Service Manual
Table Of Contents
- Safety Notices
- Definitions
- General Information
- Installation
- Stacking Two Ice Machines on a Single Storage Bin
- Location of Ice Machine
- Clearance Requirements
- Dual Evaporator Model Installation on a Manitowoc Bin
- Ice Machine on a Dispenser Installation
- Water Supply and Drains
- Lineset Applications
- QuietQube® Remote Condensing Unit
- Additional Refrigerant Charge For 51' to 100' Line Sets
- Maintenance
- Operation
- Menu Navigation
- Component Check Procedures
- Control Board, Display And Touchscreen
- Operating an ice machine without a Touchscreen
- Control Board Relay Test
- Programming A Replacement Control Board
- USB Flash Drive Specifications and Formatting
- Exporting Data to a Flash Drive
- Upgrading Firmware with a Flash Drive
- Main Fuse
- Bin Switch
- Water Level Control Circuitry
- Ice Thickness Probe (Initiates Harvest)
- Bin Level Probe
- Thermistors
- High Pressure Cutout (HPCO) Control
- Low Pressure Cutout (LPCO) Control
- Compressor Time Delay
- Fan Cycle Control
- Harvest Assist Air Pump
- Compressor Electrical Diagnostics
- Diagnosing Start Components
- Refrigeration Components
- Recovery/Evacuation/Charging Procedures QuietQube® Models
- System Contamination Clean-Up
- Total System Refrigerant Charge QuietQube® CVD Models
- Control Board, Display And Touchscreen
- Charts
- Diagrams
84 Part Number: 000015431 Rev 02 6/20
E09 Flooding Evaporator Fault Single Evaporator, Single
Circuit
Average compressor discharge line temperature during
the first 6 minutes of the freeze cycle (T2) compared to the
average of the Prechill (T1) +50°F is less than 1.05°F.
E10 Flooding Evaporator Fault Dual TXV, Dual Circuit
Average compressor discharge line temperature during
the first 6 minutes of the freeze cycle (T2) compared to the
average of the Prechill (T1) +50°F is less than 1.05°F.
E11 Refrigeration Fault
The compressor discharge temperature did not increase
by at least 10° F, and the evaporator temperature did not
decreased by at least 10° F - Measured from Refrigeration
Start up or Prechill until 2 minutes into the Freeze cycle.
E12 Curtain Switch Fault Open more than 24 hours
The ice machine is set to ice making and remains in bin
full condition for more than 24 hours. The curtain switch is
open or curtain is off.
E13 Spare
E14 Spare
E15 Fan Cycle Control Fault - Low Liquid Line Temperature
The liquid line temperature dropped below 60° F for more
than one continuous minute during the freeze cycle.
E16 Remote Condensing Unit Fault (CVD Only)
The liquid line temperature dropped below 40° F, or
exceeded 140° F for more than 1 continuous minute during
the freeze cycle.
E17 Spare
E18 Spare