Engineered for Ease ® QuietQube Remote Condensing Unit Ice Machines Technician’s Handbook Part Number: 000015431 Rev 02 6/20
Safety Notices Read these precautions to prevent personal injury: • Read this manual thoroughly before operating, installing or performing maintenance on the equipment. Failure to follow instructions in this manual can cause property damage, injury or death. • Routine adjustments and maintenance procedures outlined in this manual are not covered by the warranty. • Proper installation, care and maintenance are essential for maximum performance and trouble-free operation of your equipment.
DEFINITIONS DANGER Indicates a hazardous situation that, if not avoided, will result in death or serious injury. This applies to the most extreme situations. nWarning Indicates a hazardous situation that, if not avoided, could result in death or serious injury. ,Caution Indicates a hazardous situation that, if not avoided, could result in minor or moderate injury. Notice Indicates information considered important, but not hazard-related (e.g. messages relating to property damage).
nWarning Follow these electrical requirements during installation of this equipment: • All field wiring must conform to all applicable codes of the authority having jurisdiction. It is the responsibility of the end user to provide the disconnect means to satisfy local codes. Refer to rating plate for proper voltage. • This appliance must be grounded. • This equipment must be positioned so that the plug is accessible unless other means for disconnection from the power supply (e.g.
nWarning Follow these precautions to prevent personal injury during installation of this equipment: • Installation must comply with all applicable equipment fire and health codes with the authority having jurisdiction. • Connect to a potable water supply only. • To avoid instability the installation area must be capable of supporting the combined weight of the equipment and product. Additionally the equipment must be level side to side and front to back.
nWarning Follow these precautions to prevent personal injury while operating or maintaining this equipment: • Legs or casters must be installed and the legs/casters must be screwed in completely. When casters are installed the mass of this unit will allow it to move uncontrolled on an inclined surface. These units must be tethered/secured to comply with all applicable codes. Swivel casters must be mounted on the front and rigid casters must be mounted on the rear.
nWarning Follow these precautions to prevent personal injury while operating or maintaining this equipment: • Objects placed or dropped in the bin can affect human health and safety. Locate and remove any objects immediately. • Never use sharp objects or tools to remove ice or frost. • Do not use mechanical devices or other means to accelerate the defrosting process. • When using cleaning fluids or chemicals, rubber gloves and eye protection (and/or face shield) must be worn.
DANGER Follow these precautions to prevent personal injury during use and maintenance of this equipment: • It is the responsibility of the equipment owner to perform a Personal Protective Equipment Hazard Assessment to ensure adequate protection during maintenance procedures. • Do Not Store Or Use Gasoline Or Other Flammable Vapors Or Liquids In The Vicinity Of This Or Any Other Appliance. Never use flammable oil soaked cloths or combustible cleaning solutions for cleaning.
nWarning Follow these precautions to prevent personal injury while operating or maintaining this equipment. • Refer to nameplate to identify the type of refrigerant in your equipment. • Only trained and qualified personnel aware of the dangers are allowed to work on the equipment. • Read this manual thoroughly before operating, installing or performing maintenance on the equipment. Failure to follow instructions in this manual can cause property damage, injury or death. • Crush/Pinch Hazard.
nWarning Follow these precautions to prevent personal injury during use and maintenance of this equipment: • Units with two power cords must be plugged into individual branch circuits. During movement, cleaning or repair it is necessary to unplug both power cords. • Never use a high-pressure water jet for cleaning on the interior or exterior of this unit. Do not use power cleaning equipment, steel wool, scrapers or wire brushes on stainless steel or painted surfaces.
THIS PAGE INTENTIONALLY LEFT BLANK
Table of Contents Safety Notices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 General Information Model Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . QuietQube® Models . . . . . . . . . . . . . . . . . . . . . How to Read a Model Number . . . . . . . . . . . . . . . .
Maintenance Detailed Cleaning and Sanitizing . . . . . . . . . . . . . . General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Detailed Descaling/Sanitizing Procedure . . . . Remedial Cleaning Procedure . . . . . . . . . . . . . iAuCS® . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Exterior Cleaning . . . . . . . . . . . . . . . . . . . . . . .
Menu Navigation Touch Screen Features . . . . . . . . . . . . . . . . . . . . . . . 69 Home screen icon descriptions . . . . . . . . . . . . 71 Setup Wizard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73 Menu Navigation Overview . . . . . . . . . . . . . . . . . . 74 Settings Menu Screen Navigation . . . . . . . . . . 74 USB Flash Drive Specifications and Formatting . . . . . . . . . . . . .
Recovery/Evacuation/Charging Procedures QuietQube® Models . . . . . . . . . . . . . . . . . . . . . . . 169 Connections . . . . . . . . . . . . . . . . . . . . . . . . . . 170 Recovery/Evacuation Procedures . . . . . . . . . 171 Charging Procedures . . . . . . . . . . . . . . . . . . . 172 System Contamination Clean-Up . . . . . . . . . . . . . 173 Determining Severity of Contamination . . . .
Diagrams Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . 193 Wiring Diagram Legend . . . . . . . . . . . . . . . . . 193 IF0600C/IBF0620C/IBF0820C/IF0900C 1ph . 194 IT1200C/IBT1020C 1ph . . . . . . . . . . . . . . . . . 196 IF1400C/IF1800C/IF2100C 1ph . . . . . . . . . . . 198 CVD 1ph Condensing Unit . . . . . . . . . . . . . . . 200 CVD 3ph Condensing Unit . . . . . . . . . . . . . . .
THIS PAGE INTENTIONALLY LEFT BLANK 18 Part Number: 000015431 Rev 02 6/20
General Information Model Numbers QUIETQUBE® MODELS Ice Machine Head Section IYF0600C IBF0620C IBF0820C IYF0900C IBT1020C IDT1200C IYT1200C IDF1400C IYF1400C IDF1800C IYF1800C IDF2100C IYF2100C CVD® Condensing Unit CVDF0600 CVDF0900 CVDT1200 CVDF1400 CVDF1800 CVDF2100 nWarning All Manitowoc ice machines require the ice storage system (bin, dispenser, etc.) to incorporate an ice deflector.
Regular Dice Half-dice Flake Nugget Gourmet for IB only REFRIGERANT TYPE P R290 (propane) F R404A (four) T R410A (ten) B R600A (butane) E R134A (eight) 2= 22" wide cabinet #= all other #s mean producon value ELECTRICAL CONFIGURATION 161 = 115/60/1 261 = 208-230/60/1 251 = 220-240/50/1 (S=230) 263 = 208-230/60/3 271 = 200/50-60/1 273 = 200/50-60/3 453 = 380-415/50/3 463 = 460/60/3 ICE MACHINE SERIES I Indigo U Undercounter K Koolaire R Flake/Nugget B Big shot S S-series IB Ice Beverage C Countertop
CVD CONDENSING UNITS CVDT 1200 3 CONDENSING UNIT MODEL CONDENSING UNIT SERIES REFRIGERANT TYPE F = R404A 3 PHASE T = R410 Ice Cube Sizes Regular 1-1/8" x 1-1/8" x 7/8" 2.86 x 2.86 x 2.22 cm Dice 7/8" x 7/8" x 7/8" 2.22 x 2.22 x 2.22 cm Part Number: 000015431 Rev 02 6/20 Half Dice 3/8" x 1-1/8" x 7/8" 0.95 x 2.86 x 2.
Model/Serial Number Location These numbers are required when requesting information from your local Manitowoc Distributor, service representative, or Manitowoc Ice, Inc. • The model and serial number can be viewed by pressing the information icon on the touchscreen. • The owner warranty registration card. • The model/serial number data plate located in the evaporator compartment and on the back of the ice machine.
Warranty For warranty information visit: www.manitowocice.com/Service/Warranty • Warranty Coverage Information • Warranty Registration • Warranty Verification Warranty coverage begins the day the ice machine is installed. WARRANTY REGISTRATION Completing the warranty registration process is a quick and easy way to protect your investment. Scan the QR code with your smart device or enter the link in a web browser to complete your warranty registration. WWW.MANITOWOCICE.
LuminIce® II The LuminIce® growth inhibitor recirculates the air in the ice machine foodzone over a UV bulb. This process will inhibit the growth of common micro-organisms on all exposed foodzone surfaces. • LuminIce® bulbs require replacement on a yearly basis. • The control board can be set to automatically display a reminder after 12 months. NOTE: LuminIce® and LuminIce® II bulbs are not interchangeable; verify your model before ordering a replacement bulb.
Installation nWarning PERSONAL INJURY POTENTIAL Remove all ice machine panels before lifting. Notice IF1400C/IF1800C/IF2100C ice machines are not approved for use on Manitowoc D570 bins. Notice The ice machine head section must be protected if it will be subjected to temperatures below 32°F (0°C). Failure caused by exposure to freezing temperatures is not covered by the warranty. STACKING TWO ICE MACHINES ON A SINGLE STORAGE BIN Indigo Model ice machines cannot be stacked.
Location of Ice Machine HEAD SECTION The location selected for the ice machine head section must meet the following criteria. If any of these criteria are not met, select another location. • The location must be free of airborne and other contaminants. • The air temperature must be at least 35°F (1.6°C), but must not exceed 110°F (43°C). • Ice Making Water Inlet - Water Pressure must be at least 20 psi (1.4 bar), but must not exceed 80 psi (5.5 bar).
ICE BEVERAGE MODELS • Ice/Beverage Ice Machines require that a proper ice level be maintained when installed on a dispenser. Ice Beverage machines ship with a ice level management sensor pre-installed. • The ice machine head is installed with the electrical inlet, water supply inlet, refrigeration tubing and water drain entering from the back of the ice machine. • The ice machine head section contains a service loop that must remain installed between the ice machine head section and line set.
LOCATION OF CVD CONDENSING UNITS The location selected for the CVD Condensing Unit must meet the following criteria. If any of these criteria are not met, select another location. • The air temperature must be at least -20°F (-28.9°C) but must not exceed 120°F (48.9°C). • The location must not allow exhaust fan heat and/or grease to enter the condenser. • The location must not obstruct airflow through or around the condensing unit. See below for clearance requirements.
Clearance Requirements QuietQube Model Clearance Requirements Model Top Back Sides IF0600C IF0900C IT1200C 5" 5" 5" IF1400C (13 cm) (13 cm) (13 cm) IF1800C IF2100C IBF0620C 2"** 5" 8" ** IBF0820C (5 cm) (13 cm) (20 cm) IBT1020C ** 24" (61 cm) is recommended on top/sides for servicing Condensing Unit Clearance Requirements Model Top/Sides Back Front CVDF0600 CVDF0900 CVDT1200 0" 48" 48" CVDF1400 (0 cm*) (122 cm) (122 cm) CVDF1800 CVDF2100 * 24" (61 cm) is recommended on top/sides for servicing Part Number:
Dual Evaporator Model Installation on a Manitowoc Bin Dual evaporator models will not function correctly with the stock bin deflector. An ice deflector kit is required for installation and is ordered separate. Order appropriate kit (30" or 48") for your bin. The stock bin deflector must be removed and replaced with the correct deflector to prevent injury. nWarning PERSONAL INJURY POTENTIAL Do not operate any ice machine with the deflector removed.
Ice Machine on a Dispenser Installation No deflector is needed for machines that match the size of the dispenser (30" head section on a 30" dispenser) unless required by the dispenser manufacturer. Adapters are required when a smaller ice machine is going on a larger dispenser (22" machine on a 30" dispenser). Ice level management is recommended to prevent water leakage or movement of ice machine during agitation.
Water Supply and Drains Potable Water • Water temperature must be between 40°F (4.4°C) and 90°F (32°C). • Water pressure must be between 20 psi (140 kPa) and 80 psi (550 kPa). • Minimum internal diameter of tubing 3/8" (10 mm). Drain Connections • Drain lines must have a 1.5 inch drop per 5 feet (2.5 cm per meter) of run and must not create traps. • The floor drain must be large enough to accommodate drainage from all drains. • Run separate bin and ice machine drain lines.
Lineset Applications Notice The 60-month compressor warranty (including the 36-month labor replacement warranty) will not apply if the Manitowoc Ice Machine, Condenser or QuietQube® Condensing Unit were not installed according to specifications. This warranty also will not apply if the refrigeration system is modified with a condenser, heat reclaim device, or other parts or assemblies not manufactured by Manitowoc Ice.
QuietQube® Remote Condensing Unit QuietQube® Ice Machine IF0600C IBF0620C IBF0820C IF0900C IBT1020C IT1200C IF1400C Remote Single Circuit Condenser IF1800C CVDF1800 IF2100C CVDF2100 CVDF0600 CVDF0900 CVDT1200 CVDT1200 CVDF1400 Line Set* S Trap RC-21 RC-31 RC-51 K00172 RC-20 RC-30 RC-50 RC-23 RC-33 RC-53 K00166 *Line Set Suction Line Liquid Line RC 21/31/51 5/8 inch (16 mm) 3/8 inch (10 mm) RC 20/30/50 3/4 inch (19 mm) 1/2 inch (13 mm) RC 23/33/53 3/4 inch (19 mm) 5/8 inch (16 mm) 34
Additional Refrigerant Charge For 51' to 100' Line Sets Ice Machine IF0600C IBF0620C IBF0820C IF0900C IBT1020C IT1200C Condenser CVDF0600 CVDF0900 CVDT1200 IF1400C CVDF1400 IF1800C CVDF1800 IF2100C CVDF2100 Part Number: 000015431 Rev 02 6/20 Additional Amount of Refrigerant To Be Added To Nameplate Charge 1.
Calculating Allowable Lineset Distance Line Set Length The maximum length is 100' (30.5 m). Line Set Rise/Drop The maximum rise is 35' (10.7 m). The maximum drop is 15' (4.5 m). S TRAP REQUIRED IF RISE IS HIGHER THAN 20' 35 FT. (10.7 M) MAXIMUM DISTANCE 35 ft. (10.7 m) Rise: The maximum distance the Condenser or Condensing Unit can be above the ice machine. 15 FT. (4.5 M) MAXIMUM DISTANCE 15 ft. (4.5 m) Drop: The maximum distance the Condenser or Condensing Unit can be below the ice machine.
Maintenance Detailed Cleaning and Sanitizing GENERAL You are responsible for maintaining the ice machine in accordance with the instructions in this manual. Maintenance procedures are not covered by the warranty. Descale and sanitize the ice machine every six months for efficient operation. If the ice machine requires more frequent detailing and sanitizing, consult a qualified service company to test the water quality and recommend appropriate water treatment.
DETAILED DESCALING/SANITIZING PROCEDURE This procedure must be performed a minimum of once every six months. • The ice machine and bin must be disassembled descaled and sanitized. • All ice produced during the descaling and sanitizing procedures must be discarded. REMEDIAL CLEANING PROCEDURE • This procedure descales the components in the water flow path, and is used to descale the ice machine between the bi-yearly detailed descaling/sanitizing procedure.
Touchscreen Operation For The Clean Cycle STARTING A CYCLE Pressing the clean button will display a Continue/Abort screen, and a warning that pressing Continue will result in a clean cycle that can last up to 35 minutes. WATER CURTAIN/DAMPER OPERATION DURING THE CLEAN CYCLE The water curtain/damper must remain closed during the clean sequence.
Detailed Descaling/Sanitizing Procedure ,Caution Do not mix Cleaner/Descaler and Sanitizer solutions together. It is a violation of Federal law to use these solutions in a manner inconsistent with their labeling. nWarning Wear rubber gloves and safety goggles (and/or face shield) when handling Ice Machine Cleaner or Sanitizer. Ice machine cleaner/descaler is used to remove lime scale and mineral deposits. Ice machine sanitizer disinfects and removes algae and slime.
Step 1 Open the front door to access the evaporator compartment. Ice must not be on the evaporator during the descaling/sanitize cycle. Follow one of the methods below: • Press the power switch at the end of a harvest cycle after ice falls from the evaporator(s). • Press the power switch and allow the ice to melt. • Use the touchscreen to initiate a manual harvest cycle. Notice Never use anything to force ice from the evaporator. Damage may result. Step 2 Remove all ice from the bin/dispenser.
Step 5 Wait until the cycle is complete, then disconnect power to the ice machine (and dispenser when used). nWarning Disconnect the electric power to the ice machine at the electric service switch box. Step 6 Remove parts for descaling. Please refer to the proper parts removal for your ice machine. Continue with next step when the parts have been removed.
Step 8 Use 1/2 of the descaler/water mixture to clean all components. The solution will foam when it contacts lime scale and mineral deposits; once the foaming stops use a soft-bristle nylon brush, sponge or cloth (NOT a wire brush) to carefully clean the parts. Soak parts for 5 minutes (15 - 20 minutes for heavily scaled parts). Rinse all components with clean water.
Step 12 Replace all removed components. Step 13 Wait 20 minutes. Step 14 Reapply power to the ice machine . Step 15 Press the Clean button and select “Make ice when complete”. Water will flow through the water dump valve and down the drain. Wait approximately 1 minute until the water trough refills and the display indicates Add Chemical. Add the proper amount of ice machine sanitizer to the water trough by pouring between the water curtain and evaporator, then confirm the chemical was added.
PARTS REMOVAL FOR DESCALING/SANITIZING Single Evaporator Ice Machines D A B E C A. Remove the water curtain • Gently flex the curtain in the center and remove it from the right side. • Slide the left pin out. B. Remove the water trough • Depress tabs on right and left side of the water trough. • Allow front of water trough to drop as you pull forward to disengage the rear pins. C. Remove the water level probe • Pull the water level probe straight down to disengage.
D. Remove the ice thickness probe • Compress the hinge pin on the top of the ice thickness probe. • Pivot the ice thickness probe to disengage one pin then the other. The ice thickness probe can be cleaned at this point without complete removal. If complete removal is desired, disconnect the ice thickness control wiring from the control board. E. Remove the water distribution tube NOTE: Distribution tube thumbscrews are retained to prevent loss.
Ice Beverage Ice Machines B D A E C A. Remove splash shield • Grasp the top center of splash shields. • Lift up and then out. B. Remove ice thickness probe • Compress the hinge pin on the top of the ice thickness probe. • Pivot the ice thickness probe to disengage one pin then the other. The ice thickness probe can be cleaned at this point without complete removal. If complete removal is desired, disconnect the ice thickness control wiring from the control board.
C. Remove the water trough • Depress tabs on right and left side of the water trough. • Allow front of water trough to drop as you pull forward to disengage the rear pins. D. Remove the water level probe • Pull the water level probe straight down to disengage. • Lower the water level probe until the wiring connector is visible. • Disconnect the wire lead from the water level probe. • Remove the water level probe from the ice machine. E.
Dual Evaporator Ice Machines A B C D E F A. Remove front splash shield • Grasp the top of the splash shield. • Lift up and then out. B. Remove evaporator splash shields • Grasp the top center of splash shields. • Lift up and then out. C. Remove the water trough shield • Grasp the water trough shield in the center and the left end. • Flex the water trough shield in the center and pull the left end forward until clear of the side wall. Repeat for the right end.
D. Remove ice thickness probe • Compress the hinge pin on the top of the ice thickness probe. • Pivot the ice thickness probe to disengage one pin then the other. The ice thickness probe can be cleaned at this point without complete removal. If complete removal is desired, disconnect the ice thickness control wiring from the control board. E. Remove ice dampers • Grasp ice damper and apply pressure toward the back mounting bracket. • Apply pressure to the front mounting bracket with thumb.
G. Remove distribution tubes • Distribution tubes thumbscrews are retained to prevent loss. Loosen thumbscrews but do not pull thumbscrews out of distribution tube. • Loosen the two outer screws and pull forward on the distribution tube to release from slip joint. • Disassemble distribution tube by loosening the two (2) middle thumbscrews and dividing the distribution tube into two pieces. H. Remove the water trough • Depress the two tabs on the top of the water trough.
Ice Thickness Probe & Water Level Probe Clean the probes using the following procedure. NOTE: Do not soak electrical connectors in cleaner or sanitizer solution. 1. Mix a solution of Manitowoc ice machine cleaner/ descaler and water (2 ounces of cleaner/descaler to 16 ounces of water) in a container. 2. Soak probes in container of descaler/water solution while disassembling and cleaning water circuit components (soak probes for 10 minutes or longer). 3.
Water Inlet Valve The water inlet valve normally does not require removal for cleaning. Refer to ”Water System Checklist” on page 103, if you are troubleshooting water related problems. 1. When the ice machine is off, the water inlet valve must completely stop water flow into the machine. Watch for water flow. When the ice machine is on, the water inlet valve must allow the proper water flow through it. Press the Power button to energize the ice machine. Watch for water flow into the ice machine.
Remedial Cleaning Procedure This procedure will descale the components in the water flow path, and is used to descale the ice machine between the bi-yearly detailed cleaning and sanitizing procedure. Ice machine cleaner/descaler is used to remove lime scale and mineral deposits. Ice machine sanitizer disinfects and removes algae and slime. NOTE: Although not required and dependent on your installation, removing the ice machine top cover may allow easier access. 1.
Model IF0600C/IBF0620C/IBF0820C IF0900C/IBT1020C/IT1200C IF1400C/IF1800C/IF2100C Amount of Cleaner/Descaler 5 ounces (150 ml) 9 ounces (265 ml) 4. Close and secure the front door. The ice machine will automatically start ice making after the descale cycle is complete (approximately 24 minutes). NOTE: Once the cycle has started it must complete before the ice machine can make ice again.
Removal from Service/Winterization General Special precautions must be taken if the ice machine is to be removed from service for an extended period of time or exposed to ambient temperatures of 32°F (0°C) or below. Notice If water is allowed to remain in the ice machine in freezing temperatures, severe damage to some components could result. Damage of this nature is not covered by the warranty. 1. Turn off the ice machine by pressing the On/Off Button. 2. Turn off the water supply. 3.
Operation Operational Checks GENERAL Manitowoc ice machines are factory-operated and adjusted before shipment. Normally, new installations do not require any adjustment. To ensure proper operation, always follow the Operational Checks: • when starting the ice machine for the first time • after a prolonged out of service period • after cleaning and sanitizing NOTE: Routine adjustments and maintenance procedures are not covered by the warranty.
ICE THICKNESS CHECK The ice thickness probe is factory-set to maintain the ice bridge thickness at 1/8 in. (3 mm). NOTE: Make sure the water curtain/splash shields are in place when performing this check. It prevents water from splashing out of the water trough. Remove the curtain to make an adjustment, then replace immediately after the adjustment is made. 1. Inspect the bridge connecting the cubes. It should be about 1/8 in. (3 mm) thick. 2.
Control Board Timers The control board has the following non-adjustable timers: • The ice machine is locked into the freeze cycle for 6 minutes before a harvest cycle can be initiated. This can be overridden by initiating a manual harvest. Refer to “Manual Harvest” on page 75. • The maximum freeze time is 35 minutes at which time the control board automatically initiates a harvest sequence.
Sequence of Operation QUIETQUBE® MODELS NOTE: The power button must be depressed and the water curtain/ice dampers must be in place on the evaporator before the ice machine will start. INITIAL START-UP OR START-UP AFTER AUTOMATIC SHUT-OFF 1. Water Purge Before the compressor starts, the water pump and water dump solenoid are energized to purge the ice machine of old water. This feature ensures that the ice making cycle starts with fresh water. 2.
FREEZE SEQUENCE 3. Prechill The compressor lowers the temperature of the evaporator(s) before the water pump is energized. The water fill valve will energize and remain on until water completes the water level probe circuit. 4. Freeze The water pump energizes and water flows over the evaporator. After water contacts the water level probe the water fill valve de-energizes. The control board will automatically cycle the water fill valve.
Water Inlet Valve The water inlet valve energized in prechill. After water contacts the low and high water probes the water fill valve de-energizes. Ice builds on the evaporator and the water level drops. When water loses contact with the high water probe, the water fill valve energizes until water contacts the high water probe again. Maximum Fill Time = Prechill fill time + first fill + second fill.
HARVEST SEQUENCE 5. Water Purge The air pump(s) and the harvest valve(s) open at the beginning of the water purge to divert refrigerant gas into the evaporator. The water pump continues to run, and the water dump valve energizes to purge the water in the water trough. CVD Condensing Unit: When the refrigerant pressure is low enough to open the fan cycling pressure control the condenser fan motor stops. 6. Harvest The air pump(s) remain energized and the harvest valve(s) remains open.
AUTOMATIC SHUT-OFF 7. Automatic Shut-Off Ice Machine Section: Shuts off when: • The storage bin is full at the end of a harvest sequence. • The sheet of cubes fails to clear the water curtain and holds it open. • One or both ice dampers are held down. • Bin level probe thermistor senses setpoint (when used). After the water curtain or ice damper are held open for 30 seconds, the ice machine shuts off.
Part Number: 000015431 Rev 02 6/20 65 Off Off Compressor Start On Water Pump Pressure Equalization 2. Refrigeration System Start-up 1.
Part Number: 000015431 Rev 02 6/20 5. Water Purge Harvest Sequence 3. Pre chill 4.
Part Number: 000015431 Rev 02 6/20 67 Off Off ** Off Water Pump Off On On Harvest Valve(s) Off On On Air Pumps Off On Off Water Inlet Valve Off Off** Off Water Dump Valve Off On On Liquid Line Solenoid Valve Off On On Contactor Refrigeration Compressor & Condenser Fan Motor* Until 10 min.
THIS PAGE INTENTIONALLY LEFT BLANK 68 Part Number: 000015431 Rev 02 6/20
Menu Navigation Power Button Touchscreen Lock 11/18/2018 10:42 AM 3 3 Clean Button S MAKING ICE i Touch Screen Features The Indigo® control panel offers a series of pressuresensitive buttons and an interactive touchscreen. Buttons Power Button: Provides On/Off functions for the ice machine. Lock/Unlock Button: Allows or prevents touchscreen navigation. Cleaning Button: Initiates a cleaning cycle.
Touchscreen 11/18/2018 10:42 AM 3 3 S MAKING ICE i 11/18/2018 10:42 AM 3 S Program Mode On 3 Home screen allows viewing of ice machine status, alerts and messages. Navigation with the touchscreen provides access to menu items,machine information, settings and event logs. Setup and Energy Saver settings can be adjusted along with access to service and troubleshooting information. The icons provide status indication and allow navigation by pressing the icon.
HOME SCREEN ICON DESCRIPTIONS Icon Description Home Screen Pressing this icon at any time will return the display to the home screen. State of ice Machine is the center portion of the screen which displays the current condition of the ice machine - Making ice, bin full, program mode or machine off Alert Alert icon with number of messages. Pressing icon will display the alert log which will 3 this allow viewing and resetting of alerts Message 3 Menu Information i Message icon with umber of messages.
Icon iAuCS Description This icon appears when the iAUCS activates during a programed cleaning cycle. Making Ice This icon with a green ring appears after the ice machine has been programmed to run either by time, weight or night off. Machine Off This icon with an orange ring appears after the ice machine has been turned off by either time, weight or night off program. Ice Now This icon with a light blue/dark blue ring allows immediate ice production regardless of ice program settings.
Setup Wizard Screens will automatically advance after a selection is made or press the arrows to advance/go back one screen. All settings can be accessed and changed without the wizard by using menu screen navigation. Setup Press ON/OFF Button Select Language Description On/Off button is used to start/stop ice making. Default is English. Scroll to select a different language. Setup wizard will guide ice machine Start Wizard programming. Date and Time Select Month/Day/Year or Day/Month/Year.
Menu Navigation Overview SETTINGS MENU SCREEN NAVIGATION Select SETTINGS Icon from the Home Screen to access Main Menu screen. The main menu screen contains four main headings, which allow access to subheadings under each main heading.
Service Data Real Time Data Time and Temperature Inputs Outputs Data History for 5 Previous Days Minimum and Maximum Freeze (Length, Time of day, Thermistor Temperatures) Minimum and Maximum Harvest (Length, Time of day, Thermistor Temperatures) Lifetime Data History Installation Date Control Board Replacement Date Control Board Manufacture Date Runtime Cycle Count Potable Water Clean Cycles Alert Log Lists/Clears Alerts Manual Harvest Off or On Control Board Replacement Manual Replacement Manually enter m
Service Diagnostics Control board Enable All Relays Self Check Temperature Sensors Lists Sensor Temperatures Inputs Lists Control Board Input Information User Interface Screen Calibration Button Diagnostics Screen Diagnostics Screen Calibration Contact information Factory defaults to QR code and website address to Manitowoc Ice’s Global Locator. Edit Contact Information Button. USB Upgrade Firmware Export Data iAuCS Manually initiate the iAuCS pump for pump/hose priming.
Settings Language Select Language Reminders Clean Reminder Set Month Interval Air Filter Set On/Off/Interval Water Filter Set Reminder Configure Date & Time Configure Date & Time Set Time Set Date Units Standard or Metric Brightness Adjust Touch Screen Brightness For Sleep Mode or Inactivity. NOTE: 100% brightness is activated by touching the screen when the lock feature is off.
Reset Defaults Require Setup Wizard Optional Setup Wizard restart for training purposes or resale of equipment.
USB FLASH DRIVE SPECIFICATIONS AND FORMATTING Updating firmware on Indigo™ model ice machines requires a properly formatted 32 GB or smaller USB flash drive. All USB flash drives must be formatted before use to remove any software programs or files currently on the flash drive. USB Flash Drive Specifications: • USB 2 Version • 32 GB or less capacity • Fat32 File System USB Flash Drive Formatting: Procedure to format a USB flash drive varies with operating system software.
EXPORTING DATA TO A FLASH DRIVE Data can be copied from the control board memory to a flash drive and used to transfer setup and/or cycle data to a replacement control board or to transfer setup information to multiple ice machines. Data may also be requested by service department personnel for analysis or as an aid to troubleshooting. The data files are small and can be attached to an email. Important The flash drive must be formatted before using.
Troubleshooting Troubleshooting Check the touchscreen for alerts - An alert icon with the number of messages will be displayed if alerts are present. Pressing the alert icon will display the alert log which will allow viewing and resetting of alerts. Refer to the alert log and event log on the following pages for a description of the event.
EVENT LOG Refer to Event Log Detail For Code descriptions.
Displayed Text Checksum WatchDog UI Comm Code Description E36 Check Sum Error E37 Watch Dog Event E38 UI Comm Event EVENT LOG DETAIL E01 Long Freeze 3 consecutive 35 minute freeze cycles = Ice machine is off. E02 Long Harvest 3 consecutive 7minute harvest cycles = Ice machine is off. E03 Power Loss When power is interrupted to the ice machine the control board will log the event in the ELOG and stamp the loss of power on power-up.
E09 Flooding Evaporator Fault Single Evaporator, Single Circuit Average compressor discharge line temperature during the first 6 minutes of the freeze cycle (T2) compared to the average of the Prechill (T1) +50°F is less than 1.05°F. E10 Flooding Evaporator Fault Dual TXV, Dual Circuit Average compressor discharge line temperature during the first 6 minutes of the freeze cycle (T2) compared to the average of the Prechill (T1) +50°F is less than 1.05°F.
E19 Ice Thickness Probe Fault The monitored Frequencies is out of the appropriate range (Probe unplugged or problem with microphone). E20 Water System Fault Any of the following: 1. Sensing high water probe and not low water probe. 2. Evaporator outlet temperature is less than -10°F 6.5 to 7.5 minutes in freeze cycle. 3. Low water probe is satisfied at the end of harvest. 4. Low or high water probe is satisfied at end of freeze cycle.
E26 T6 or T7 Temperature Issue The thermistor had an average value reading outside of the valid range. E27 T6 or T7 Temperature Issue The thermistor had an average value reading outside of the valid range. E28 AuCS When the AUCS clean option is selected from the menu, the control checks for the presence of the AUCS board. When the AUCS is not connected it will signal an Event which will clear as soon as the hardware is detected.
E36 Check Sum Error Event Log Only: Activates on power loss. E37 Watch Dog Event Event Log Only: Micro Process time out, possible electrical noise. E38 UI Comm Event Event Log Only: User interface communication error: loose communication cable, power interruption.
THAW CYCLE When the damper/curtain does not open during the 7 minute harvest cycle the following ice thaw cycle occurs: • The compressor, harvest solenoid valve and dump valve de-energize. The water pump remains energized and the water inlet valve energizes until water touches the high water level probe. • Water is circulated, dumped and refilled to the high water level probe for 3 minutes.
SAFE OPERATION MODE Allows the ice machine to operate up to 72 hours if the ice thickness probe (E19 fault) and/or water level probe sensors fail (E20 fault). • When the control board starts the safe mode an alert is flashed on the LCD display to notify the end-user they have a production problem. • The control board automatically initiates and monitors the safe mode. The control will automatically exit the safe mode if a normal signal is received from the input.
E01 LONG FREEZE CYCLE If the freeze time reaches 35 minutes, the control board automatically initiates a harvest cycle. If 3 consecutive 35-minute freeze cycles occur, the ice machine stops. E02 LONG HARVEST CYCLE If the harvest time reaches 7 minutes, the control board will start a thaw cycle and automatically return the ice machine to the freeze cycle. After 3 consecutive long harvest cycles the ice machine stops.
E01 LONG FREEZE Improper Installation • Refer to “Installation/Visual Inspection Checklist” on page 103 Water System • Defective water level probe • Low water pressure (20 psig min.) • High water pressure (80 psig max.) • High water temperature (90°F/32.2°C max.
Miscellaneous • Non-Manitowoc components • Improper refrigerant charge • Defective head pressure control • Defective harvest valve • Defective compressor • TXV starving or flooding (check bulb mounting) • Non-condensible in refrigeration system • Plugged or restricted high side refrigerant lines or component • Restricted air flow/dirty condenser fins • High inlet air temperature • Condenser discharge air recirculation 92 Part Number: 000015431 Rev 02 6/20
E02 LONG HARVEST Harvest time exceeds 7 minutes for 3 consecutive harvest cycles.
Troubleshooting By Symptom The troubleshooting procedures follow flow charts. There are four symptoms, the symptom that you are experiencing will determine which flow chart to use. The flow chart asks yes and no questions to determine the problem. The flow chart will direct you to a procedure to correct the problem. QuietQube® remote condensing units use separate charts.
RESET TO FACTORY DEFAULTS Before starting troubleshooting procedures, reset the control board to factory defaults to prevent mis-diagnosis. Before resetting to factory defaults do one of the following: A. Copy settings to a usb device and flash settings into the control board when diagnostics are complete. B. Write down any customer settings so they can be re-entered when diagnostics are complete.
Part Number: 000015431 Rev 02 6/20 No Are there any lights on or flashing on the control board? No START Is the display interface energized and functioning? No No No Yes Display light Flashing? Yes No Is there an Alert or Error Logged? Yes Yes Cycle Power to Board, are lights flashing? Micro light flashing? Does the ice machine start when the Power button is pushed? Refer to display & control board diagnostics Yes Yes SYMPTOM #1 ICE MACHINE WILL NOT RUN No Yes Refer to display & c
Part Number: 000015431 Rev 02 6/20 97 Yes Refer to display & control board diagnostics Control board fuse is good? Yes Replace fuse & determine which component caused fuse to blow No Supply power to the ice machine No Line voltage at wires 55 & 56 on 9 pin control board connector? Yes Yes Bin switch light on? (Multi evap all lights on?) Yes No Yes All water curtains or dampers in place? No Install the water curtain/damper
Part Number: 000015431 Rev 02 6/20 Refer to display & control board diagnostics No Which Event? Yes Test run ice machine Yes Ice machine starts? No Press power button to start ice making, E01 or E02 In Event Log? Yes E02 E01 No Refer to bin switch diagnostics. Replace the water curtain/damper. Refer to E02 Long Harvst Cycle Refer to E01 Long Freeze Cycle Yes Is magnet on the water curtain/damper.
DIAGNOSING A CONDENSING UNIT THAT WILL NOT RUN If the ice machine water pump is not energized, refer to “Diagnosing an Ice Machine that Will Not Run.” 1. Verify primary voltage is supplied to the ice machine condensing unit and the fuse/circuit breaker is closed. 2. Verify the high-pressure control is closed. 3. Verify the low-pressure control is closed. 4. Verify voltage is present at terminals 1 & 2 on the compressor time delay relay. 5.
SYMPTOM #2 LOW PRODUCTION, LONG FREEZE CYCLE Ice Machine has a Long Freeze Cycle Ice Formation is Thick or Thin ice fill at Inlet or Outlet of Evaporator or Low Production Information must be verified to eliminate non-refrigeration problems which can cause good refrigeration components to appear defective. Before starting, see “Before Beginning Service” on page 100 for a few questions to ask when talking to the ice machine owner.
Ice Production Check The amount of ice a machine produces directly relates to the operating water and air temperatures. This means a condensing unit with a 70°F (21°C) outdoor ambient temperature and 50°F (10°C) water produces more ice than the same model condensing unit with a 90°F (32°C) outdoor ambient temperature and 70°F (21°C) water. 1. Determine the ice machine operating conditions: Air temp entering condenser: ____° Air temp around ice machine: ____° Water temp entering sump trough: ____° 2.
Weighing the ice is the only 100% accurate check. However, if the ice pattern is normal and the 1/8 in. thickness is maintained, the ice slab weights listed with the 24-Hour Ice Production Charts may be used. 4. Compare the results of step 3 with step 2. Ice production checks that are within 10% of the chart are considered normal. If they match closely, determine if: • Another ice machine is required. • More storage capacity is required.
Installation/Visual Inspection Checklist Inadequate Clearances • Check all clearances on sides, back and top.
Water System Checklist A water-related problem often causes the same symptoms as a refrigeration system component malfunction. Water system problems must be identified and eliminated prior to replacing refrigeration components. Water area (evaporator) is dirty • Clean as needed Water inlet pressure not between 20 and 80 psig (1-5 Bar, 138-552 kPa).
Ice Formation Pattern Evaporator ice formation pattern analysis is helpful in ice machine diagnostics. Analyzing the ice formation pattern alone cannot diagnose an ice machine malfunction. However, when this analysis is used along with Manitowoc’s Freeze Cycle Refrigeration System Operational Analysis Tables, it can help diagnose an ice machine malfunction. Any number of problems can cause improper ice formation.
2. Extremely Thin at Evaporator Outlet There is no ice, or a considerable lack of ice formation, at the outlet of the evaporator. Examples: No ice at all on the outlet half of the evaporator, but ice forms on the inlet half of the evaporator. Or, the ice at the outlet of the evaporator reaches 1/8 in. to initiate a harvest, but the inlet of the evaporator already has 1/2 in. to 1 in. of ice formation. 3.
One Evaporator, Two TXV Models Tubing routing for one evaporator with two TXV’s is different. The evaporator has two inlets and outlets. Fill pattern varies depending on which circuit is affected. Extremely Thin at the Evaporator Outlet will first be visible either 1/4 or 3/4 of the way down the evaporator. Extremely Thin at the Evaporator Inlet will show at the bottom of the evaporator or 1/2 of the way down depending on the circuit affected.
Analyzing Discharge Pressure in the Freeze Cycle 1. Determine the ice machine operating conditions: Air temp. entering condenser ______ Air temp. around ice machine ______ Water temp. entering sump trough ______ 2. Refer to “Cycle Times/24-Hour Ice Production/ Refrigerant Pressure Charts” on page 183 for ice machine being checked. Use the operating conditions determined in step 1 to find the published normal discharge pressures. Freeze Cycle ______ Harvest Cycle ______ 3.
FREEZE CYCLE DISCHARGE PRESSURE HIGH CHECKLIST Improper Installation • Refer to “Installation/Visual Inspection Checklist” on page 103 Air Condenser • Dirty condenser filter • Dirty condenser fins • High inlet air temperature • Condenser discharge air recirculation • Defective “Fan Cycle Control” on page 157) • Defective fan motor • Defective head pressure control valve (Remote) Other • Overcharged • Non-condensible (air) in system • Wrong type of refrigerant • Non-Manitowoc components in s
FREEZE CYCLE DISCHARGE PRESSURE LOW CHECKLIST Improper Installation • Refer to “Installation/Visual Inspection Checklist” on page 103 Condenser • Defective head pressure control valve, won’t bypass page 162 • Defective fan cycle control, stuck closed (page 157) Other • Undercharged • Wrong type of refrigerant • Non-Manitowoc components in system • Liquid line/component restricted 110 Part Number: 000015431 Rev 02 6/20
Analyzing Suction Pressure The suction pressure gradually drops throughout the freeze cycle. The actual suction pressure (and drop rate) changes as the air and water temperature entering the ice machine changes. These variables also determine the freeze cycle times. To analyze and identify the proper suction pressure drop throughout the freeze cycle, compare the published suction pressure to the published freeze cycle time. NOTE: Analyze discharge pressure before analyzing suction pressure.
SUCTION PRESSURE HIGH CHECKLIST Improper Installation • Refer to “Installation/Visual Inspection Checklist” on page 103 Discharge Pressure • Discharge pressure is too high and is affecting suction pressure – refer to ”Analyzing Discharge Pressure in the Freeze Cycle” on page 108 Improper Refrigerant Charge • Overcharged • Wrong type of refrigerant • Non condensible in system Components • Harvest valve leaking • TXV flooding • Defective compressor Other • Non-Manitowoc components in system 112 Part
SUCTION PRESSURE LOW CHECKLIST Improper Installation • Refer to ”Installation/Visual Inspection Checklist” on page 103 Discharge Pressure • Discharge pressure is too low and is affecting low side – refer to “Analyzing Discharge Pressure in the Freeze Cycle” on page 108 Improper Refrigerant Charge • Undercharged • Wrong type of refrigerant Other • Non-Manitowoc components in system • Improper water supply over evaporator – refer to “Water System Checklist” on page 104 • Restricted/plugged liquid line dr
Harvest Valve Analysis Symptoms of a harvest valve remaining partially open during the freeze cycle can be similar to symptoms of either an expansion valve or compressor problem. Use the following procedures to determine if a harvest valve is remaining partially open during the freeze cycle. QUIETQUBE® HARVEST VALVE ANALYSIS The valve can fail in two positions: • Valve will not open in the Harvest cycle. • Valve remains open during the Freeze cycle.
Analyzing Freeze Cycle Suction Line Temperature Suction line temperature alone cannot diagnose an ice machine. However, comparing this temperature during the freeze cycle can help diagnose an ice machine malfunction. The actual temperature of the suction line varies by model, and will change throughout the freeze cycle. This makes documenting the “normal” suction line temperature difficult.
SYMPTOM #3 HARVEST PROBLEMS Normal Ice Cube Melted Out Ice Cube Definition of a harvest problem; At the end of a 7 minute harvest cycle the slab(s) of ice is still contacting the evaporator. The slab of ice may or may not be removable by hand. Harvest problems can be split into two categorizes. • Melted sheet of cubes at the end of the harvest cycle. Ice can be removed rather easily by hand. The back of the cubes are misshapen and melted.
Diagnosing Harvest Issues Follow these steps in order and refer to specific procedures referenced to troubleshoot and diagnose problems. 1. Record the model and serial number of the ice machine and condenser and verify the head section and condensing unit match. 2. Verify the ice formation is normal see page 105 and the bridge thickness is 1/8” at the beginning of the harvest cycle see “Ice Thickness Check” on page 58. 3. Verify power is present at the harvest valve(s) throughout the entire harvest cycle.
5. If the cubes are not melted, confirm the line set outside diameter is correct (see page 33 )the lineset is installed correctly (see page 36) and no kinks exist in the tubing. 6. Record and verify ambient temperature is within guidelines: 118 A. Air temperature entering condenser page 28 B.
7. Refer to chart and record refrigeration operating data. Freeze Data* HP¹ LP² LLT³ HP¹ LP² LLT³ 1 minute after water starts flowing over the evaporator Middle of the freeze cycle End of the freeze cycle Harvest Data* 30 seconds into harvest 2.
FAILURE TYPE AND SYMPTOMS: Refrigerant overcharge page 162 Measured in the freeze cycle a. Head pressure is above or on the high end of the published numbers b. Sub cooling will be greater than 25°F. Head Pressure Control Valve failure in the freeze cycle page 163 Measured in the freeze cycle a. Head pressure is floating up and down b. Liquid line temperature floats up and down Fan cycle control turns condenser fan motor on/off - This symptom will not be observed at temperatures above 70°F.
Harvest valve failure Measured in the harvest cycle a. High pressure will be higher b. Low pressure will be lower than published. Fan cycling control failure page 157 Measured in the harvest cycle a. Condenser fan motor does not cycle off when pressure is below fan cycle control cut out setting . Accumulator failure page 168 Measured in the freeze cycle • The suction line temperature between the accumulator and compressor does not increase 20+°F within 6 minutes of a freeze cycle .
Part Number: 000015431 Rev 02 6/20 Note: All pressure readings are taken from the Liquid & Suction Shut-off Valves or access ports at the ice machine head section.
Part Number: 000015431 Rev 02 6/20 123 Cold Feel temperature of Receiver after 30 seconds into harvest cycle YES Is Head Pressure low & Suction Pressure low in harvest? NO YES Feels Warm to Hot No; Harvest PSI Normal Is Head Pressure high & Suction Pressure low in harvest? YES Replace Harvest Valve Not a refrigeration problem, Clean & Inspect Evaporator YES
Part Number: 000015431 Rev 02 6/20 NO Does the Condenser Fan Motor run below cut-out setpoint in harvest? Cold Feel temperature of Liquid Line at Condensing Unit Cold Feel temperature of Liquid Line at rear of Head Section Cold YES Feels Hot Feels Hot Refer to Fan Cycling Control Diagnostics Look for Restriction, Correct Line Set Size, & Proper Insulation Backseat Liquid Line Shut Off Valve or Replace
Part Number: 000015431 Rev 02 6/20 125 Refer to Symptom #2 Refrigeration Operational Analysis Table Head Pressure Valve is in 100% Bypass Feel Temperature of Discharge Line after 30 Seconds into Harvest Cycle (refer to Head Pressure Valve Diagnostics) NO Evacuate System, Recharge & Perform Production Check Change Head Pressure Contol Valve Refrigerant Charge is Correct IMPORTANT Weigh charge as you are recovering, if incorrect evacuate & recharge, if correct then proceed Refrigerant Charge is Inco
Part Number: 000015431 Rev 02 6/20 NO Ice remains frozen to the evaporator at the end of the harvest cycle? NO START Back of cubes are melted at end of harvest cycle? Refer To Symptom #2 Freeze Cycle Operaon Analysis Table YES YES NO Is water flow over the evaporator in the harvest cycle? YES Is Ice Machine level? YES NO Refer to Dump Valve Diagnoscs Level Ice Machine SYMPTOM #4 ICE MACHINE WILL NOT HARVEST - FREEZE CYCLE IS NORMAL AND ICE CUBES ARE MELTED AFTER HARVEST
Part Number: 000015431 Rev 02 6/20 127 Refer to Hard Cleaning Procedure YES Refer to Freeze Cycle Analysis Chart NO >150F/65C Discharge line temperature is normal at the end of the freeze cycle? NO Is the evaporator dirty or damaged? (Dry evaporator first then check) Dents, loose partitions or plating issues NO YES Refer to Hard Cleaning Procedure Are ice thickness, cycle times and slab weights correct?
THIS PAGE INTENTIONALLY LEFT BLANK 128 Part Number: 000015431 Rev 02 6/20
Component Check Procedures CONTROL BOARD, DISPLAY AND TOUCHSCREEN FUNCTION The control board, display and touch screen provide user input and control the ice machine sequence of operation. NOTE: Anytime power is supplied to wires #55 & #56 on the control board, the “Display” and “Micro” lights will flash on and off randomly. The two green lights are located on the top corner of the control board. Display Diagnostics Symptom - Micro light flashes and display light is off. 1.
Control Board Diagnostics 1. Micro light is not flashing. 2. Disconnect line voltage power supply to the ice machine and wait a minimum of 15 seconds, then reapply power. A. Micro light flashes - continue with step 3. B. Micro light is off - Test fuse for continuity. If fuse tests good replace control board. 3. Perform a control board self-test. • Menu / Service / Diagnostics / Control Board / Self Check The control board performs a self test.
Touchscreen Diagnostics Verify touchscreen is unlocked prior to performing diagnostics. 1. Navigate to User Interface on the display and perform the on-screen instructions. • Menu / Service / Diagnostics / User Interface. NOTE: During screen calibration it is important to touch and hold down the cross hairs for three seconds at a time. 2. The calibration will either pass or fail. If the touchscreen fails calibration and will not function correctly in other menu functions replace the touchscreen module.
CONTROL BOARD RELAY TEST The control board can be set to energize all relays for 3.5 minutes. This allows testing to verify control board relays are closed and line voltage is available for ice machine components - Water pump, dump valve, water inlet valve, harvest valve(s), air compressor(s), contactor/compressor/ fan motor - The fan cycle control must close to energize the fan motor. 1. Press On/Off button to turn off ice machine and navigate in menu to enable all relays.
PROGRAMMING A REPLACEMENT CONTROL BOARD Indigo NXT replacement control boards require the model number to be entered to activate the appropriate look up tables for operation and diagnostic. This can be done two different ways, USB Setup or Manual Setup. USB Setup - Applicable when the control board is operational and has a mechanical issue such as a sticking relay. The asset data is transferred to the replacement control board from the faulty control board.
USB FLASH DRIVE SPECIFICATIONS AND FORMATTING Updating firmware on Indigo NXT model ice machines requires a properly formatted 32 GB or smaller USB flash drive. All USB flash drives must be formatted before use to remove any software programs or files currently on the flash drive. USB Flash Drive Specifications: • USB 2 Version • 32 GB or less capacity • Fat32 File System USB Flash Drive Formatting: Procedure to format a USB flash drive varies with operating system software.
EXPORTING DATA TO A FLASH DRIVE Data can be copied from the control board memory to a flash drive and used to transfer setup and/or cycle data to a replacement control board or to transfer setup information to multiple ice machines. Data may also be requested by service department personnel for analysis or as an aid to troubleshooting. The data files are small and can be attached to an email. Important The flash drive must be formatted before using.
UPGRADING FIRMWARE WITH A FLASH DRIVE Important The flash drive must be formatted before using. All files and software on the flash drive are removed during the formatting process. 1. Drag and drop the files from website or email onto a flash drive, insuring they are not in a folder. 2. Ensure that the ice machine’s power is on. 3. Navigate to USB - Menu / Service / USB. 4. Insert the flash drive into the USB port on the ice machine control board. Do not remove flash drive until update is complete).
MAIN FUSE FUNCTION The control board fuse stops ice machine operation if electrical components fail, causing high amp draw. SPECIFICATIONS The main fuse is 250 Volt, 6.3 amp. nWarning High (line) voltage is applied to the control board (terminals #55 and #56) at all times. Removing the control board fuse or pressing the On/Off button will not remove the power supplied to the control board. CHECK PROCEDURE 1. If control board lights are energized the fuse is good.
BIN SWITCH FUNCTION Movement of the water curtain/ice dampers control bin switch operation. The bin switch has two main functions: 1. Terminating the Harvest cycle and returning the ice machine to the Freeze cycle. This occurs when the bin switch is opened and closed again within 30 seconds during the Harvest cycle. 2. Automatic ice machine shut-off. If the storage bin is full at the end of a Harvest cycle, the sheet of cubes fails to clear the water curtain/ice dampers and holds it open.
Diagnostics SYMPTOMS Bin Switch Fails Open • The ice machine will not start an ice making cycle and the display indicates “Full Bin”. • The ice machine displays “Full Bin Remove Ice” in the clean cycle. Bin Switch Fails Closed • When running a “Long Harvest” alert is displayed and E02 Long Harvest indicated. • May be off on a E02 Long Harvest. • The harvest cycle continues after ice opens and closes the ice damper (harvest cycle is 7 minutes).
DIAGNOSTICS 1. Verify bin switch, curtain/damper and curtain/damper magnet are in place and navigate to inputs. • Menu/Service/Diagnostics/Inputs 2. Open and close the ice damper(s) repeatedly while observing the display and control board lights. A. Curtain switch cycles open/closed - The display indicates open/closed and the control board light energizes/de-energizes - Bin switch is operating normally B.
WATER LEVEL CONTROL CIRCUITRY FUNCTION The water level probe controls the water level by sensing whether water is or is not contacting the water level probe. The water level probe has three sensing probes. Two probes are equal in length and are used to measure conductivity for diagnostics. Factory default settings measure resistance from both long probes to the short probe. SPECIFICATIONS Freeze Cycle Water Level Setting The water level is not adjustable.
PRECHILL & FREEZE CYCLE OPERATION The water inlet valve energizes and de-energizes in conjunction with the water level probe located in the water trough. • The water inlet valve is ON when there is no water in contact with the water level probes. • The water inlet valve turns OFF after water contacts the water level probes for 6 continuous seconds. • The water inlet valve can cycle ON and OFF once in the prechill and up to two times in the freeze cycle.
Diagnostics Important The following occurs when the reverse osmosis (R.O.) option has been enabled and then disabled (i.e. placed back into factory default) and the jumper has not been reset to the 45 second factory default position. A. The higher water level probe sensitivity will remain active see “Reverse Osmosis or Deionized Water Usage” on page 148. B. The control board will generate Water-Level probe faults on every cycle. C. The control board initiates a “Safe-Mode” every other cycle.
3. Disconnect the water level probe wiring harness from the control board and ohm harness and water level probe. Normal readings will show no resistance. White Black Red Short Probe Ohm water Level Probe and Wiring Harness WATER LEVEL PROBE CIRCUIT CHECK AT CONTROL BOARD Wait until prechill cycle starts, then jumper water level probe connections (Red/Black) on the control board. 144 A. Sensing displays and the water stops. Repair wire or replace water level probe. B.
ICE THICKNESS PROBE (INITIATES HARVEST) FUNCTION The ice thickness probe senses ice on the evaporator and signals the control board to start a harvest cycle. SPECIFICATIONS Freeze Time Lock-In Feature The ice machine control system incorporates a 6 minute freeze time lock-in feature. This prevents the ice machine from short cycling in and out of harvest. Maximum Freeze Time The maximum freeze time is 35 minutes at which time the control board automatically initiates a harvest sequence.
Ice Thickness Check The ice thickness probe is factory-set to maintain the ice bridge thickness at 1/8 in. (3 mm). NOTE: Make sure the water curtain/splash shields are in place when performing this check. It prevents water from splashing out of the water trough. Remove the curtain to make an adjustment, then replace immediately after the adjustment is made. Make adjustment only when the ice machine is off to prevent initiating a harvest 1. Inspect the bridge connecting the cubes. It should be about 1/8 in.
Ice Thickness Probe Diagnostics 1. Perform Control Board Self Check and insure the internal ITP circuit passes before proceeding. (Menu/Service/Diagnostics/Control Board/Self Check) • Ice Thickness Circuit: Pass = Continue with step #2. • Ice Thickness Circuit: Fail = Change control board. 2. Remove all ice from the evaporator when present, by initiating a manual harvest in the service menu. 3. Press the power button and turn off the ice machine. 4.
The initial numbers displayed are constantly changing and are less than 3000. With an initial reading of less than 300 and a tap test reading of 3300 or higher indicates a good ice thickness probe and control board. The initial numbers displayed do not change or initial numbers did not increase by 3000 during tap test. • Verify the ice thickness probe connector is properly plugged into the board and the ice thickness probe wiring is correct. If the wiring is incorrect replace the ice thickness probe.
BIN LEVEL PROBE The bin level probe accessory will place the ice machine in a full bin state when ice lowers the temperature to 36° F or less. The touchscreen will display Program Mode On during the full bin state. A lower ice level in dispensers will prevent overfilling or dispense wheel or motor damage. • The bin probe reads actual temperature and must be connected to the T5 terminal on the control board. • The control board recognizes the bin level probe automatically when installed.
Troubleshooting: Refer to normal operation before troubleshooting - The T5 thermistor reading must indicate 36° F or less in the freeze cycle and throughout the harvest cycle to shutoff on full bin at the end of the harvest cycle. View the T5 thermistor temperature on the touch screen (menu/service/diagnostics/temperatures). PROBE SHORTED - TEMPERATURE DISPLAYED IS ABOVE 400° F: A shorted bin level probe wire/thermistor will indicate a temperature higher than 400° F.
THERMISTORS FUNCTION Thermistor resistance values change with temperature. The value supplied to the control board is used to identify temperature at the thermistor location.
Thermistor Matrix Four thermistors are standard on the ice machine. They are labeled T1, T2, T3, T4. Three additional thermistors are available as an option and measure ice bin level, potable water supply temperature and air temperature entering the condenser.
SYMPTOM The alert log indicates a T1, T2, T3, or T4 Fault. CHECK PROCEDURE NOTE: Navigate to Menu/Service/Data/Real Time data/ Time & Temperature NOTE: An open thermistor will display -10°F (-23°C) and a shorted thermistor displays 400°F (204°C). Thermistor Test 1. Disconnect the suspect thermistor from the control board and swap with another thermistor. A. The symptoms move with the thermistor Replace the thermistor. B. The symptom does not change - Perform control board test. Control Board Test 1.
HIGH PRESSURE CUTOUT (HPCO) CONTROL FUNCTION Stops the ice machine if subjected to excessive high-side pressure. The HPCO control is normally closed, and opens on a rise in discharge pressure. SPECIFICATIONS R404A R410A Specifications Cut-Out Cut-In 450 psig ±7 300 psig ±10 (3102 kPa ±48 (2068 kPa ±69 31 bar ±0.48) 20.68 bar ±0.69) 600 psig ±10 450 psig ±10 (3147 kPa ±69) (3103 kPa ±69) Automatic Reset Opening the HPCO will initiate the 5 minute compressor time delay.
LOW PRESSURE CUTOUT (LPCO) CONTROL FUNCTION Supplies or interrupts power to the compressor time delay when suction pressure rises above or falls below setpoint. The LPCO control is closed at pressures above setpoint and opens at pressures below setpoint. R404A R410A Specifications Cut-Out 12 psig ±3 20 psig ±3 Cut-In 35 psig ±5 50 psig ±5 CHECK PROCEDURE Opening the LPCO will initiate the 5 minute compressor time delay relay.
COMPRESSOR TIME DELAY FUNCTION Supplies or interrupts power to the compressor contactor coil. The time delay starts whenever line voltage is removed/reapplied; The contact closes when the delay period ends. Contact SPST Normally open Specifications Delay Period 300 seconds (5 minutes) +35%/-15% CHECK PROCEDURE 1. Verify line voltage is supplied to the condensing unit. 2. Disconnect/reconnect power to the condensing unit and test for line voltage at terminals 2 & 3.
FAN CYCLE CONTROL FUNCTION Cycles the fan motor on and off to maintain proper operating discharge pressure. The fan cycle control closes on an increase, and opens on a decrease in discharge pressure. SPECIFICATIONS Model CVDF0600 CVDF0900 CVDF1400 CVDF1800 CVDF2100 CVDT1200 Specifications Cut-In (Close) 250 psig ±5 (1723 kPa ±34) (17.23 bar ±.34) 335 psig ±5 2310 kPa ±34 (23.10 bar ±.34) Cut-Out (Open) 200 ±5 (1517 kPa ±34) (15.17 bar ±.34) 275 psig ±5 1896 kPa ±34 (18.96 bar ±.34) CHECK PROCEDURE 1.
HARVEST ASSIST AIR PUMP FUNCTION The air pump helps break the vacuum between the sheet of ice and the evaporator which results in shorter harvest cycles. SPECIFICATIONS 115 Volt or 230 Volt - matches the ice machine voltage. CHECK PROCEDURE 1. The air pump is wired in parallel with the harvest valve - Verify the ice machine is in the harvest cycle and the harvest valve is energized. 2.
COMPRESSOR ELECTRICAL DIAGNOSTICS The compressor does not start or will trip repeatedly on overload. Check Resistance (Ohm) Values NOTE: Compressor windings can have very low ohm values. Use a properly calibrated meter. Perform the resistance test after the compressor cools. The compressor dome should be cool enough to touch (below 120°F/49°C) to assure that the overload is closed and the resistance readings will be accurate. SINGLE PHASE COMPRESSORS 1.
CHECK MOTOR WINDINGS TO GROUND Check continuity between all three terminals and the compressor shell or copper refrigeration line. Scrape metal surface to get good contact. If continuity is present, the compressor windings are grounded and the compressor should be replaced. COMPRESSOR DRAWING LOCKED ROTOR To determine if the compressor is seized, check the amp draw while the compressor is trying to start. The two likely causes of this are a defective starting component or a mechanically seized compressor.
DIAGNOSING START COMPONENTS If the compressor attempts to start, or hums and trips the overload protector, check the start components before replacing the compressor. Capacitor Visual evidence of capacitor failure can include a bulged terminal end or a ruptured membrane. Do not assume a capacitor is good if no visual evidence is present. A good test is to install a known good substitute capacitor. Use a capacitor tester when checking a suspect capacitor.
Refrigeration Components HEAD PRESSURE CONTROL VALVE Manitowoc remote systems require head pressure control valves with special settings. Replace defective head pressure control valves only with “original” Manitowoc replacement parts. Refrigerant Charge Verification The correct amount of refrigerant (name plate charge) is required to operate correctly at all ambient conditions.
Freeze Cycle Operation All Models The head pressure control valve is non adjustable. At ambient temperatures of approximately 70°F (21°C) or above, refrigerant flows through the valve from the condenser to the receiver inlet. At temperatures below this (or at higher temperatures if it is raining), the head pressure control dome’s nitrogen charge closes the condenser port and opens the bypass port from the compressor discharge line.
Diagnostics FREEZE CYCLE - QUIETQUBE® REMOTE CONDENSING UNIT 1. Determine if the coil is clean. 2. Determine the air temperature entering the condenser. 3. Determine if the head pressure is high or low in relationship to the outside temperature. (Refer to the proper “Cycle Times/24-Hour Ice Production/ Refrigerant Pressure Charts” on page 183.) 4. Determine the temperature of the liquid line entering the receiver by feeling it. This line is normally warm; “body temperature.” 5.
Harvest Cycle QUIETQUBE® REMOTE CONDENSING UNIT QuietQube® ice machines may fail in the harvest cycle when the refrigerant charge and ambient temperature create a marginal undercharge of refrigerant. The ice machine may be able to make a full sheet of ice, but fails in the harvest cycle when the receiver runs out of liquid refrigerant. A E02 Long Harvest will result when the ice machine is unable to harvest.
HARVEST CYCLE DIAGNOSTICS QUIETQUBE® REMOTE CONDENSING UNIT The head pressure control valve diverts the compressor discharge gas to the ice machine receiver in the harvest cycle. All refrigerant flow through the condenser in the harvest cycle stops. Symptoms of a head pressure control valve that will not seat 100% closed (completely bypass the condenser) in the harvest cycle are: • Freeze cycle suction and discharge pressure are normal.
Step 3 Details Grasp Here with Hands to Compare Temperatures No Flow R ef w t Flo n a r rige LIQUID LINE FROM CONDENSER HARVEST CYCLE HEAD PRESSURE CONTROL VALVE FAILURE LIST Temperature of the compressor discharge line and liquid line to the ice machine receiver feel the same 30 seconds into the harvest cycle. • The head pressure control valve is functioning correctly. The compressor discharge line is noticeably warmer than the liquid line to the ice machine receiver.
SUCTION ACCUMULATOR OPERATION Liquid refrigerant collects in the suction accumulator during the harvest cycle and is removed during the freeze cycle. The liquid refrigerant is returned to the compressor through a screen and orifice in the suction accumulator J tube. Passing the liquid through the orifice causes a pressure drop; the liquid flashes to a vapor and creates a refrigeration affect. It is normal to see frost on the accumulator, suction line and compressor suction port in the freeze cycle.
Recovery/Evacuation/Charging Procedures QuietQube® Models Do not purge refrigerant to the atmosphere. Capture refrigerant using recovery equipment. Follow the manufacturer’s recommendations. Notice Manitowoc Ice assumes no responsibility for the use of contaminated refrigerant. Damage resulting from the use of contaminated refrigerant is the sole responsibility of the servicing company. Notice Replace the liquid line drier after recovering the refrigerant and before evacuating and recharging.
CONNECTIONS Manifold gauge sets must utilize low loss fittings to comply with U.S. Government rules and regulations. CVD condensing units with reciprocating compressors are manufactured with a check valve in the compressor discharge line. The check valve requires an additional connection on the condensing unit during evacuation or recovery procedures.
RECOVERY/EVACUATION PROCEDURES 1. Press the power button to stop the ice machine and disconnect all power to the ice machine and condensing unit. 2. Install manifold gauges, charging scale, and recovery unit or two-stage vacuum pump. 3. Open high and low side on the manifold gauge set. 4. Perform recovery or evacuation: A. Recovery: Operate the recovery unit as directed by the manufacturer’s instructions. B. Pressure test the system. C. Evacuation prior to recharging: Evacuate to 500 microns.
CHARGING PROCEDURES 1. The ice machine must be off. 2. Close the vacuum pump valve and the low side manifold gauge valve. 3. Open the refrigerant cylinder and add the proper refrigerant charge (shown on nameplate) into the system high side (receiver service valve and discharge line shut-off valve). 4. If the high side does not take the entire charge, close the high side on the manifold gauge set.
System Contamination Clean-Up General This section describes the basic requirements for restoring contaminated systems to reliable service. Notice Routine adjustments and maintenance procedures Manitowoc Ice assumes no responsibility for the use of contaminated refrigerant. Damage resulting from the use of contaminated refrigerant is the sole responsibility of the servicing company.
CONTAMINATION CLEANUP CHART Symptoms/Findings No symptoms or suspicion of contamination Moisture/Air Contamination symptoms Refrigeration system open to atmosphere for longer than 15 minutes Refrigeration test kit and/or acid oil test shows contamination No burnout deposits in open compressor lines Mild Compressor Burnout symptoms Oil appears clean but smells acrid Refrigeration test kit or acid oil test shows harmful acid content No burnout deposits in open compressor lines Severe Compressor Burnout sympt
CLEANUP PROCEDURE Mild System Contamination 1. Replace any failed components. 2. If the compressor is good, change the oil. 3. Replace the liquid line drier. NOTE: If the contamination is from moisture, use heat lamps during evacuation. Position them at the compressor, condenser and evaporator prior to evacuation. Do not position heat lamps too close to plastic components, or they may melt or warp. Important Dry nitrogen is recommended for this procedure. This will prevent refrigerant release. 4.
Severe System Contamination 1. Remove the refrigerant charge. 2. Remove the compressor and inspect the refrigeration lines. If burnout deposits are found, install a new harvest valve and TXV. 3. Wipe away any burnout deposits from suction and discharge lines at compressor. 4. Sweep through the open system with dry nitrogen. Important Refrigerant sweeps are not recommended, as they release refrigerant into the atmosphere. 5. Install a new compressor and new start components. 6.
9. Follow the normal evacuation procedure, except replace the evacuation step with the following: A. Pull vacuum to 1000 microns. Break the vacuum with dry nitrogen and sweep the system. Pressurize to a minimum of 5 psig (35 kPa, .35 bar). B. Change the vacuum pump oil. C. Pull vacuum to 500 microns. Break the vacuum with dry nitrogen and sweep the system. Pressurize to a minimum of 5 psig (35 kPa, .35 bar). D. Change the vacuum pump oil. E. Pull vacuum to 500 microns.
LIQUID LINE FILTER-DRIERS The filter-driers used on Manitowoc ice machines are manufactured to Manitowoc specifications. A Manitowoc drier has dirt-retaining filtration, with fiberglass filters on both the inlet and outlet ends. This is very important because ice machines have a back-flushing action that takes place during every Harvest cycle. The size of the filter-drier is important. The refrigerant charge is critical.
REPLACING PRESSURE CONTROLS WITHOUT REMOVING REFRIGERANT CHARGE This procedure reduces repair time and cost. Use it when any of the following components require replacement, and the refrigeration system is operational and leak-free. • Fan cycle control • High pressure cut-out control • Low Pressure cut-out control • High side service valve • Low side service valve Important This is a required in-warranty repair procedure. 1. Disconnect power to the ice machine. 2.
Total System Refrigerant Charge QuietQube® CVD Models Ice machines listed with an F in the model number use R404A refrigerant - Ice machines listed with a T in the model number use R410A. This information is for reference only. Refer to the ice machine model/serial label to verify the system charge and refrigerant type. Serial plate information overrides the information listed in this chart.
Model Condensing Unit IF1800C CVDF1800 IF2100C CVDF2000 Refrigerant Charge 15.00 lbs. 6.80 kg 17.00 lbs 7.71 kg 18.00 lbs. 8.16 kg 22.00 lbs 9.98kg Part Number: 000015431 Rev 02 6/20 Line Set Length 0-50 ft. 0-15 m 51-100 ft. 15-30 m 0-50 ft. 0-15 m 51-100 ft.
THIS PAGE INTENTIONALLY LEFT BLANK 182 Part Number: 000015431 Rev 02 6/20
Charts Cycle Times/24-Hour Ice Production/ Refrigerant Pressure Charts These charts are used as guidelines to verify correct ice machine operation. Accurate collection of data is essential to obtain the correct diagnosis. • Production and cycle times are for dice cube - Half dice cube cycle times can be 2 - 3 minutes faster, depending on model and ambient temperature. • Regular cube production derate is 7%. • Ice production checks that are within 10% of the chart are considered normal.
IF0600C/CVDF0600 Remote Air-Cooled Condensing Unit Model Characteristics vary depending on operating conditions. All data on this page is preliminary and subject to change Cycle Times Freeze Time + Harvest Time = Total Cycle Time Air Temp. Freeze Time Entering Water Temperature °F/°C Condenser 50/10 70/21 90/32 °F/°C -20 to 70/ 8.9-10.2 9.5-11.0 10.3-11.9 -29 to 21 80/27 9.3-10.7 10.0-11.5 10.9-12.5 90/32 9.6-11.1 10.4-12.0 11.4-13.0 100/38 10.2-11.8 11.1-12.8 12.2-13.9 110/43 11.0-12.6 12.0-13.8 13.2-15.
IBF0620C/CVDF0600 Remote Air-Cooled Condensing Unit Model Characteristics vary depending on operating conditions. All data on this page is preliminary and subject to change Cycle Times Freeze Time + Harvest Time = Total Cycle Time Air Temp. Freeze Time Entering Water Temperature °F/°C Condenser 50/10 70/21 90/32 °F/°C -20 to 70/ 8.9-10.2 9.5-11.0 10.3-11.9 -29 to 21 80/27 9.3-10.7 10.0-11.5 10.9-12.5 90/32 9.6-11.1 10.4-12.0 11.4-13.0 100/38 10.2-11.8 11.1-12.8 12.2-13.9 110/43 11.0-12.6 12.0-13.8 13.2-15.
IBF0820C/CVDF0900 Remote Air-Cooled Condensing Unit Model Characteristics vary depending on operating conditions. All data on this page is preliminary and subject to change Cycle Times Freeze Time + Harvest Time = Total Cycle Time Air Temp. Freeze Time Entering Water Temperature °F/°C Condenser 50/10 70/21 90/32 °F/°C -20 to 70/ 8.5-9.8 9.3-10.7 10.0-11.5 -29 to 21 90/32 9.5-11.0 10.8-12.4 11.4-13.1 100/38 11.2-12.9 12.3-14.1 13.3-15.2 110/43 13.0-14.9 14.0-16.0 14.9-17.
IF0900C/CVDF0900 Remote Air-Cooled Condensing Unit Model Characteristics vary depending on operating conditions. All data on this page is preliminary and subject to change Cycle Times Freeze Time + Harvest Time = Total Cycle Time Air Temp. Freeze Time Entering Water Temperature °F/°C Condenser 50/10 70/21 90/32 °F/°C -20 to 70/ 8.9-10.3 9.4-14.4 10.1-11.6 -29 to 21 90/32 9.8-11.3 10.4-12.0 11.2-12.9 100/38 11.0-12.7 11.9-13.6 12.8-14.6 110/43 12.5-14.4 13.4-15.4 14.3-16.
IBT1020C/CVDT1200 Remote Air-Cooled Condensing Unit Model Characteristics vary depending on operating conditions. Cycle Times Freeze Time + Harvest Time = Total Cycle Time Air Temp. Freeze Time Entering Water Temperature °F/°C Condenser 50/10 70/21 90/32 °F/°C -20 to 70/ 6.2-7.2 6.5-7.8 7.4-8.8 -29 to 21 80/27 6.4-7.7 6.8-8.1 7.8-9.2 90/32 6.7-8.1 7.3-8.7 7.9-9.5 100/38 7.1-8.5 7.8-9.2 8.9-10.6 110/43 8.2-9.7 8.7-10.3 10.0-11.9 1 Times in minutes - Dice cube Harvest Time .75-2.
IT1200C/CVDT1200 Remote Air-Cooled Condensing Unit Model Characteristics vary depending on operating conditions. Cycle Times Freeze Time + Harvest Time = Total Cycle Time Air Temp. Freeze Time Entering Water Temperature °F/°C Condenser 50/10 70/21 90/32 °F/°C -20 to 70/ 6.4-7.7 7.4-8.8 7.8-9.4 -29 to 21 80/27 7.2-8.6 7.7-9.1 8.2-9.7 90/32 7.6-9.0 8.0-9.5 8.8-10.4 100/38 8.3-9.9 8.5-10.1 9.9-11.8 110/43 8.9-10.6 9.7-11.5 10.5-12.4 1 Times in minutes - Dice cube Harvest Time .75-2.
IF1400C/CVDF1400 Remote Air-Cooled Condensing Unit Model Characteristics vary depending on operating conditions. All data on this page is preliminary and subject to change Cycle Times Freeze Time + Harvest Time = Total Cycle Time Air Temp. Freeze Time Entering Water Temperature °F/°C Condenser 50/10 70/21 90/32 °F/°C -20 to 70/ 11.3-13.4 12.3-14.6 14.2-16.8 -29 to 21 90/32 12.8-15.2 13.7-16.3 16.0-18.9 100/38 13.8-16.3 15.8-18.7 17.1-20.2 110/43 14.7-17.4 16.9-19.9 18.2-21.
IF1800C/CVDF1800 Remote Air-Cooled Condensing Unit Model Characteristics vary depending on operating conditions. All data on this page is preliminary and subject to change Cycle Times Freeze Time + Harvest Time = Total Cycle Time Air Temp. Freeze Time Entering Water Temperature °F/°C Condenser 50/10 70/21 90/32 °F/°C -20 to 70/ 11.5-12.6 15.5-14.4 14.3-15.6 -29 to 21 90/32 14.3-15.5 16.4-17.8 17.7-19.3 100/38 15.4-16.8 17.7-19.3 19.3-20.9 110/43 11.5-12.6 15.5-14.4 14.3-15.
IF2100C/CVDF2100 Remote Air-Cooled Condensing Unit Model Characteristics vary depending on operating conditions. Cycle Times All data on this page is preliminary Freeze Time + Harvest Time = Total Cycle Time Air Temp. Freeze Time Entering Water Temperature °F/°C Condenser 50/10 70/21 90/32 °F/°C -20 to 70/ 10.4-11.4 11.4-12.4 12.3-13.4 -29 to 21 80/27 11.3-12.3 12.1-13.2 13.2-14.4 90/32 11.6-12.6 12.4-13.5 14.2-15.4 100/38 12.8-13.9 13.9-15.1 15.3-16.6 110/43 13.9-15.1 14.9-16.2 16.0-17.
Diagrams Wiring Diagrams The following pages contain electrical wiring diagrams. Be sure you are referring to the correct diagram for the ice machine you are servicing. nWarning Always disconnect power before working on electrical circuitry. Some components are wired differently on energy efficient machines. Please verify your model number (“Model Numbers” on page 19) to reference the correct diagrams.
49 57 22 L1 (8) WHT 41 34 GND 3 (9) GRN 32 (55) BRN 28 54 19 34 (56) WHT (58) ORG (57) GRY (60) BLK (61) RED (20) YEL (83) ORG (98) BLK (76) BLK (77) RED (28) RED (21) BLU 45 58 55 42 1 56 (97)WHT (81) WHT (99) WHT (22) WHT (27) WHT (82)WHT (75) WHT 000014655_02 (80) WHT N QuietQube® Ice Machine Head Section IF0600C/IBF0620C/IBF0820C/IF0900C 1PH Part Number: 000015431 Rev 02 6/20
IF0600C/IBF0620C/IBF0820C/IF0900C/IT0900C 1Ph Number 1 3 19 22 32 34 41 42 45 49 54 55 56 57 58 Component Air Pump Harvest Assist Bin Switch Control Board Touchscreen Ice Thickness Probe LED See Control Board Schematic For Detail Solenoid Valve - Harvest Solenoid Valve - Liquid Line Thermistors Transformer Control Board Water Dump Valve Water Inlet Valve Water Level Probe Water Pump Wire Colors BLK Black BLU Blue BRN Brown GRY Grey ORG Orange PRPL Purple RED Red WHT White YEL Yellow Refer to control board
49 57 22 L1 (8) WHT 41 34 GND 3 (9) GRN 32 (55) BRN 28 54 19 34 (56) WHT (58) ORG (57) GRY (60) BLK (61) RED (20) YEL (83) ORG (98) BLK (76) BLK (28) RED (77) RED (28) RED (29) RED (21) BLU 45 58 55 1 42 1 43 56 (97)WHT (81) WHT (99) WHT (22) WHT (27) WHT (27) WHT (30) WHT (82)WHT (75) WHT 000014655_02 (80) WHT N QuietQube® Ice Machine Head Section IT1200C/IBT1020C 1PH Part Number: 000015431 Rev 02 6/20
IT1200C/IBT1020C 1PH Number 1 3 19 22 32 34 41 42 43 45 49 54 55 56 57 58 Component Air Pump Harvest Assist Bin Switch Control Board Touchscreen Ice Thickness Probe LED See Control Board Schematic For Detail Solenoid Valve - Harvest Solenoid Valve - Harvest Solenoid Valve - Liquid Line Thermistors Transformer Control Board Water Dump Valve Water Inlet Valve Water Level Probe Water Pump Wire Colors BLK Black BLU Blue BRN Brown ORG Orange RED Red WHT White YEL Yellow Refer to control board schematic for cont
49 57 22 L1 (8) WHT 41 34 GND 3 (9) GRN 32 (55) BRN 28 54 19 34 (56) WHT (58) ORG (57) GRY (60) BLK (61) RED (20) BLU (62) RED/WHT (83) ORG (98) GRY (76) BLK (91) RED (27) RED (21) BLU (25) RED (77) RED/WHT (75)WHT 45 58 55 42 1 56 1 43 (92) WHT (22) WHT N (82)WHT (80) WHT (79) WHT (99) WHT (82) WHT (28) WHT (26) WHT (80)WHT 000015237_00 N QuietQube® Ice Machine Head Section IF1400C/IF1800C/IF2100C 1PH Part Number: 000015431 Rev 02 6/20
IF1400/IF1800C/IF2100C 1ph Number 1 3 19 22 32 34 41 42 43 45 49 54 55 56 57 58 Component Air Pump Harvest Assist Bin Switch Control Board Touchscreen Ice Thickness Probe LED See Control Board Schematic For Detail Solenoid Valve - Harvest Left Hand Solenoid Valve - Harvest Right Hand Solenoid Valve - Liquid Line Thermistors Transformer Control Board Water Dump Valve Water Inlet Valve Water Level Probe Water Pump Wire Colors BLK Black BLU Blue BRN Brown GRY Grey ORG Orange RED Red WHT White Refer to control
L1 GRND 200 18 (43) BLK BLK PRPL 7 BLK 29 BLK PRPL 31 5 RED YEL BLU 36 BLU 15 14 8 (44) BLU (46) RED 12 11 17 18 2 1 (75) RED 000014543_01 (50) BLU (74) RED (76) YEL 3 10 L2 QuietQube® CVD Condensing Unit CVD 1PH CONDENSING UNIT Part Number: 000015431 Rev 02 6/20
CVD 1PH Condensing Unit Number 5 7 8 10 11 12 14 15 17 18 31 36 BLK BLU PRPL RED YEL Component Compressor Compressor Overload Compressor Potential Relay Compressor Time Delay Relay Compressor Run Capacitor Compressor Start Capacitor Condenser Fan Motor Condenser Fan Motor Run Capacitor Contactor Contacts Contactor Coil High Pressure Cutout Low Pressure Cutout Wire Colors Black Blue Purple Red Yellow Part Number: 000015431 Rev 02 6/20 201
YEL BLK L1 L2 5 RED 17 L3 (75) RED GRND BLK PRPL 25 31 BLK PRPL BLU 36 BLU 15 14 18 1 (75) RED 2 000014543_01 (74) RED (76) YEL 3 10 QuietQube® CVD Condensing Unit CVD 3PH CONDENSING UNIT Part Number: 000015431 Rev 02 6/20
CVD 3PH Condensing Unit Number 5 10 14 15 17 18 31 36 BLK BLU PRPL RED YEL Component Compressor Compressor Time Delay Relay Condenser Fan Motor Condenser Fan Motor Run Capacitor Contactor Contacts Contactor Coil High Pressure Cutout Low Pressure Cutout Wire Colors Black Blue Purple Red Yellow Part Number: 000015431 Rev 02 6/20 203
Electronic Control Board 3 75 74 34-10 34-9 71 34-1 34-2 34-3 34-4 70 34-5 34-6 34-7 34-8 2 38 72 22 34 73 34 58 34 56 57 34 49-1 33 49-2 5 28 42 34 55 34 43 204 49-7 49-6 49-4 49-5 49-3 31 1 4 7 2 5 8 3 6 9 Part Number: 000015431 Rev 02 6/20
Electronic Control Board Schematic Number 2 3 5 22 28 31 33 34 34-1 34-2 34-3 34-4 34-5 34-6 34-7 34-8 34-9 34-10 38 42 43 49-1 49-2 49-3 49-4 49-5 49-6 49-7 55 56 57 58 70 71 72 73 74 75 Description iAuCS Bin Switch Compressor Contactor Coil Relay Touchscreen Fuse High Pressure Cutout Ice Thickness Probe LED - Relays LED - Display LED - Micro LED - Clean LED - Harvest LED - Ice Thickness Probe LED - High Water Probe LED - Low Water Probe LED - Display Bypass Is Active LED - Right Bin Switch LED - Left Bi
Refrigeration Tubing Schematics IF0600C/CVDF0600 IB0620C/CVDF0600 IBF0820/CVDF0900 IF0900C/CVDF0900 17 2 18 1 3 4 16 5 15 11 13 T4 12 T3 14 10 9 8 T2 T1 6 7 206 Part Number: 000015431 Rev 02 6/20
IF0600C/CVDF0600 IB0620C/CVDF0600 IBF0820/CVDF0900 IF0900C/CVDF0900 Number 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 T1 T2 T3 T4 Component Compressor Discharge Check Valve Condenser - Remote Air-Cooled Head Pressure Control Valve Liquid Line Shut-off Valve Liquid Line Check Valve Receiver Receiver Access Valve Liquid Line Filter Drier Liquid Line Solenoid Valve Heat Exchanger TXV - Thermostatic Expansion Valve Evaporator Harvest Solenoid Valve Suction Shut-off Valve S Trap - Required on 21’ or greater r
IBT1020C/CVDT1200 IT1200C/CVDT1200 1 17 2 3 4 18 16 5 15 14 12 T4 11 T3 14 10 12 9 T2 8 208 13 T1 7 6 Part Number: 000015431 Rev 02 6/20
IBT1020C/CVDT1200 IT1200C/CVDT1200 Number 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 T1 T2 T3 T4 Component Compressor Discharge Check Valve Condenser - Remote Air-Cooled Head Pressure Control Valve Liquid Line Shut-off Valve Liquid Line Check Valve Receiver Receiver Access Valve Liquid Line Filter Drier Liquid Line Solenoid Valve Heat Exchanger TXV - Thermostatic Expansion Valve Evaporator Harvest Solenoid Valve Suction Shut-off Valve S Trap - Required on 21’ or greater rise Suction line Filter Accumulat
Dual Evaporators IF1400C/IF1800C 17 2 1 18 3 4 16 15 5 11 13 12 14 14 8 13 T3 12 10 9 T4 T2 T1 6 7 210 Part Number: 000015431 Rev 02 6/20
IF1400C/IF1800 Number 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 T1 T2 T3 T4 Component Compressor Discharge Check Valve Condenser - Remote Air-Cooled Head Pressure Control Valve Liquid Line Shut-off Valve Liquid Line Check Valve Receiver Receiver Access Valve Liquid Line Filter Drier Liquid Line Solenoid Valve Heat Exchanger TXV - Thermostatic Expansion Valve Evaporator Harvest Solenoid Valve Suction Shut-off Valve S Trap - Required on 21’ or greater rise Suction line Filter Accumulator Thermistor - Rece
IF2100C 17 1 18 4 2 3 16 5 15 14 T4 13 12 14 11 11 12 12 T3 12 13 10 9 T2 7 212 T1 6 Part Number: 000015431 Rev 02 6/20
IF2100C Number 1 2 3 4 5 6 7 9 10 11 12 13 14 15 16 17 18 T1 T2 T3 T4 Component Compressor Discharge Check Valve Condenser - Remote Air-Cooled Head Pressure Control Valve Liquid Line Shut-off Valve Liquid Line Check Valve Receiver Liquid Line Filter Drier Liquid Line Solenoid Valve Heat Exchanger TXV - Thermostatic Expansion Valve Evaporator Harvest Solenoid Valve Suction Shut-off Valve S Trap - Required on 21’ or greater rise Suction line Filter Accumulator Thermistor - Receiver Inlet Thermistor - Receive
THIS PAGE INTENTIONALLY LEFT BLANK 214 Part Number: 000015431 Rev 02 6/20
MANITOWOC ICE 2110 SOUTH 26TH STREET MANITOWOC, WI 54220 844-724-2273 WWW.MANITOWOCICE.COM ©2020 Welbilt Inc. except where explicitly stated otherwise. All rights reserved.