Service Manual
Table Of Contents
- Safety Notices
- Definitions
- General Information
- Installation
- Stacking Two Ice Machines on a Single Storage Bin
- Location of Ice Machine
- Clearance Requirements
- Dual Evaporator Model Installation on a Manitowoc Bin
- Ice Machine on a Dispenser Installation
- Water Supply and Drains
- Lineset Applications
- QuietQube® Remote Condensing Unit
- Additional Refrigerant Charge For 51' to 100' Line Sets
- Maintenance
- Operation
- Menu Navigation
- Component Check Procedures
- Control Board, Display And Touchscreen
- Operating an ice machine without a Touchscreen
- Control Board Relay Test
- Programming A Replacement Control Board
- USB Flash Drive Specifications and Formatting
- Exporting Data to a Flash Drive
- Upgrading Firmware with a Flash Drive
- Main Fuse
- Bin Switch
- Water Level Control Circuitry
- Ice Thickness Probe (Initiates Harvest)
- Bin Level Probe
- Thermistors
- High Pressure Cutout (HPCO) Control
- Low Pressure Cutout (LPCO) Control
- Compressor Time Delay
- Fan Cycle Control
- Harvest Assist Air Pump
- Compressor Electrical Diagnostics
- Diagnosing Start Components
- Refrigeration Components
- Recovery/Evacuation/Charging Procedures QuietQube® Models
- System Contamination Clean-Up
- Total System Refrigerant Charge QuietQube® CVD Models
- Control Board, Display And Touchscreen
- Charts
- Diagrams
154 Part Number: 000015431 Rev 02 6/20
HIGH PRESSURE CUTOUT (HPCO) CONTROL
FUNCTION
Stops the ice machine if subjected to excessive high-side
pressure. The HPCO control is normally closed, and opens
on a rise in discharge pressure.
SPECIFICATIONS
Specifications
Cut-Out Cut-In
R404A 450 psig ±7
(3102 kPa ±48
31 bar ±0.48)
300 psig ±10
(2068 kPa ±69
20.68 bar ±0.69)
R410A 600 psig ±10
(3147 kPa ±69)
450 psig ±10
(3103 kPa ±69)
Automatic Reset
Opening the HPCO will initiate the 5 minute compressor
time delay. Repeated HPCO opening/closing or failure to
close will result in an E01 long freeze error.
CHECK PROCEDURE
1. Connect manifold gauges to ice machine.
2. Hook voltmeter in parallel across the fan cycle control,
leaving wires attached.
3. Refer to chart below.
HPCO Setpoint Reading Should Be HPCO Contact Position
Below Cut-Out 0 Volts Closed
Above Cut-In Line Voltage Open