Service manual
Electrical System Section 6
6-14
Part No. 80-1206-3
ELECTRONIC BIN THERMOSTAT
Function
The temperature control opens the bin switch circuit
when ice contacts the sensor. When ice no longer
contacts the sensor, the circuit closes and the ice
machine starts.
Specifications
Setpoint Range: -30 to 212°F (-34 - 100°C)
Control Location
CONTROL SETTINGS
Verify control is set properly before proceeding..
Positioning the Touchpad Jumper
The P5 jumper position determines if the touchpad is
locked or unlocked. The control is factory locked; to
unlock move the jumper from one pin to two pins.
Inside of Bin Thermostat Control
Setting Control Setpoint Value
To view and adjust setpoint, follow these steps:
1. Press MENU until the display flashes SP.
2. Press MENU again to display the existing setpoint
value.
3. Press Up or Down (arrows) to change the setpoint
value.
4. Press MENU again to save the new value. The
display returns to the sensed temperature.
NOTE: If no setup entry is made for 30 seconds, the
control reverts to the normal temperature display.
Display Function Preset Settings
SP Set Point 40
DIF Differential 1
ASD Anti-Short Cycle Delay 1
OFS Temperature Offset 0
SF Sensor Failure Mode 1
CONTROL
LOCATION
Important
If MENU is not pressed after changing the setpoint
value, the control reverts to the previously
programmed setpoint value.
115V
240V
COM
NC
NO
C
P5
P5
RED LEAD
SENSOR
PROBE
BLACK
LEAD
SENSOR
PROBE
MATCH
WIRING
TO ICE
MACHINE
VOLTAGE
WHITE LEAD
BIN SWITCH
or TOGGLE
SWITCH
WIRE
RED LEAD
BIN SWITCH
or TOGGLE
SWITCH
WIRE
KEYPAD
JUMPER
LOCATION