Specifications

140 Part Number STH025 02/12
SUCTION PRESSURE LOW CHECKLIST
Improper Installation
Refer to “Installation/Visual Inspection Checklist”
(page 131)
Discharge Pressure
Discharge pressure is too low and is affecting low
side – refer to “Freeze Cycle Discharge Pressure
Low Checklist” (page 137)
Improper Refrigerant Charge
Undercharged
Wrong type of refrigerant
Other
Non-Manitowoc components in system
Improper water supply over evaporator – refer to
“Water System Checklist” (page 132)
Restricted/plugged liquid line drier
Restricted/plugged tubing in suction side of
refrigeration system
TXV starving - continue the table