Service Manual
Table Of Contents
- Safety Notices
- Definitions
- General Information
- Installation
- Maintenance
- Operation
- Troubleshooting
- Troubleshooting
- Troubleshooting By Symptom
- Reset To Factory Defaults
- Symptom #1 - Ice Machine Will Not Run
- #2 - Low Production, Long Freeze Cycle
- Symptom #2 - Freeze Cycle Refrigeration System Operational Analysis Tables
- Symptom #3 & #4 - Harvest Problems Self‑contained Air, Water & Remote Condenser Models
- Symptom #3 - Self-Contained Air or Water-cooled
- Symptom #3 - Remote Condenser
- Symptom #4 - Self-Contained Air, Water-Cooled or Remote
- Component Check Procedures
- Electrical Components
- Control Board, Display And Touchscreen
- Control Board Relay Test
- Programming A Replacement Control Board
- USB Flash Drive Specifications and Formatting
- Exporting Data to a Flash Drive
- Upgrading Firmware with a Flash Drive
- Main Fuse
- Bin Switch
- Water Level Control Circuitry
- Ice Thickness Probe (Initiates Harvest)
- Bin Level Probe
- Thermistors
- High Pressure Cutout (HPCO) Control
- Fan Cycle Control
- Harvest Assist Air Pump
- Compressor Electrical Diagnostics
- Diagnosing Start Components
- Refrigeration Components
- Refrigerant Recovery/Evacuation
- System Contamination Clean-Up
- Liquid Line Filter-Driers
- Replacing Pressure Controls Without Removing Refrigerant Charge
- Total System Refrigerant Charge
- Electrical Components
- Charts
- Diagrams
- Wiring Diagrams
- Wiring Diagram Legend
- IF0300/IT0420/IT0450/IT0500/IT0620/IT0750 1ph Air/Water
- IT0500/IT1200 - 1ph Remote Air-Cooled
- IF0600/IF0900/IT0900/IT1200 - 1ph Air/Water
- IF0600/IF0900/IT0900/IT1200 - 3ph Air/Water
- IT1500/IT1900 - 1ph Air/Water
- IT1500/IT1900 - 3 ph Air/Water
- IF0500/IF0600/IF0900/IT1200/IF1500 - 1ph Remote
- IF0500/IF0600/IF0900/IT1200/IF1500 - 3ph Remote Condenser
- Electronic Control Board
- Refrigeration Tubing Schematics
- Wiring Diagrams
Part Number: 000015430 Rev 02 5/20 153
Ice Thickness Probe Diagnostics
1. Perform Control Board Self Check and insure the
internal ITP circuit passes before proceeding.
(Menu/Service/Diagnostics/Control Board/Self Check)
• Ice Thickness Circuit: Pass = Continue with step #2.
• Ice Thickness Circuit: Fail = Change control board.
2. Remove all ice from the evaporator when present.
3. Press the On/Off button and turn off the ice machine.
4. Disconnect power to the ice machine at the main
disconnect.
5. Inspect the ice thickness probe for physical damage.
On the face of the probe look for bulging, cracks
around the nipple and deformed pivot pins or pivot
pin arms.
6. Verify the ice thickness probe gap is approximately
9/32 in. (7 mm) and the ice thickness probe wire and
bracket do not restrict movement of the probe. See
.
7. Reapply power to the ice machine at the main
disconnect and confirm the ice machine is off.
8. Navigate to Real Time data (Menu/Service/Data/
Real Time data/Inputs) and observe ITP FFT 100 Hz &
9. Observe the initial number range and perform a tap
test.
• Remove the water curtain or splash shield if present.
• Lift the ice thickness probe and carefully tap the nipple
on the face of the probe for at least 10 seconds.
NOTE: When performing tap test:
• Pass = ITP is not the problem
• Fail = Check DC Voltage on the control board