270-340 70-30 170-200 115-135
80/27 270-340 75-35 170-200 115-135
90/32 350-405 75-38 205-240 140-155
100/38 450-520 90-40 290-340 160-235
110/43 450-540 90-42 290-340 160-235
1 Suction pressure drops gradually throughout the freeze cycle