Service Manual
Table Of Contents
- Safety Notices
- Definitions
- General Information
- Installation
- Maintenance
- Operation
- Troubleshooting
- Troubleshooting
- Troubleshooting By Symptom
- Reset To Factory Defaults
- Symptom #1 - Ice Machine Will Not Run
- #2 - Low Production, Long Freeze Cycle
- Symptom #2 - Freeze Cycle Refrigeration System Operational Analysis Tables
- Symptom #3 & #4 - Harvest Problems Self‑contained Air, Water & Remote Condenser Models
- Symptom #3 - Self-Contained Air or Water-cooled
- Symptom #3 - Remote Condenser
- Symptom #4 - Self-Contained Air, Water-Cooled or Remote
- Component Check Procedures
- Electrical Components
- Control Board, Display And Touchscreen
- Control Board Relay Test
- Programming A Replacement Control Board
- USB Flash Drive Specifications and Formatting
- Exporting Data to a Flash Drive
- Upgrading Firmware with a Flash Drive
- Main Fuse
- Bin Switch
- Water Level Control Circuitry
- Ice Thickness Probe (Initiates Harvest)
- Bin Level Probe
- Thermistors
- High Pressure Cutout (HPCO) Control
- Fan Cycle Control
- Harvest Assist Air Pump
- Compressor Electrical Diagnostics
- Diagnosing Start Components
- Refrigeration Components
- Refrigerant Recovery/Evacuation
- System Contamination Clean-Up
- Liquid Line Filter-Driers
- Replacing Pressure Controls Without Removing Refrigerant Charge
- Total System Refrigerant Charge
- Electrical Components
- Charts
- Diagrams
- Wiring Diagrams
- Wiring Diagram Legend
- IF0300/IT0420/IT0450/IT0500/IT0620/IT0750 1ph Air/Water
- IT0500/IT1200 - 1ph Remote Air-Cooled
- IF0600/IF0900/IT0900/IT1200 - 1ph Air/Water
- IF0600/IF0900/IT0900/IT1200 - 3ph Air/Water
- IT1500/IT1900 - 1ph Air/Water
- IT1500/IT1900 - 3 ph Air/Water
- IF0500/IF0600/IF0900/IT1200/IF1500 - 1ph Remote
- IF0500/IF0600/IF0900/IT1200/IF1500 - 3ph Remote Condenser
- Electronic Control Board
- Refrigeration Tubing Schematics
- Wiring Diagrams
Part Number: 000015430 Rev 02 5/20 147
WATER LEVEL CONTROL CIRCUITRY
FUNCTION
The water level probe controls the water level by sensing
whether water is or is not contacting the water level
probe. The water level probe has three sensing probes.
Two probes are equal in length and are used to measures
conductivity for diagnostics, ice clarity and water miser
options. Factory default settings measure resistance from
both long probes to the short probe.
SPECIFICATIONS
Freeze Cycle Water Level Setting
The water level is not adjustable. If the water level is
incorrect, check the water level probe position. Reposition
or clean the probe as necessary.
Water Inlet Valve Safety Shut-Off
In the event of a water level probe failure, this feature
limits the maximum amount of time the water inlet valve
can remain.
SINGLE EVAPORATOR MODELS
Regardless of the water level probe input, the control
board automatically shuts off the water inlet valve if it
remains on for 12.5 continuous minutes (30 seconds in
prechill and two 6 minute periods in the freeze cycle).
Initial cycle is 14 minutes and 12.5 minutes thereafter.
DUAL EVAPORATOR MODELS
Regardless of the water level probe input, the control
board automatically shuts off the water inlet valve if it
remains on for 16.5 continuous minutes (30 seconds in
prechill and two 8 minute periods in the freeze cycle).
Initial cycle is 18 minutes and 16.5 minutes thereafter.