Water Regulating Valve
Problem (Freeze Cycle)
Valve not maintaining discharge pressure.
Valve incorrectly set, dirty or defective. Adjust
valve to correct discharge pressure for your model
(refer to cycle times/24 hour productions charts),
clean or replace valve.
Discharge pressure extremely high; Liquid line
entering receiver feels hot.
Water regulating valve incorrectly set or not
opening
Insufficient water volume - undersized/kinked
lines, mineral or scale buildup in lines. Verify Head
Pressure Control Valve operation before changing
water regulating valve.
Discharge pressure low, Liquid line entering
receiver feels warm to hot.
Ice machine low on charge. Verify Total System
Refrigerant Charge
page 220.