Service Manual
Table Of Contents
- Safety Notices
- Definitions
- General Information
- Installation
- Maintenance
- Operation
- Troubleshooting
- Troubleshooting
- Troubleshooting By Symptom
- Reset To Factory Defaults
- Symptom #1 - Ice Machine Will Not Run
- #2 - Low Production, Long Freeze Cycle
- Symptom #2 - Freeze Cycle Refrigeration System Operational Analysis Tables
- Symptom #3 & #4 - Harvest Problems Self‑contained Air, Water & Remote Condenser Models
- Symptom #3 - Self-Contained Air or Water-cooled
- Symptom #3 - Remote Condenser
- Symptom #4 - Self-Contained Air, Water-Cooled or Remote
- Component Check Procedures
- Electrical Components
- Control Board, Display And Touchscreen
- Control Board Relay Test
- Programming A Replacement Control Board
- USB Flash Drive Specifications and Formatting
- Exporting Data to a Flash Drive
- Upgrading Firmware with a Flash Drive
- Main Fuse
- Bin Switch
- Water Level Control Circuitry
- Ice Thickness Probe (Initiates Harvest)
- Bin Level Probe
- Thermistors
- High Pressure Cutout (HPCO) Control
- Fan Cycle Control
- Harvest Assist Air Pump
- Compressor Electrical Diagnostics
- Diagnosing Start Components
- Refrigeration Components
- Refrigerant Recovery/Evacuation
- System Contamination Clean-Up
- Liquid Line Filter-Driers
- Replacing Pressure Controls Without Removing Refrigerant Charge
- Total System Refrigerant Charge
- Electrical Components
- Charts
- Diagrams
- Wiring Diagrams
- Wiring Diagram Legend
- IF0300/IT0420/IT0450/IT0500/IT0620/IT0750 1ph Air/Water
- IT0500/IT1200 - 1ph Remote Air-Cooled
- IF0600/IF0900/IT0900/IT1200 - 1ph Air/Water
- IF0600/IF0900/IT0900/IT1200 - 3ph Air/Water
- IT1500/IT1900 - 1ph Air/Water
- IT1500/IT1900 - 3 ph Air/Water
- IF0500/IF0600/IF0900/IT1200/IF1500 - 1ph Remote
- IF0500/IF0600/IF0900/IT1200/IF1500 - 3ph Remote Condenser
- Electronic Control Board
- Refrigeration Tubing Schematics
- Wiring Diagrams
154 Part Number: 000015430 Rev 02 5/20
The initial numbers displayed are constantly changing
and are greater than 3000.
When the initial reading is 300 or lower and the tap test
reading exceeds the initial reading by 3000 or more, the
ice thickness probe and control board are both operating
correctly.
The initial numbers displayed do not change or initial
numbers did not increase by 3000 during tap test.
• Verify the ice thickness probe connector is properly
plugged into the board and the ice thickness probe
wiring is correct. If the wiring is incorrect replace the
ice thickness probe.
Ice Probe Connector On Control Board
Pin 1 (+) Red
Pin 2 (-) Black
Pin 3 Twisted Wire
10. Unplug the ice thickness probe and set a VOM to DC
voltage scale - Measure voltage across Pin 1 (+) Red
Wire and Pin 2 (-) Black Wire. Refer to “Electronic
.
A. Voltage measures 3.25 to 3.35 VDC = Replace ice
thickness probe.
B. Voltage does not measure 3.25 to 3.35 VDC =
Replace the control board.